MR 150M–1050M - PLC CONTROLLER
MAINTENANCE
45
PAGE
31
SERVICE CHART STAGER CONTROLLER
SYMPTOM
PROBABLE CAUSE
HOW TO CORRECT
1. No electrical power.
Check circuit. Start a
regeneration with Manual
Regeneration Lever.
2. Frequency levers on Time Dial not
set properly.
Refer to “How to Set
Regeneration Cycle Program
3200 Series Mechanical Timer”.
3. Faulty timer mechanism or
defective timer motor.
Replace.
4. Defective stager drive motor.
Replace
Softener does not
regenerate.
5. Defective micro-switch in stager
drive assembly.
Replace drive assembly.
Softener regenerates as
wrong time.
6. Interrupted electrical power. Time
dial set improperly
Reset Time Dial to correct time.
Refer to “How to Set Cycle
Controller”.
7. Stager drive motor burned out.
Replace.
8. Loose Electrical connections.
Repair.
Position dial does not
rotate.
9. Jammed stager valve.
Replace.
10. Controller out of sequence due to:
A. Turning position dial manually
when time switch is not in “OFF”
position or turning the cycle
adjustment knob too quickly for
stager to index.
With time switch mechanism in
normally “OFF” position, (Red
arrowhead pointing straight
down), manually turn Position
Dial clockwise to No. 4 "Service”
position.
B Temporary low voltage condition
of poor electrical connection.
Check circuitry.
C. Jammed Stager.
Replace.
D. Defective time switch assembly.
Replace.
E. Defective time switch assembly.
Replace.
Softener Diaphragm
Valves end regeneration
cycle in wrong position.
F. Defective drive motor.
Replace.
Leak to drain from stager
valve during service.
11. Leaky or cut seal in stager valve.
Replace.
12. Faulty seal in stager valve.
Replace.
13. Clogged stager strainer.
Clean strainer.
Hardness Leakage or
Improper cycling or valves.
Individual valves not being
pressurized or vented
correctly.
14. Clogged or kinked stager tubing.
Replace tubing or clean.
Page
45
MR 150M–1050M PLC
MAINTENANCE
Summary of Contents for MR Series
Page 7: ...MR 150M 1050M PLC CONTROLLER SYSTEM INFORMATION 4 Page 4 MR 150M 1050M PLC INSTALLATION ...
Page 11: ...MR 150M 1050M PLC CONTROLLER INSTALLATION 8 TUBING DIAGRAM VALVE NEST MULTITANK ASCO SOLENOID ...
Page 36: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 33 ...
Page 37: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 34 ...
Page 38: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 35 ...
Page 39: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 36 ...
Page 40: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 37 ...
Page 41: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 38 ...
Page 42: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 39 ...
Page 51: ...MR 150M 1050M PLC CONTROLLER 48 NOTES ...
Page 52: ...2227 South Street P O Box 044170 Racine WI 53404 7003 www Marlo Inc com 8 217 R5 ...