4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table
below.
Symptom
Possible Cause
Remedy
The AC input power is not
connected well.
Check if input power cord
firmly connected to the
mains.
No indication and alarm even
though the mains is normal.
The AC input is connected
to the UPS output.
Plug AC input power cord
to AC input correctly.
The icon
and
flashing on
LCD display and alarm is sounding
every second.
Line and neutral
conductors of UPS input
are reversed.
Rotate mains power socket
by 180° and then connect
to UPS system.
The icon
and
flashing
on LCD display and alarm is
sounding every second.
The external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.
Fault code is shown as 27 and the
icon
is lighting on LCD
display and alarm is continuously
sounding.
Battery voltage is too high
or the charger is fault.
Contact your dealer.
Fault code is shown as 28 and the
icon
is lighting on LCD
display and alarm is continuously
sounding.
Battery voltage is too low
or the charger is fault.
Contact your dealer.
UPS is overloaded.
Remove excess loads from
UPS output.
UPS is overloaded. Devices
connected to the UPS are
fed directly by the
electrical network via the
Bypass.
Remove excess loads from
UPS output.
The icon
and
is
flashing on LCD display and alarm
is sounding twice every second.
After repetitive overloads,
the UPS is locked in the
Bypass mode. Connected
devices are fed directly by
the mains.
Remove excess loads from
UPS output first. Then shut
down the UPS and restart
it.
Fault code is shown as 43 and The
icon
is lighting on LCD
display and alarm is continuously
sounding.
The UPS shut down
automatically because of
overload at the UPS
output.
Remove excess loads from
UPS output and restart it.
Fault code is shown as 14 and the
icon
is lighting on LCD
display and alarm is continuously
sounding.
The UPS shut down
automatically because
short circuit occurs on the
UPS output.
Check output wiring and if
connected devices are in
short circuit status.
Maruson Technology Corporation
ULTIMA SERIES 1K-3KVA | 2012 Jan.
2. Installation and Setup
NOTE: Before installation, please inspect the unit. Be sure nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
2-1. Rear Panel View
ULT-1K(L)
IEC Type
Schuko Type
India Type
NEMA Type
ULT-2K(L)
IEC Type
Schuko Type
India Type
NEMA Type
ULT-3K(L)
IEC Type
Schuko Type
India Type
NEMA Type
1.
Output receptacles
2.
AC input
3.
Input circuit breaker