CHARGE BY WEIGHT

If you selected the “charge by weight” option in “SCREEN 2”, proceed with the charge, 

screwing the refrigerant fluid cylinder on the holder of the IDEA TRONIC device.

Set up the refrigerant gas charge in grams which you need to fill inside the system, by sliding 

the 

“      ” 

 keys.

Then press the 

“ent 

key and the empty electronic bar will appear on the display.

Open the refrigerant gas tap very slowly and the empty electronic bar will start to gradually 

fill up until the preset quantity visible at the end of the bar is reached.

Guide the filling procedure with the hand and close the refrigerant gas tap quickly, avoiding 

to release a greater quantity of fluid than preset.

This charge procedure can be performed with the system off; anyway, if at some point you 

are unable to fill the preset quantity (especially in small systems), you need to switch it on 

for a few minutes.

N.B.:  The refrigerant fluid ends during the charge procedure. If by any chance the refrigerant 

fluid contained in the cylinder ends before finishing the charging procedure, the written 

word “empty cylinder” will appear on the display.

Press 

enter

key and replace the cylinder. The system stores the refrigerant gas quantity already 

filled, so complete the charge.

ATTENTION: the written word “empty cylinder” can also be shown if the refrigerant fluid 

does not enter inside the system. Switch on the compressor to guide the filling.

N.B.:  Once the gas charge procedure has been completed, if you desire to “check the system”, 

let the equipment running for at least 15 minutes, then proceed.

ATTENTION: ACCIDENTALLY TOUCHING THE REFRIGERANT CYLINDER DURING 

THE CHARGE MAY INVALIDATE THE PROCEDURE DUE TO THE POSSIBLE RESETTING 

OF THE DEVICE.

Picture 1:  

Setting of the refrigerant 

quantity

Picture 2: Press enter key with the 

compressor running and open 

the gas tap slowly

Picture 3: Monitor the progress 

of the charge on the display. 

Close the tap when the charge is 

reached.

12 

Summary of Contents for Idea Tronic

Page 1: ......

Page 2: ...INSTRUCTIONS FOR USE...

Page 3: ...linders 8 Connection of 5 10 12 40 kg cylinders 9 Choice of refrigerant fluid BT TN AC and charge method 10 System check up 11 Vacuum 11 Charge Charge by weight 12 Charge by pressure 13 Refrigerant re...

Page 4: ...re disconnecting to 1 RECOVER THE REFRIGERANT GAS 2 MAKE THE VACUUM 3 CHECK FOR POSSIBLE LEAKS 4 MAKE THE CHARGE WITH GRAM ACCURACY 5 CHECK IF THE CARRIED OUT CHARGE IS CORRECT 1 SYSTEM CONNECTION OR...

Page 5: ...RIPTION Pic CODE 1 Complete device 2 parts base hand held equipment IDEAT 1 Brass adapter 5 16 F 1 8 M with aerosol M connection 1 ADATTATORI5 16 1 Brass adapter 1 4 F 1 8 M with aerosol M connection...

Page 6: ...point 4 3 Connect the yellow hose point 1 to the 1A nut and to the vacuum connecting port of the Idea Tronic point 2 4 Select the appropriate reduction before screwing the cylinder check page 8 5 Brac...

Page 7: ...cons contemporaneously and all available languages will appear on the display Slide the arrow keys until the desired choice has reached then press the en key to validate the preference The same proced...

Page 8: ...CONNECTION OF 1 2 KG CYLINDERS NB Connect the appropriate adapter R134 R600a do not connect any adapter R22 R422B R407C R404A 1 4 F Sae adapter R410A 5 16 SAE F adapter 8...

Page 9: ...to use the refrigerant fluid in the liquid phase SUGGESTIONS FOR THE CHARGE BY PRESSURE PROCEDURE If you use a cylinder bigger than 2 kg the charge by pressure is recommended If you know the exact qu...

Page 10: ...tic refrigerators etc or AC suitable for air conditioning systems You will then be asked to select the opportune charge method it means by weight if you work with 1 or 2 kg cylinders screwed on IDEA T...

Page 11: ...ACUUM If you need to perform the vacuum procedure slide the arrow keys up and down and confirm the VACUUM option by pressing the entkey Open the vacuum tap and switch on the pump then press ente key T...

Page 12: ...for a few minutes N B The refrigerant fluid ends during the charge procedure If by any chance the refrigerant fluid contained in the cylinder ends before finishing the charging procedure the written w...

Page 13: ...d phase and close it as soon as the electronic bar will be completely filled up and on the display will appear the wait for compensation written words Picture 2 Keeping the refrigerant gas tap closed...

Page 14: ...evice the recovery unit and the vacuum pump simultaneously Once connected all equipment it will be then possible to perform all operations without never disconnecting them in fact you will be able to...

Page 15: ...refrigerant fluid If the installation of the circuit has been effected in abnormal conditions poor ventilation different length of hoses etc the working pressures may be different altering the correc...

Page 16: ...of the performances You need to start again from the beginning after switching it on 2 IMPORTANT do not leave any residue of refrigerant fluid after use to avoid danger BATTERIES REPLACEMENT The IDEA...

Page 17: ...components PVC aluminium etc NOTE For disposal dispose this equipment in a facility that complies with local state and federal regulations WARRANTY 1 The validity of the warranty is of n one 01 year...

Page 18: ...mensions cm 11 x 32 x 43 RE12A Refrigerant recovery unit for domestic industrial and automotive air conditioners Oil less and air cooled compressor it recovers all commonly used refrigerant fluids inc...

Page 19: ...vacuum pump and recovy unit simultaneous connection MA29 3 ways adapter for gauge connection D1004 Blue low pressure gauge R600a D1006 Blue low pressure gauge R410A D1008 Blue low pressure gauge R134a...

Page 20: ...Manufactured by MARIEL srl Via Olubi 5 28013 Gattico NO ITALY www mariel it...

Reviews: