Flow Rate Trip Point Table
Program Values for A, B, C & D
Alternating Operation
(gpm)
Parallel Operation
(gpm)
MODEL
Second Unit Trip
Flow Range
Second Unit Trip
Flow Range
*Third Unit Trip
Flow Range
Exchange
Pipe
Min
Max
Min
Max
Min
Max
Capacity
Size
A
B
A
B
C
D
150 1 30
40 7 30
15
60
150
1 1/4
40
60
10
40
20
80
150
1 1/2
50
80
15
50
30
100
150 2 70
100
25
70
50
140
210
1 1/4
40
60
10
40
20
80
210
1 1/2
60
90
15
60
30
120
210 2 80
120
25
80
50
160
210
2 1/2
110
160
30
110
60
220
300
1 1/2
70
100
15
70
30
140
300 2 90
130
25
90
50
180
300
2 1/2
120
190
35
140
70
280
300 3 140
230
50
160
100
320
450
1 1/2
70
90
15
60
30
120
450 2 110
120
25
80
50
160
450
2 1/2
140
170
35
120
70
240
450 3 175
190
50
140
100
280
600
1 1/2
90
100
20
70
40
140
600 2 110
130
25
110
50
220
600
2 1/2
140
190
35
140
70
280
600 3 175
250
50
175
100
350
750 2 90
120
25
90
50
180
750
2 1/2
140
190
35
140
70
280
750 3 160
230
50
160
100
320
900 2 105
140
30
105
60
210
900
2 1/2
150
220
35
150
70
300
900 3 190
280
50
190
100
380
1050 2 95
130
40
95
80
190
1050
2 1/2
145
210
45
145
90
290
1050 3 175
260
50
175
100
350
Page 3
1
MR 150M–1050M PLC
OPERATION
Summary of Contents for MR Series
Page 7: ...MR 150M 1050M PLC CONTROLLER SYSTEM INFORMATION 4 Page 4 MR 150M 1050M PLC INSTALLATION ...
Page 11: ...MR 150M 1050M PLC CONTROLLER INSTALLATION 8 TUBING DIAGRAM VALVE NEST MULTITANK ASCO SOLENOID ...
Page 36: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 33 ...
Page 37: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 34 ...
Page 38: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 35 ...
Page 39: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 36 ...
Page 40: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 37 ...
Page 41: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 38 ...
Page 42: ...MR 150M 1050M PLC CONTROLLER MAINTENANCE 39 ...
Page 51: ...MR 150M 1050M PLC CONTROLLER 48 NOTES ...
Page 52: ...2227 South Street P O Box 044170 Racine WI 53404 7003 www Marlo Inc com 8 217 R5 ...