+12V DC
INPUT 1-4
N.O.
contact
GND
INPUT 1-4
N.O.
contact
Figure 2: Input Connection diagram
9.1.1.2 ID parameters
ID parameter determines time period of the pulse length to trigger the alarm. The pulse time can be
from 0,5 seconds to 9999 seconds. The default time is 0,5 seconds when the parameter value is 0.
Parameter is in seconds.
9.1.1.3 DD parameters
This parameter is used to define the delay between the time that alarm input is trigged and the time
that alarm is reported.
Parameter is in seconds.
9.1.1.4 Table of parameters
Name
Comment
IN1
Mode of operation for input 1
ID1
Input time integration delay on input 1
DD1
Time delay for alarm reporting on input 1
Table 1: IN, ID and DD parameters
Example:
'
Programming with short text messages - SMS
GSW1 PROGRAMMING TABLE
Name
Number
Description
IN1
0
Alarm activated by connecting to GND
ID1
10
Input 1 has to be valid for 10 second to trigger the alarm
DD1
15
Reporting of the alarm on input 1 is delayed by 15s
Table 2: IN, ID and DD parameters example
'
Remote programming by SMS
;IN1=0;ID1=10;DD1=15;
GND
1-4
INPUT
N.C.
contact