![Mareli Systems RubynoR AMG 1090 Manual Download Page 27](http://html1.mh-extra.com/html/mareli-systems/rubynor-amg-1090/rubynor-amg-1090_manual_1726924027.webp)
27
Items
Value
Default
Value
User Interface
Screen Saver
(P00)
0-3
0
Screen Saver
Count down
(P01)
0-120
20
12Display unit
(P02)
C / °F
C
Time Display unit
(P03)
12 / 24
12
Temperature
Offset (P04)
-5
C
~ 5
C
,
-10°F ~ 10°F
0
C
Switching
Differential Heat
(P05)
2 ~ 4°C, 4 ~ 8°F
2
C
Switching
Differential Cool
(P06)
2 ~ 4°C, 4 ~ 8°F
2
C
Program mode
(P07)
No program (0) /
1day program (1)/
5+1+1 program (2) /
7day program (3)
3
Forced
Ventilation (P12)
Disable, Enable
Disable
Changeover
Mode(P13)
Heat, Cool, Auto
Heat
Changeover
temperature Heat
(P14)
27 ~ 40°C
27
Changeover
temperature Cool
(P15)
10 ~ 25°C
10
User Interface Screen Saver:
The thermostat will go to screen saver mode af-
ter no key for certain period
Mode 0:
Nothing will be displayed in screen sav-
er mode.
Mode 1:
Only room temperature will be dis-
played in screen saver mode.
Mode 2:
Room temperature and Time will be
displayed in screen saver mode.
Mode 3:
Display all in screen saver mode.
Screen Saver Count Down:
The count down time (in seconds) to screen
saver mode.
Display Unit:
Temperature unit in Celsius or Fahrenheit.
Time Display Unit:
12/24.
Temperature offset:
The temperature of internal sensor can be cal-
ibrated from -5°C - +5°C in case there is tem-
perature difference between actual value and
thermostat.
Switching Differential:
The difference between switching the heating or
controller on and off.
Program Mode:
0: No Program Mode, The thermostat control
the temperature simply according to single set-
point.
“1”: 1 day program, The thermostat control the
temperature according to single schedule.
“2”: 5+1+1 day program, The thermostat control
the temperature according to 5 +1+1 schedule
(Mon to Fri, Sat, Sun).
“3”: 7 day program. The thermostat control the
temperature according to 7day program (indi-
vidual program for each day).
Summary of Contents for RubynoR AMG 1090
Page 1: ...FANCOIL RADIATOR AMG 890 1090 1290 ...
Page 5: ...5 The right sided version of the fan coil The left sided version of the fan coil ...
Page 12: ...12 3 4 5 6 ...
Page 15: ...15 135 Вентилаторен Конвектор AMG890 AMG1090 AMG1290 L 890 1090 1290 Cleaning ...
Page 16: ...16 ...
Page 19: ...19 5 Finally secure controller by screw ...
Page 21: ...21 TA652FC W Mobile App Interface For smartphones with Android 1 2 3 4 5 6 ...
Page 22: ...22 7 8 9 10 ...
Page 23: ...23 For smartphones with IOS 1 2 3 4 5 6 ...
Page 24: ...24 7 8 9 10 11 12 ...
Page 29: ...29 ...
Page 30: ...30 ...
Page 31: ......