background image

 

TLA100 User’s Manual  

 

 

 

 

 

Page 10  

 

Revision 1.2 

 
 
 
 

Symptom 

Troubleshooting Procedure 

No tank level 
output 

1.  If operating in the 

NMEA 2000

®

 Mode

, check the connections to the 

NMEA 2000

®

 interface (see Section 2.3.2) and/or the connection to the 

resistive tank sender (see Section 2.3.1.2) and tighten if necessary. 

2.  If operating in the 

NMEA 2000

®

 / Analog Gauge Mode

, then check the 

connections to the NMEA 2000

®

 interface (see Section 2.3.2) and/or 

the connection to the analog gauge (see Section 2.3.1.1) and tighten if 
necessary. 

3.  Ensure that power is supplied to the NMEA 2000

®

 network. Proper 

network power can be checked by measuring the voltage at an open 
tee between NET-S and NET-C. The voltage should be between 9 and 
16 volts.  

4.  Ensure that both trunk line terminators are in place. Proper network 

termination can be checked by removing network power and 
measuring the resistance at an open tee between NET-L and NET-H 
signals. The resistance should read approximately 60 ohms (two 120 
ohm terminators in parallel equals 60 ohms). 

Inaccurate tank 
level output 

1.  Remember, the accuracy of most analog gauges/resistive tank 

senders is at best plus or minus 10%. The inaccuracies are due to 
both the analog gauge and the resistive tank senders. Although the 
TLA100 is a precision instrument, it is only as good as the resistive 
sender, which may not be as accurate as you like. Avoid low cost 
resistive tank senders if you desire good accuracy. 

2.  If using a standard resistive tank sender (American standard 240-30 

ohm, European standard 10-180 ohms), make sure you have correctly 
configured the TLA100 for the appropriate standard (see Section 
3.5.1). 

3.  If using a standard resistive tank sender (i.e., American or European), 

you may want to consider custom calibration (see Section 3.5.2). The 
standard sensor values assume that your tank is empty when the float 
is bottomed out (i.e., one end of the resistive range) and that the tank 
is full when the float is all the way up (i.e., the other end of the resistive 
range), which may not be the case if, for example, the tank drain is 
above the bottom of the tank. Custom calibration will use actual 
minimum and maximum resistive values instead of assuming that the 
tank is full and empty at the standard resistive extremes. 

4.  If using custom calibration, re-calibrate the TLA100 (see Section 

3.5.2). 

5.  If operating in the 

NMEA 2000

®

 / Analog Gauge Mode

, ensure correct 

analog gauge resistive values have been configured or programmed 
into the TLA100 (see Section 3.3.1) 

Figure 5 – Troubleshooting Guide 

www.busse-yachtshop.de  |  [email protected]

Summary of Contents for TLA100

Page 1: ...l Adapter User s Manual Revision 1 2 Copyright 2006 Maretron LLC All Rights Reserved Maretron LLC 9034 N 23rd Ave 13 Phoenix AZ 85021 7850 http www maretron com Maretron Manual Part M000901 www busse...

Page 2: ...ser s Manual Page ii Revision 1 2 Revision History Revision Description 1 0 Original document 1 1 Minor Updates 1 2 Corrected default values of transmitted PGN s www busse yachtshop de info busse yach...

Page 3: ...Attached Gray Cable to Tank Sender 5 2 3 2 Connecting to NMEA 2000 Interface 6 3 Configuring the TLA100 6 3 1 Configuring Tank Type 7 3 2 Configuring Tank Number 7 3 3 Configuring Operating Mode 7 3 3...

Page 4: ...When Used Without Analog Gauge 4 Figure 3 TLA100 Connections 4 Figure 4 NMEA 2000 Connector Face Views 6 Figure 5 Troubleshooting Guide 10 List of Tables Table 1 TLA100 Gauge Connections 5 Table 2 TLA...

Page 5: ...joy the advantages of digitally networked information The Maretron TLA100 is designed to operate within the harsh demands of the marine environment However no piece of marine electronic equipment can...

Page 6: ...e TLA100 can be used together with an analog gauge s referred to as NMEA 2000 Analog Gauge Mode or it can be used standalone to power and sense the resistive sender without an analog gauge s referred...

Page 7: ...k line and the resistive tank sender The reason for choosing this location is because you will be connecting some of the wires within the TLA100 s permanently attached gray cable to the tank sender Ma...

Page 8: ...d 2 the NMEA 2000 connection Refer to Section 2 3 1 for making the gauge or tank sender connection and Section 2 3 2 for making NMEA 2000 connection Caution Connect the TLA100 s permanently attached g...

Page 9: ...symbol or a G for ground and the sensor connection is generally marked with an S for sensor or G for gauge You might have to refer to the gauge documentation or schematic to determine the exact funct...

Page 10: ...is connected or disconnected Please follow recommended practices for installing NMEA 2000 network products Figure 4 NMEA 2000 Connector Face Views 3 Configuring the TLA100 The TLA100 has several confi...

Page 11: ...of two modes 1 NMEA 2000 Mode or 2 NMEA 2000 Analog Gauge Mode You configure or place the TLA100 into NMEA 2000 Mode when you are connecting the TLA100 directly to the resistive tank sender see Figur...

Page 12: ...terminal and the sensor terminal found on the back of the gauge Before making the measurement disconnect the power ground and sensor wires from the gauge Then measure and record the resistance betwee...

Page 13: ...standard resistive tank sender is being used 2 A standard resistive tank sender is used but maximum accuracy is desired 3 The tank shape is irregular or non rectangular Regardless of the reason for c...

Page 14: ...th the analog gauge and the resistive tank senders Although the TLA100 is a precision instrument it is only as good as the resistive sender which may not be as accurate as you like Avoid low cost resi...

Page 15: ...an be Used With or Without Analog Gauges Certifications Parameter Comment NMEA 2000 Level B Maritime Navigation and Radiocommunication Equipment Systems Tested to IEC 60945 FCC and CE Mark Electromagn...

Page 16: ...ist 4 times 7days 40 C 95 RH after 2 hour Salt Spray Per IEC 60945 8 12 Electromagnet Emission Conducted and Radiated Emission per IEC 60945 9 Electromagnetic Immunity Conducted Radiated Supply and ES...

Page 17: ...IDENTAL OR CONSEQUENTIAL DAMAGES DAMAGES FOR LOSS OF USE LOSS OF ANTICIPATED PROFITS OR SAVINGS OR ANY OTHER LOSS INCURRED BECAUSE OF INTERRUPTION OF SERVICE IN NO EVENT SHALL MARETRON S AGGREGATE LIA...

Page 18: ...TLA100 User s Manual Page 14 Revision 1 2 This page intentionally left blank www busse yachtshop de info busse yachtshop de...

Page 19: ...ith a default value of zero 2 Fluid Type This field identifies the type of fluid contained within the tank Currently the defined fluid types are fuel fresh water wastewater live well oil and black wat...

Reviews: