32
Recom-
mended
Min
Max
After factory
reset
2. ADVAN-
CED DHW
SETTINGS
1. DHW power
1. Maximum power
100
0
100
100
2. Minimum power
0
0
100
0
2. DHW
temperatures
1. Storage temperature setpoint
80
35
85
80
2. Boiler temperature setpoint
60
35
65
60
3. DHW setpoint hysteresis
6
2
10
3
3. DHW pump
settings
1. DHW post time
1
OFF
180
30
4. DHW priority
1. DHW priority status
Enabled
Enabled
Disabled
Enabled
2. DHW priority TimeOut
Off
1
60
Off
5. DHW request type
Switch
Switch
Sensor
Switch
3. SYSTEM
SETTINGS
1. Boiler
parameters
1. Ignition power
25
0
100
Higher than 30 not allowed
2. Delay siphon check
3
0
20
Check syphon is not empties by new value
3. Number of boiler pumps
2 pump
Pump
3-w-valve
2 pump
2 pump
4. PWM pump speed max
100
1
100
100
5. PWM pump speed min
40
1
100
30
6. Antilegionella
Enabled
Disabled
Enabled
Disabled
7. Modbus parameters
Adress
Baudrate
Frame
8. 3 Way valve travel time
180
1
255
10
2. User interface
settings
1. Select language
English
English|Italian|German|
Russian|Spanish
2. Select units
Celsius
Fahrenheit
Celsius
3. Set date
Set date
4. Set time
24 Hours
24 Hours
12 Hours
3. Service settings
1. Service information
Set telephone number
2. Service due date
Set service date
4. DIAGNOS-
TICS
1. Boiler information
Real time boiler status
2. Lockout history
Overview lockout history
Status boiler at time of lock/block
3. Manuel test
See chimney sweeper
5. USER
SETTINGS
0 Heating
1. CH tempera-
ture/OTC set
1. CH set point
85
20
90/abs max
CH temp
75
2. Outside tempe-
rature for CH off
off
7
25
off
2. ECO setpoint reduction
50
0
50
3. Scheduler
set
1. Enable/disable
on board sche-
duler
Enabled
Disabled
Enabled
2. Scheduler set
Set time scheduler (Time/On/ECO/OFF)
2. Domestic hot
water
1. DHW setpoint (NTC sensor)
60
35
65
1. DHW setpoint (Thermostated)
80
35
85
2. ECO setpoint (NTC sensor)
20
0
50
3. Scheduler
set
1. Enable/disable
on board sche-
duler
Enabled
Disabled
Enabled
2. Scheduler set
Set time scheduler (Time/On/ECO/OFF)
3. Holiday
1. CH holiday setpoint
20
20
90/Abs max
CH temp
1 DHW holiday setpoint (Thermo-
stated)
80
35
85
2. DHW holiday setpoint (Sensor)
60
10
65