Mark Secure 3 Instruction Manual Download Page 5

4. MARK Secure 3 installation instructions

Solid wood ceiling, suspended ceiling system, 
socket installation  
 

Anchor device type A according to EN 795:2012 for 
installation in conjunction with ceiling structures suspended 
from load-bearing wooden ceilings such as the Knauf 

ceiling  systems  D11,  D12,  D13,  or  AMF  mineral  fibre 

ceilings. Suitable for vertical load due to a fall from height.

Maximum expected total deformation of the installation 
base and the anchor point due to a fall from a height: 
15 cm vertical. Adjust the length of the connector based on 
conditions on site.

Installation: 

This product may only be installed as per this instruction manual. MARK Save A Life GmbH recommends it is installed by 
a specialist company.

3.3 Technical details

Installation base, components,  
tools, operating conditions

Approved for Knauf systems or similar products 
with the same properties

D11, D12, D13 and AMF mineral fibre ceilings

Test standard, permissible number of people

EN 795:2012, 1 person

Fasteners

2 x stainless-steel screws, countersunk head 
M10x25 
2 x deformation brackets
2 x hexagon head wood screws 12 x 100 
galvanised
2 x washers for diameter M12
4 x screws M8 x 25 8.8 galvanised 
4 x washers 8.4 x 25 galvanised 
2 x counterplates 2-hole

Drill

Wood drill bit 6 mm

Screw-in depth

100 mm

Hole cutter

95 mm with centring drill 6 mm

Torque wrench

13 mm nut and 19 mm nut, Allen socket 6 mm

Tightening torques

M8: 27 Nm, M10: 20 Nm
Hexagon head wood screws: tighten to 
hand-tight, depending on the firmness of the 
installation base

Quality of the installation base 
(static load-bearing capacity of the structure 
must be guaranteed)

≥ C 24

Addition

Installation only on load-bearing structures

Distance from edge

≥ 50 mm

Thickness of non-load-bearing cladding 
(plasterboard, insulation)

1-3 layer cladding 12.5 mm/35 mm MF or WW

Permissible load directions

Vertical

Separation height

110 mm to 3000 mm

Maximum expected deformation due to a fall 
from a height

≤ 150

Fig. Side view

8

            

9

            

1.   Mark the position of anchor point 

A

 on the load-

bearing structure. In the case of grid ceilings, in each 

case the anchor point is positioned in the centre of 

the field of a MF or WW plate.

Absorber B

UA profile K 75 mm

2.      Measure the separation height of the suspended 

ceiling (distance between lower edge of unfinished 

ceiling and upper edge of suspended ceiling). 

Cut UA profile 

K

 to this measurement.

Summary of Contents for Secure 3

Page 1: ...Secure 3 Instruction manual Anchor point for solid wood ceiling suspended ceiling system socket installation Anchor device type A according to EN 795 2012 MARK Save A Life GmbH Gleinkerau 23 4582 Spital am Pyhrn Austria Europe Tel 43 0 7563 8002 111 Fax 43 0 7563 8041 111 mark savealife at www savealife at ...

Page 2: ...roduct The instruction manual the installation report and the inspection report are available to download at www savealife at Read through the instruction manual carefully before you use this product for the first time Undergo training on the use of this product Check this product for proper function before and after each use Complete the installation report included with the product carefully Alw...

Page 3: ...duct as an anchor device according to EN 795 2012 type A The product may be used within the intended use conditions on the specified wall and attachment shell systems from Knauf Gesellschaft m b H or similar products with the same properties for the intended purpose as protection against a fall from height Note This product is an anchor device the purpose of which is to protect the user from a fal...

Page 4: ...mination damage storage and transport can all reduce the service life of this product The product features a fall indicator which clearly shows whether the anchor device has been subjected to the stress of a fall and must therefore be disposed of as per Point 8 The visual and functional inspection described in Point 7 shows every user whether the anchor device has been deformed by a previous fall ...

Page 5: ...head wood screws 12 x 100 galvanised 2 x washers for diameter M12 4 x screws M8 x 25 8 8 galvanised 4 x washers 8 4 x 25 galvanised 2 x counterplates 2 hole Drill Wood drill bit 6 mm Screw in depth 100 mm Hole cutter 95 mm with centring drill 6 mm Torque wrench 13 mm nut and 19 mm nut Allen socket 6 mm Tightening torques M8 27 Nm M10 20 Nm Hexagon head wood screws tighten to hand tight depending o...

Page 6: ...ends must be used 5 Secure deformation bracket E to the load bearing structure using two hexagon head wood screws 12 100 I incl washers J 7 If necessary first cut out a hole roughly the size of a coin at the calibrated position align the hole cutter with the central hole of the absorber B and cut out the circular hole Secure ceiling cladding and level out or insert the acoustic plate 8 Adjust the ...

Page 7: ...ensely the product is used as well as on the operating environment If the product is subjected to extremely heavy stress the inspection must be performed more than once a year 8 Disposal MARK Save A Life GmbH is committed to protecting the environment We endeavour to consider the environment when manufacturing our products and hope that our customers will use and dispose of them in an environmenta...

Page 8: ...ate Call the emergency services Lower the person who needs to be rescued Place the person on the floor with the upper body elevated in a sitting or squatting position Release the straps and any restricting clothing Only put the person into a recumbent position slowly Always pay attention to the person s circulation and breathing If the affected person is no longer displaying signs of life start re...

Page 9: ...lid wood ceiling suspended ceiling system socket installation The completed installation report for the anchor points listed below confirms that installation has been carried out properly in line with the instruction manual for the product Installation situation sketch photo Installation situation sketch photo Construction project Construction project Component Component Storey section Storey sect...

Page 10: ...om the edge 50 mm Screw in depth of the wood screws 100 mm Drilled holes 6 mm All parts of the construction kit used in full All screws tightened to nominal torque Installation carried out according to instruction manual Safety for use confirmed a Installation date Client project manager Contractor project manager Name company signature Name company signature 18 19 ...

Page 11: ...only permitted to make changes to reprint or photographically reproduce this document in whole or in part with the express consent of MARK Save A Life GmbH Gleinkerau 23 4582 Spital am Pyhrn MARK Save A Life GmbH Gleinkerau 23 4582 Spital am Pyhrn Austria Europe Tel 43 0 7563 8002 111 Fax 43 0 7563 8041 111 mark savealife at www savealife at Making your life safer ...

Reviews: