General:
The SH-003 kit can be used for general smoke / heat detection; however, it is ideal for use in high temperature areas
such as engine rooms. The SH-003 kit contains a 24v smoke / heat detector and its mounting relay base, a sounder
and its mounting base and all original manufacturers installation instructions and warranty information papers. Please
retain the provided papers for additional reference. There is a choice of 32 sounder tones and a sounder volume
control for the Klaxon sounder unit. Please refer to the provided
'Klaxon Sonos Sounder Installation Instructions'
for
information on how to adjust these settings. The kit also comes with an
8K Ohm EOL
(End of Line)
Resistor
and an
EOL Relay
necessary for circuit monitoring also known as 'circuit supervision'. The components of this kit are rated for
operation from -13°F to 158°F (-25°C to 70°C). When an SH-003 is connected to a SIM100 module, the module will
broadcast an NMEA 2000
Switch Status Indication
for that channel. The NMEA 2000 message broadcast for each
SIM100 channel
'Switch Status Indication'
is broadcast according to the SIM100's
Instance Number
and channel
number.
Configuration:
Use a Maretron IPG100, or a Maretron USB100 and PC running N2KAnalyzer software to configure the SIM100 switch
channel mode (indicated as “Channel #x Mode”) to the 'End of Line Resistor' setting.
Detector Behavior:
When a detector is triggered or in
Test Mode
the detector's sounder will sound, the detector base relays will change
state, and the integrated Red LED will illuminate solid. To reset an alarm state or exit
Test Mode
on a detector, the
detector's power will need to be cycled.
LED Modes Detector: LED Modes EOL Relay:
Power-Up..........................No LED
Standby (Detector OK)......Red LED will periodically blink Standby......................................Red LED ON
Alarm State.......................Red LED will illuminate solid
Loss or Power / Alarm State......Red LED OFF
Installation:
·
Install SH-003 in accordance with ABYC and NFPA guidelines for fire and smoke detection based on your
application.
·
Never exceed 900 sq. ft. of area for any single detector's range.
·
Detector and sounder can be ceiling or wall mounted directly or fastened to various sizes of standard
electrical boxes.
·
Pre-Mount and wire the detector and sounder bases before installing the head units. Twist head units
(detector unit and sounder unit) onto respective bases in a clockwise motion. To remove, twist head in a
counter-clockwise motion. Both detector and sounder heads are keyed to the base.
·
Wire SH-003 in accordance with ABYC or NEC guidelines to select correct wire size (22-16 AWG) and any
other applicable wiring guidelines based on your application type.
·
The application of dielectric grease on the detector and sounder base connections is recommended.
·
Do not mix high current harnessing with fire detection harnessing. For best wiring choice, choose a marine
grade, tinned copper, 16 AWG twisted pair cable.
·
The detector comes with a pre-installed dust cover. Maintain cover affixed to detector throughout vessel
construction or until first use
.
Testing:
To test an SH-003 system connected to a SIM100, the NMEA 2000 network for SIM100 and the SH-003 detector will
need to be powered. After power-up, the respective NMEA 2000
Switch Status Indication
should indicate 'Off'
(Normal State). If either detector power or any connection to SIM100 is lost for the channel, the respective NMEA 2000
Switch Status Indication
should indicate 'Error' (Maintenance Required). If a detector is in an
Alarm State,
the
respective NMEA 2000
Switch Status Indication
should indicate 'On' (Alarm State). Perform additional testing and
maintenance routine as outlined in the provided '
Apollo Orbis Marine Multi-Sensor Detector Instructions'
.