CHARGE BY PRESSURE

 

If you selected the “charge by pressure” option in “SCREEN 2”, after entering in the 

CHARGE MENU, connect the cylinder located on the floor to the IDEA TRONIC 

device through a flexible hose.

If the cylinder does not have the dip tube, perform the charge turning the container 

upside-down to use the liquid refrigerant fluid part. 

Switch on the system to be repaired, ensure that the compressor is running, then press 

the

 “ent

 key.

At  this  point,  the  empty  electronic  bar  will  appear  on  the  display  (Picture  1),                        

through which the operator will visualize the status of the system charge.

The procedure ends when the bar will be completely filled up. 

Open the refrigerant gas tap very slowly (liquid phase) and close it as soon as the 

electronic bar will be completely filled up and on the display will appear the “wait for 

compensation” written words (Picture 2).

Keeping the refrigerant gas tap closed, let the equipment running for a few minutes to 

allow the refrigerant fluid to stabilize inside the system. In the meantime, with the 

compressor running, the electronic bar will automatically empty from the top.

Repeat the operations for a few times until the Bars shown at the end of the electronic 

bar are the same (or very close) to those indicated above    xxx Bar      Bar xxx

At this stage the IDEA TRONIC device will emit an acoustic signal indicating that the 

performance is completed (Picture 3).

Use with  5 - 12 - 40 Kg. cylinders

Picture 1: Charge by 

pressure progress

Picture 2: Pressure  

compensations

Picture 3: 

After each partial 

charge, wait for pressure 

compensations until 

reaching the complete 

charge. 

13

Summary of Contents for Idea Tronic

Page 1: ......

Page 2: ...INSTRUCTIONS FOR USE...

Page 3: ...linders 8 Connection of 5 10 12 40 kg cylinders 9 Choice of refrigerant fluid BT TN AC and charge method 10 System check up 11 Vacuum 11 Charge Charge by weight 12 Charge by pressure 13 Refrigerant re...

Page 4: ...re disconnecting to 1 RECOVER THE REFRIGERANT GAS 2 MAKE THE VACUUM 3 CHECK FOR POSSIBLE LEAKS 4 MAKE THE CHARGE WITH GRAM ACCURACY 5 CHECK IF THE CARRIED OUT CHARGE IS CORRECT 1 SYSTEM CONNECTION OR...

Page 5: ...RIPTION Pic CODE 1 Complete device 2 parts base hand held equipment IDEAT 1 Brass adapter 5 16 F 1 8 M with aerosol M connection 1 ADATTATORI5 16 1 Brass adapter 1 4 F 1 8 M with aerosol M connection...

Page 6: ...point 4 3 Connect the yellow hose point 1 to the 1A nut and to the vacuum connecting port of the Idea Tronic point 2 4 Select the appropriate reduction before screwing the cylinder check page 8 5 Brac...

Page 7: ...cons contemporaneously and all available languages will appear on the display Slide the arrow keys until the desired choice has reached then press the en key to validate the preference The same proced...

Page 8: ...CONNECTION OF 1 2 KG CYLINDERS NB Connect the appropriate adapter R134 R600a do not connect any adapter R22 R422B R407C R404A 1 4 F Sae adapter R410A 5 16 SAE F adapter 8...

Page 9: ...to use the refrigerant fluid in the liquid phase SUGGESTIONS FOR THE CHARGE BY PRESSURE PROCEDURE If you use a cylinder bigger than 2 kg the charge by pressure is recommended If you know the exact qu...

Page 10: ...tic refrigerators etc or AC suitable for air conditioning systems You will then be asked to select the opportune charge method it means by weight if you work with 1 or 2 kg cylinders screwed on IDEA T...

Page 11: ...ACUUM If you need to perform the vacuum procedure slide the arrow keys up and down and confirm the VACUUM option by pressing the entkey Open the vacuum tap and switch on the pump then press ente key T...

Page 12: ...for a few minutes N B The refrigerant fluid ends during the charge procedure If by any chance the refrigerant fluid contained in the cylinder ends before finishing the charging procedure the written w...

Page 13: ...d phase and close it as soon as the electronic bar will be completely filled up and on the display will appear the wait for compensation written words Picture 2 Keeping the refrigerant gas tap closed...

Page 14: ...evice the recovery unit and the vacuum pump simultaneously Once connected all equipment it will be then possible to perform all operations without never disconnecting them in fact you will be able to...

Page 15: ...refrigerant fluid If the installation of the circuit has been effected in abnormal conditions poor ventilation different length of hoses etc the working pressures may be different altering the correc...

Page 16: ...of the performances You need to start again from the beginning after switching it on 2 IMPORTANT do not leave any residue of refrigerant fluid after use to avoid danger BATTERIES REPLACEMENT The IDEA...

Page 17: ...components PVC aluminium etc NOTE For disposal dispose this equipment in a facility that complies with local state and federal regulations WARRANTY 1 The validity of the warranty is of n one 01 year...

Page 18: ...mensions cm 11 x 32 x 43 RE12A Refrigerant recovery unit for domestic industrial and automotive air conditioners Oil less and air cooled compressor it recovers all commonly used refrigerant fluids inc...

Page 19: ...vacuum pump and recovy unit simultaneous connection MA29 3 ways adapter for gauge connection D1004 Blue low pressure gauge R600a D1006 Blue low pressure gauge R410A D1008 Blue low pressure gauge R134a...

Page 20: ...Manufactured by MARIEL srl Via Olubi 5 28013 Gattico NO ITALY www mariel it...

Reviews: