16
parameters
5.
Check air
6.
Check parameters
4 Е4 FLUX
OVERHEA
T
Flux
temperature
readed is very
high
1.
Excess flue gas
temperature
2.
Wrong set of
parameters
3.
Defective flux
sensor
1.
Check parameters.
2.
Check sensor’s position
3.
Replace sensor
5 Е5 ALARM
INPUT
The input for
external Alarm
is activated (no
connection)
1.
Overheating - back
fire
2.
Overheating of
pellet bin
1.
Chimney is stuck
2.
Pellet house is loose
3.
Other technical failure
6 Е6 BAD LINE
230V
Power supply is
of bad quality
1.
Frequency
supplied or voltage is
bad
2.
Applied UPS or
generator is not
sinusoidal or frequency
is out of ±5% limits
3.
Defective
control board
1.
Supply the unit from normal
mains outlet 230V/50Hz
2.
Use pure sinewave UPS or
generator with frequency
regulation to match ±5% limits
(48Hz
52Hz)
3.
Replace control board if
needed
7 Е7 BLOCKAG
E
Cleaning is
stuck
Not implemented
SWITCHING ON AND OFF THE SYSTEM
1. Press and hold the ON/OFF (B5) button for 4-5 seconds (until you select the desired mode).
* Screen # 2 will be visualized.
SETTING THE DESIRED TEMPERATURE INSIDE THE BOILER
1.
Select screen # 3 by pr(B3) button once.
2.
Press OK button.
3.
Correct the value by + and - (B2/B3) buttons.
4.
Confirm the change by ОК.
5.
Go back to the main screen by pressing - (B2) button once.
SETTING THE DESIRED TEMPERATURE FOR HOT WATER SUPPLY
1.
Select screen # 4 by pr (B3) twice.
2.
Press OK button.
3.
Correct the value by + and - (B2/B3) buttons.
4.
Confirm the change by ОК.
5.
Go back to the main screen by pressing - (B2) button twice.
RECOVERY AFTER ALARM
1.
Remove the alarm source.
2.
Press OK button.
Service screen # 7
Select this screen by h and - (B2/B3) buttons.
Select the desired item by using + and -
(B2/B3) buttons, confirm the selection by ОК, correct the value by + and - (B2/B3) buttons
and confirm the change by ОК, select EXIT to exit this mode.