Breakdowns 13
The motor doesn't run
- Check the rotation direction.
- Circuit breaker activated
✔
Check the liquid level.
✔
Reset the circuit breaker.
- Faulty bearings
✔
Replace the bearings.
- Insufficient fluid
✔
Add some fluid.
- Non-standard fluid quality
✔
Change the fluid.
- Motor out of order
✔
Replace the motor.
The motor runs, but without the pressure increasing in the circuit concerned
- Faulty pump
✔
Replace the pump
G.
Check that the compressor is running
The compressor is powered on but doesn't work
- The internal compressor safety switch has been activated
✔
Cut off the power supply
Let the unit cool off (may take several hours)
Restart the unit
✔
Check that the exhaust fan is working properly
Clean the condenser
LP contact is open (optional on CSW50 through CSW150), intake pressure too low
for the compressor
- Gas leakage?
✔
Call a refrigeration engineer to repair the leak and refill the circuit with gas
LP contact is open (optional), intake pressure too low for the compressor
- The breakdown is indicated on the breakdown indicator (starting at model CSW200)
✔
Follow the instructions
Summary of Contents for CSSW 50
Page 1: ...INDUSTRIAL REFRIGERATION UNITS TECHNICAL NOTICE V1 0...
Page 8: ...Page 8 100 Technical Notice V1 0 01 09 Table of contents...
Page 14: ...Page 14 100 Technical Notice V1 0 01 09 1 Introduction...
Page 32: ...Page 32 100 Technical Notice V1 0 01 09 4 Model CSW 100 150...
Page 38: ...Page 38 100 Technical Notice V1 0 01 09 5 Model CSW 200 300...
Page 44: ...Seite 44 100 Technical Notice V1 0 01 09 6 Model CSW 400...
Page 90: ...Page 90 100 Technical Notice V1 0 01 09 12 Options...
Page 99: ...Technical Notice V1 0 01 09 Page 99 100 100 Appendix 14 14 5 Compliance documents...