background image

Outdoor Unit 

Installation

 Page 29

 

 

 

Step 4: Connect signal and power cables

The outside unit’s terminal block is protected by 

an electrical wiring cover on the side of the unit. 

A comprehensive wiring diagram is printed on 

the inside of the wiring cover.

 WARNING

 

 

 

 

 

 

 

 

 

 

1. Prepare the cable for connection:

USE THE RIGHT CABLE 

Please choose the right cable refer to
 “ 

Cable types

” in page 23.

a.  Using wire strippers, strip the rubber 

jacket from both ends of cable to reveal 

about 40mm (1.57in) of the wires inside.

b.  Strip the insulation from the ends of the wires. 

c.  Using a wire crimper, crimp u-lugs on the 

ends of the wires.

PAY

 ATTENTION TO LIVE WIRE

While crimping wires, make sure you clearly 

distinguish the Live (“L”) Wire from other wires.

 

    

7. Insulate unused wires with PVC electrical tape.

    Arrange them so that they do not touch any

    electrical or metal parts.

8. Replace the wire cover on the side of the unit,

    and screw it in place.    

2. Unscrew the electrical wiring cover and remove it.

3. Unscrew the cable clamp below the terminal

    block and place it to the side.

4. Connect the wire according to the wiring 

    diagram, and firmly screw the u-lug of each 

    wire to its corresponding terminal.

5. After checking to make sure every connection is 

    secure, loop the wires around to prevent rain

    water from flowing into the terminal.   

6. Using the cable clamp, fasten the cable to the

    unit. Screw the cable clamp down tightly. 

    

1. Remove the wire cover from the unit by 
    loosening the 3 screws.
2. Dismount caps on the conduit panel.
3. Temperarily mount the conduit tubes(not 
    included) on the conduit panel.
4. Properly connect both the power supply and 
    low voltage lines to the corresponding 
    terminals on the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches
    longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.
      

BEFORE PERFORMING ANY ELECTRICAL
OR WIRING WORK, TURN OFF THE MAIN
POWER TO THE SYSTEM.

 WARNING

ALL WIRING WORK MUST BE PERFORMED 
STRICTLY IN ACCORDANCE WITH THE 
WIRING DIAGRAM LOCATED INSIDE OF 
WIRE COVER OF THE OUTDOOR UNIT .

 

 

 

 

 

 

 

 

 

 

 

 

 

CHOOSE THE RIGHT CABLE SIZE

In North America

The size of the power supply cable, signal cable, 
fuse, and switch needed is determined by the 
maximum current of the unit. The maximum 
current is indicated on the nameplate located 
on the side panel of the unit.  

NOTE:

 In North America, please choose the right 

cable size according to the Minimum Circuit 
Ampacity indicated on the nameplate of the unit. 

Cover

Screw

G

Wire Cover 

Over 1.57in.(40mm)

Terminal block

Conduit panel

Connecting cable 

Power supply cord 

Please select the appropriate through-hole according
to the diameter of the wire.

Three size hole: Small, Large, Medium

When the calbe is not fasten enough, use the
buckle to prop it up , so it can be clamped tightly. 

Buckle        

NOTE: 

If the cable clamp looks like the following,

please select the appropriate through-hole according 
to the diameter of the wire.

 

Summary of Contents for Comfort-Aire Century A-DVH09SH-0-CY

Page 1: ...www marsdelivers com Owner s Manual Installation Manual DVH Series Inverter Single Zone Ductless Mini Split DVH09SH 0 DVH09SH 1 DVH12SH 0 DVH12SH 1 DVH18SH 1 DVH24SH 1...

Page 2: ...Owner s Manual Table of Contents Safety Precautions 03 Care and Maintenance 12 Troubleshooting 14 1 Indoor unit display 07 2 Operating temperature 09 3 Other features 10 4 Setting angle of airflow 11...

Page 3: ...t 25 Outdoor Unit Installation 26 1 Select installation location 26 2 Install drain joint 27 3 Anchor outdoor unit 27 4 Connect signal and power cables 29 Refrigerant Piping Connection 30 A Note on Pi...

Page 4: ...ALL INVERTER MINI SPLITS REQUIRE 14 4 STRANDED WIRE BETWEEN THE INDOOR AND OUTDOOR UNITS NO EXCEPTIONS 14 AWG 4 C TRAY CABLE A14 4SRBTHHNBK 14 AWG 19 0147 BC 4 C THHN CONDUCTORS POWER CONTROL TRAY CAB...

Page 5: ...not insert fingers rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or pain...

Page 6: ...exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules For all electrical work follow all local and national wiring standards regulations and th...

Page 7: ...o not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the u...

Page 8: ...ot be mixed with general household waste WARNING for Using R32 R290 Refrigerant 2 2 2 2 2 When flammable refrigerant are employed appliance shall be stored in a well ventilated area where the room siz...

Page 9: ...OFF remains on when TIMER ON is set FRESH UV C lamp SWING TURBO SILENCE or SOLAR PV ECO feature is turned on for 3 seconds when TIMER OFF is set FRESH UV C lamp SWING TURBO SILENCE or SOLAR PV ECO fea...

Page 10: ...OFF is set FRESH UV C lamp SWING TURBO or SILENCE features is turned off when defrosting for cooling heating units when unit is self cleaning some units when fresh feature is turned on some units whe...

Page 11: ...2 F 15 C 30 C 5 F 86 F 0 C 50 C 32 F 122 F 0 C 52 C 32 F 126 F For special tropical models 0 C 52 C 32 F 126 F For special tropical models 15 C 50 C 5 F 122 F For models with low temp cooling systems...

Page 12: ...settings to stay comfortable This function can only be activated via remote control And the Sleep function is not available in FAN or DRY mode Press the SLEEP button when you are ready to go to sleep...

Page 13: ...do not use this function unless the remote control is lost and it is absolutely necessary To restore regular operation use the remote control to activate the unit Unit must be turned off before manua...

Page 14: ...be bad for your health Make sure to clean the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter lift it up then pull it towards yourself 3...

Page 15: ...If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the...

Page 16: ...Troubleshooting Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may o...

Page 17: ...customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following po...

Page 18: ...oor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Page 19: ...Shape Quantity PC Need to be installed on the back of main air filter by the authorized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote co...

Page 20: ...Wall Hole 4 9 90 0 5 55 5i in n 2 2 3 3m m 4 4 7 75 5i in n 1 12 2c cm m Mount Indoor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in North America Connect Piping Prepare Drain...

Page 21: ...requirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller...

Page 22: ...refrigerant piping While choosing a location be aware that you should leave ample room for a wall hole see Drill wall hole for connective piping step for the signal cable and refrigerant piping that c...

Page 23: ...ke sure to avoid wires plumbing and other sensitive components Type A Type B 101mm 4in 179mm 7 05in 136mm 5 35in 37mm 1 45in 290mm 11 4in 49mm 1 95in Right rear wall hole 65mm 2 5in Indoor unit outlin...

Page 24: ...side Right hand side Left rear Right rear Knock out Panel CAUTION Be extremely careful not to dent or damage the piping while bending them away from the unit Any dents in the piping will affect the u...

Page 25: ...the compressor or any moving parts within the unit If the unit has an auxiliary electric heater it must be installed at least 1 meter 40in away from any combustible materials To avoid getting an elect...

Page 26: ...on the back DRAIN HOSE MUST BE ON BOTTOM Make sure that the drain hose is at the bottom of the bundle Putting the drain hose at the top of the bundle can cause the drain pan to overflow which can lea...

Page 27: ...pressure to the left and right hand sides of the unit The unit should not jiggle or shift 6 Using even pressure push down on the bottom half of the unit Keep pushing down until the unit snaps onto th...

Page 28: ...that air outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Stro...

Page 29: ...bber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain j...

Page 30: ...Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DRILLING INTO C...

Page 31: ...amp down tightly 1 Remove the wire cover from the unit by loosening the 3 screws 2 Dismount caps on the conduit panel 3 Temperarily mount the conduit tubes not included on the conduit panel 4 Properly...

Page 32: ...et substances or gases other than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrig...

Page 33: ...alling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper flaring is essential to achieve an airtig...

Page 34: ...0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the pa...

Page 35: ...for at least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that...

Page 36: ...0Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump Li...

Page 37: ...Water Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If...

Page 38: ...re of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check that all refrigerant pipe connectio...

Page 39: ...ging bag Outdoor Unit 1 Cut the packing belt 2 Take the unit out of the carton 3 Remove the foam from the unit 4 Remove the packaging bag from the unit Packing Indoor unit 1 Put the indoor unit into t...

Page 40: ...r The consumer must retain a receipted bill of sale as proof of warranty period Without this proof the express warranty begins on the date of shipment from the factory REMEDY PROVIDED BY THE LIMITED E...

Page 41: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 42: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 43: ...THIS PAGE IS INTENTIONALLY LEFT BLANK...

Page 44: ...GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEO...

Reviews: