Two-Wire Control Circuit using an SPST Switch
Typical connection points for the IMI 686B vibration switch used with the
E-Clipse bypass terminal strip of an ABB ACH550 VFD.
Breaking the control circuit between points 1 and 7 will disable VFD and bypass
operation. To reset the vibration switch remove incoming power to the VFD,
wait a minute or two allowing the VFD capacitors to discharge then reapply
power. At this point the switch will be in a closed state allowing VFD operation.