INSTALLATION

Gas and Electrical Information

INSTALLATION CODES AND STANDARDS

Installation must conform with local codes, or in the ab-

sence of local codes, with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and 

Propane Installation Code, CSA B149.1, as applicable.
1.  The appliance and its individual shut off valve must 

be disconnected from the gas supply piping system 

during any pressure testing of that system at pres-

sures in excess of 1/2 PSI (0.03 kg/cm2) (3.5 kPa).

2.  The appliance must be isolated from the gas supply 

piping system by closing its individual manual shut off 

valve during any pressure testing of the gas supply 

piping system at test pressures equal to or less than 

1/2 PSI (0.03 kg/cm2) (3.5 kPa).

Electrical grounding must be provided in accordance with 

local codes, or in the absence of local codes, with the 

National Electrical Code, ANSI/NFPA 70, or the Canadian 

Electrical Code, CSA C22.2, as applicable.
Ventilation must be provided in accordance with local 

codes, or in the absence of local codes, with ANSI/NFPA 

96 Standard for Ventilation and Fire Protection of Com-

mercial Cooking Operations.

   WARNING

ELECTRICAL GROUNDING INSTRUCTIONS 

This appliance is equipped with a three-prong 

(grounding) plug for your protection against 

shock hazard and should be plugged directly 

into a properly grounded three-prong recepta-

cle. Do not cut or remove the grounding prong 

from this plug. (120V units only).

The electrical wiring diagram is located inside the right 

hand console of the appliance.

GAS CONNECTION

   WARNING

Do not connect the appliance to the electrical 

supply until after the gas connection has been 

made.

   CAUTION

The pipe thread compound used when install-

ing pipes must be a type that is resistant to 

the action of liquefied petroleum or propane 

gases.

1.  The Serial and Rating Plate on the unit indicates the 

type of gas your unit is equipped to burn. DO NOT 

connect to any other gas type.

2. 

A  3/4”  NPT  line  is  provided  at  rear  for  the  connec

-

tion. The  unit  is  equipped  with  an  internal  pressure 

regulator which is set at 4” W.C. manifold pressure for 

Natural Gas and 10” W.C. for Propane Gas. Use 1/8” 

pipe tap on the union elbow assembly located in the 

console for checking pressure.

An adequate gas supply is imperative. Undersized or low 

pressure lines will restrict the volume of gas required for 

satisfactory performance. A steady supply pressure, mini-

mum 6 inch W.C. for natural gas and minimum 12 inch 

W.C. for propane gas is recommended. With all units op-

erating simultaneously, the manifold pressure on all units 

should not show any appreciable drop.
Fluctuations of more than 25% on natural gas and 10% 

on propane gas will create problems, affecting burner op-

eration. Contact you gas company for correct supply line 

sizes. Purge the supply line to clean out any dust, dirt or 

other foreign matter before connecting the line to the unit. 

Use pipe joint compound which is suitable for use with 

L.P. on all threaded connections.
Test pipe connections thoroughly for gas leaks.

   WARNING

Never use an open flame to check for gas 

leaks. Check all connections for leaks using 

soapy water before use.

   NOTICE

If this equipment is being installed at over 

2,000 feet altitude and was not so specified on 

order, contact service department. Failure to 

install with proper orifice sizing may void the 

warranty.

Summary of Contents for FT-12CG

Page 1: ...FT 12CG GAS FIRED STEAM JACKETED TILTING KETTLE INSTALLATION OPERATION MAINTENANCE Telephone 802 658 6600 Fax 802 864 0183 www marketforge com PN 14 0366 Rev A 9 14 2014 Market Forge ...

Page 2: ...Your Service Agency s Address Model Serial number Oven installed by Installation checked by ...

Page 3: ...SMELLS GAS MUST BE POSTED IN A PROMINENT LO CATION This information may be obtained by contacting your local gas supplier FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors or liq uids in the vicinity of this or any other appliance The information contained in this manual is important for the prop er installation use and mainte nance of this oven Adherence to these procedures a...

Page 4: ...e sequence of operation is as follows 1 Operator turns the power switch to the on position and sets the temperature control dial to the desired setting 2 The red light comes on indicating the kettle is heating The green IGNITION light comes on indicating that the ignition and burner are active 3 Once the kettle reaches the set temperature the red TEMPERATURE light and the green IGNITION light exti...

Page 5: ... 152 355mm Propane 12 14 W C 305 355mm Contact manufacturer for installation over 2 000 ft elevation CW Cold Water 3 8 O D tubing to faucet optional HW Hot Water 3 8 O D tubing to faucet optional DIMENSIONS ARE IN INCHES MM G 25 39 645 EC 4 75 121 3 76 23 75 603 FLANGE FOOT DETAIL 4 EQUALLY SPACED Ø7 16 11 HOLES ON 3 76 B C Ø20 508 Ø16 75 425 I D 15 88 403 30 762 6 152 55 75 1416 49 75 1264 32 88 ...

Page 6: ...appliance to the electrical supply until after the gas connection has been made CAUTION The pipe thread compound used when install ing pipes must be a type that is resistant to the action of liquefied petroleum or propane gases 1 The Serial and Rating Plate on the unit indicates the type of gas your unit is equipped to burn DO NOT connect to any other gas type 2 A 3 4 NPT line is provided at rear ...

Page 7: ...chor ing holes provided in the flanged adjustable feet 7 Remove the appliance from installation position and drill holes in locations marked on the floor Insert proper anchoring devices Not supplied 8 Place appliance back in the installation position and Re level left to right and front to back 9 Bolt and anchor appliance securely to the floor 10 Seal bolts and flanged feet with silastic or equiva...

Page 8: ...he tilt knob located on the console at the top left This feature locks the ket tle in the upright position and also allows the operator to lock the kettle at 105 degrees for ease of cleaning Follow these steps to tilt kettle 1 Pull out the tilt knob at the top left of console 2 Using kettle tilt handle pull kettle forward to desired angle of pour or until kettle locks at 105 degrees The tilt knob ...

Page 9: ...eated and remain at room temperature during the entire cleaning process 2 If the stain resists removal additional exposure time with vinegar may be required to a maximum of one hour 3 Thoroughly wash all of the vinegar away with fresh clear water Dry the surface completely and allow one hour before using the appliance to cook Following daily and period maintenance procedures will prolong the life ...

Reviews: