18
MAIN MENU
Description
001
MAN/FEED
Selected element is – “CODE” access code
Set correct CODE to access certain parameters.
Displays software date
FUEL/AIR
MODE
PARAMETER
EXIT
LANG/ЕЗИК
CODE 01-
JUN15
2.
Setting of system’s mode
Please make sure all settings match exactly installed heating systems. This is very important for
correct operation of all logics and priorities used.
To maximize flexibility if possible use two separate pumps for heating and hot water supply (P2).
MODE
Description
SUMMER
Selected element is „SUMMER”. Press ОК to confirm
The symbol „
” shows which the selected season – in
this case „SUMMER”.
WINTER
AUTO
ANTI ICE
STOP
ROOM TERM.
DHW=P2/
EXIT
Operation during season „ SUMMER”:
System operates according to following notes:
-
Boiler temperature changes with respect to DHW’s temperature settings.
-
Room thermostat is ignored
-
Both temperatures of DHW and boiler determine the conditions for boiler ignition/extinction.
-
If DHW mode is selected as “P2”, the main pump (P1) will not be activated, only P2 is
activates
-
If DHW mode is selected as valve ”
”
, the main pump (P1) will be activated together with
P2. It is necessary to manually cut the circulation for heating circuit.
MAIN MENU
Description
EN
MAN/FEED
Selected element is – “Language” – English (EN)
Changes used language for texts
FUEL/AIR
MODE
PARAMETER
EXIT
LANG/ЕЗИК
CODE 01-JUN15