17
Step 1 - Connecting UPS Module to AC:
Option 1 – Connect the included power cord to an AC receptacle.
Option 2 – Connect the included power cord to the AC convenience port on the back of
the Energy Storage Module.
IF the Electronics Module is plugged into the
AC
convenience outlet located on the back
of the Supercapacitor Energy Storage Module make sure that the AC source to which the
Storage Module connects can support the combined currents that will be drawn by
both
the Electronics Module and the Energy Storage Module. For example, at start-up the
Energy Storage Module can draw up to 15A RMS. The AC source must be rated to supply
this current in addition to the current required by the Electronics Module/UPS.
Step 2 - Connecting the SuperCap UPS to the Energy Storage Module:
The Energy Storage Module comes with a high-current DC output cord with a polarized connector
on each end. Check the orientation of the connectors and the DC sockets on the rear panel of
the UPS Module and the Energy Storage Module. Plug one end of the DC cord into the DC socket
on the back of the Energy Storage Module and the other end into the DC socket on the back of
the UPS Module.
NOTE: