Non-Jacketed Cable (Bare Copper Armor)
T&B J-800, two hole one piece strap, two piece single hole, Cobra Clamp/
Saddle Clamp, two hole Copper or Steel Clips that wrap around cable. Electrical
tape may be used between cable and strap if isolation is required due to
concerns with galvanic action.
Tray
Cables laid in steel tray shall neatly arranged and be secured with steel banding
or steel ties every four feet. Cables shall be installed snug, but not excessively
where cable is damaged. Ties should be compatible with tray, cable and
environment.
Grounding
The Armor may be used as an equipment ground. For grounding equivalents,
see the VITALink® MC/RC90 General Installation and Handling Manual.
Pulling Lubricant
As acceptable by AHJ, Polywater LZ may be used for cables with polymeric
jacket.
Any lubrication non-deleterious or non-corrosive to bare copper is acceptable
for bare copper armored/sheathed cable.
Splicing
2 hour and 1 hour splices are available. Contact RSCC for details.