MD5016 Field Installation
08-1612 SECTION-3 PAGE 2 OF 10
Collection Basin Options
Sump Outlet
FULL FACE GASKET
OUTLET PIPING AND FASTENERS
Supplied by others. fasteners must be
stainless steel in stainless basins
SUMP SCREEN
On sumps with high flows a screen
assembly with anti-vortex plate is used.
See "Outlet Anti-Vortex Plate" detail.
A sump plate is shipped
wired inside fiberglass
sumps only. Remove
wire and install using
outlet piping fasteners
(supplied by others)
Z11 TYPE 'B'
Clean surfaces and apply a 3/8"
[10mm] bead of sealer around and
between all holes on sump plate and
outside of sump.
PIPING, SUPPORTS, DESIGN
OF PIPING AND SUPPORTS,
AND RESTRAINT OF LATERAL
PIPING LOADS ARE THE
RESPONSIBILITY OF OTHERS.
DO NOT SUPPORT PIPING
FROM THE TOWER
COLLECTION BASIN
DEPRESSED FLOOR
For added leak
protection apply
sealer under bolt
head and washer.