2.0 Technical specifications
• Type description
: In module
• Type of thermostat
: Module for communication with, for example,
a building management system
• Article code
: 06 29 188
• Connection
: In module
g
air heater Bus system
(2 wires)
In module
g
external connections eg.
building management system 230V or 24V
(for both
potential free exits only 1 voltage may be used: 230V or 24V)
In module
g
external controller 0-10V
In module
g
0-10V external connection eg.
building management system: Modbus
• Wiring
: In module
g
air heater
Shielded bus cable, see
§3.0
• Dimensions
: 109 x 154 x 49mm (lxwxh)
• Weight
: 498 grams
• Degree of protection
: IP20
• Ambient temperature
: 0-40°C
3.0 Wiring
For the wiring between the In module and an air heater a shielded bus cable must be used.
For the maximum lenght and the proper diameter see table
[1]
.
Pay attention!
Ground the shielding of the cable on the air heater.
The bus cable must be chosen according to the country specific implementation, the values in the
technical specifications must be maintained.
Suitable bus cables:
Cable type
Application
EIB-specification
YCYM
Fixed installation
Dry, humid, wet areas. In the
open sky (no direct sunlight).
Build-up, installation, in pipes.
J-Y(st)Y
Fixed installation
Only indoors.
Build-up, in pipes.
JH(st)H
Halogen-free cables,
remote installation.
A-2Y(L)2Y
A-2YF(L)2Y
Telephone earth wire,
Installation in the outskirts.
Summary of Contents for Interface+
Page 2: ...2...
Page 14: ...14...
Page 26: ...26...
Page 38: ...38...
Page 51: ...51 2 G S 3 G S GSX 17 20 GS L1 N PE 1 2 3 4 5 6 max 8 GS GSX GS GSX GS GSX...
Page 52: ...52 4 G S GSX 8 7 6 5 4 3 2 1 OFF ON S4...
Page 54: ...54 7 GSX 8 7 6 5 4 3 2 1 OFF ON S4 6 GSX max 8 GSX GSX GSX...
Page 57: ...57...