Page 6
Optima 829 Series
•
–PSW = inlet power is monitored, outlets are switched
•
–NSW = inlet power is not monitored, outlets are switched
•
000 is a dash number allowing for future variations
1.7 Product Ratings
By model number, the following are the corresponding inlet and outlet ratings.
Model
Inlet Rating
Outlet Ratings
829001
829002
829009
829010
100–240 Vac, 1
ɸ
, 50/60 Hz
16 A continuous
(20 A maximum)
•
100–240 Vac, 1
ɸ
, 12 A continuous (15 A max.) per C13 receptacle
•
100–240 Vac, 1
ɸ
, 16 A continuous (20 A max.) per C19 receptacle
•
16 A continuous (20 A max.) total per unit (regardless of receptacle
count used)
829003
829011
200–240 Vac, 1
ɸ
, 50/60 Hz
16 A continuous
(20 A maximum)
•
200–240 Vac, 1
ɸ
, 12 A continuous (15 A max.) per C13 receptacle
•
200–240 Vac, 1
ɸ
, 16 A continuous (20 A max.) per C19 receptacle
•
16 A continuous (20 A max.) total per unit (regardless of receptacle
count used)
829004
829012
200–240 Vac, 1
ɸ
, 50/60 Hz
24 A continuous
(30 A maximum)
•
200–240 Vac, 1
ɸ
, 12 A continuous (16 A max.) per C13 receptacle
•
200–240 Vac, 1
ɸ
, 16 A continuous (20 A max.) per C19 receptacle
•
16 A continuous (20 A max.) total per outlet group (regardless of
receptacle count used)
•
24 A continuous (30 A max.) total per unit (regardless of receptacle
count used)
829005
829013
100–120 Vac, 1
ɸ
, 50/60 Hz
12 A continuous
(15 A maximum)
•
100–120 Vac, 1
ɸ
, 12 A continuous (15 A max.) per 5-15R receptacle
•
12 A continuous (20 A max.) total per unit (regardless of receptacle
count used)
829006
829007
829014
829015
100–120 Vac, 1
ɸ
, 50/60 Hz
16 A continuous
(20 A maximum)
•
100–120 Vac, 1
ɸ
, 12 A continuous (15 A max.) per 5-15R receptacle
•
16 A continuous (20 A max.) total per unit (regardless of receptacle
count used)
829008
829016
100–120 Vac, 1
ɸ
, 50/60 Hz
24 A continuous
(30 A maximum)
•
100–120 Vac, 1
ɸ
, 16 A continuous (20 A max.) per 5-20R receptacle
•
16 A continuous (20 A max.) total per outlet group (regardless of
receptacle count used)
•
24 A continuous (30 A max.) total per unit (regardless of receptacle
count used)