DOC-FW562-UM-R1.0 

INSTALLATION MANUAL 
 

© 2021. MAPLE ARMOR FIRE ALARM DEVICE CO., LTD.  

8866, boulevard du Quartier, Brossard, Quebec, Canada, J4Y 0R2  

All rights reserved. www.maplearmor.com 

Page 

1

 of 

5

 

 

FW562-A/B/C, FW562C-A/B/C TWO-WIRE DUCT DETECTOR

 

 

 

DESCRIPTION 

The  FW562-A/B/C  and  FW562C-A/B/C  models  are 
ventilation  duct  detectors  smart  designed  FOR  USE 
WITH  MODEL  FW511A  DETECTOR  HEADS.  FW562-
A/B/C  are  UL-listed  devices  according  to  UL  268A, 
and FW562C-A/B/C are ULC listed according to ULC-
S529  for  fire  protection  systems.  Equipped  with  a 
photoelectric  smoke  detector,  the  units  will  signal 
the presence of a dangerous amount of combustion 
product  in  the  ventilation  system.  They  are 

compatible with Maple Armor’s control panel model 

FW106, FW106C, FW106S, FW106SC.  

Note: These detectors are not designed to be used in 
open areas.  

ATTENTION 

The  products  must  be  installed  in  accordance  with 

NFPA  72,  CAN/ULC-S524,  and/or  Canadian 
Electrical  Code  depending  on  the  country  of 
installation. Check information of equipment 

used in the system by other manufacturers for any 
guidelines or restrictions.  

The detector should never be installed in the following 
locations: areas with excessive exhaust fumes, kitchen 
areas, near fireplaces, furnace rooms, etc. Smoke 
detectors are not to be used with detector guards 
unless the combination has been evaluated and found 
suitable for that purpose. 

 
NOTE 

Do not paint this device. 
Any material extrapolated from this document or from 

Maple  Armor’s  instructions  or  other  documents 

describing  the  product  for  use  in  promotional  or 
advertising  claims,  or  for  any  other  use,  including  a 

description  of  the  product’s  application,  operation, 

installation, and testing is the sole responsibility of the 
user. Maple Armor will not assume any liability for such 

use.  In  no  case  will  Maple  Armor’s  liability  exceed  the 

purchase price paid for a product. 

 

 

 

SPECIFICATION 

Nominal Voltage 

24V dc 

SLC Voltage Range 

17.6 to 28V dc 

Standby Current 

0.35 mA 

Alarm Current 

2 mA 

Operating 
Temperature 

32°F to 100°F (0°C to 38°C) 

Operating Humidity  

0% to 93% RH 

Dimension 

329(W) x 114(H) x 51(D) mm                             
(13 1/8 x 4 x 2) in. 

Weight (with base) 

4.6 oz (132 g) 

Mounting location 

Side and top 

SPECIFICATIONS  

Duct Detector models  

a.

 

Applicable to ULC listing required area 

Model  

Air Velocity 

Contents 

FW562C-A 

2000 to 4000 FPM 
(ft/min)               
10.2 to 20.3 (m/s) 

 

Duct detector assembly 

 

One exhaust tube 

 

One detector headcover 

 

One 

φ

5 * 2 hole sampling 

tube (order separately) 

FW562C-B 

700 to 2000 FPM 
(ft/min)                
3.6 to 10.2 (m/s) 

 

Duct detector assembly 

 

One exhaust tube 

 

One detector headcover 

 

One 

φ

5 * 4 hole sampling 

tube (order separately) 

FW562C-C 

300 to 700 FPM 
(ft/min)                 
1.5 to 3.6 (m/s) 

 

Duct detector assembly 

 

One exhaust tube 

 

One 

φ

5 * 4 hole sampling 

tube (order separately) 

 

b.

 

Applicable to UL listing required area 

Model  

Air Velocity 

Contents 

FW562-A 

2000 to 4000 ft/min 
10.2 to 20.3 (m/s) 

 

Duct detector assembly 

 

One exhaust tube 

 

One detector headcover 

 

One 

φ

5 * 4 hole sampling 

tube (order separately) 

FW562-B 

1000 to 2000 ft/min 
5.1 to 10.2 (m/s)    

 

Duct detector assembly 

 

One exhaust tube 

 

One 

φ

5 * 4 hole sampling 

tube (order separately) 

FW562-C 

300 to 1000 ft/min 
1.5 to 5.2 (m/s) 

 

Duct detector assembly 

 

One exhaust tube 

 

One detector head baffle 

 

One 

φ

5 * 2 hole sampling 

tube (order separately) 

 
 
 
 
 
 

Summary of Contents for FW562-A

Page 1: ...he product for use in promotional or advertising claims or for any other use including a description of the product s application operation installation and testing is the sole responsibility of the user Maple Armor will not assume any liability for such use In no case will Maple Armor s liability exceed the purchase price paid for a product SPECIFICATION Nominal Voltage 24V dc SLC Voltage Range 1...

Page 2: ...as long as the diameter is 12 inches or more Step 5 If possible try to install the duct detector in an accessible location Step 6 If the duct detector is hidden in a ceiling you will need to install a remote indicating light in the ceiling under the detector to show the location Step 7 It can be installed horizontally on a duct as narrow as 6 inches and vertically on a duct as wide as 16 inches St...

Page 3: ... for details Note The duct FW562 A B C or FW562C A B C share the same address with the smoke detector model FW511 9 You must perform an air differential pressure test by using an Air Velocity Meter ex Dwyer model 460 or Reed R3001 or equivalent Wright down the air pressure differential value next you must select the appropriate model that falls in the specified operating range 10 Duct detector ass...

Page 4: ...LTD 8866 boulevard du Quartier Brossard Quebec Canada J4Y 0R2 All rights reserved www maplearmor com Page 4 of 5 Figure 8 Figure 9 Figure 10 Figure 11 When the part number is determined use the blank sticker to cover the additional part numbers shown on the label See Figure 12 ...

Page 5: ...test the detector to ensure it is operating correctly Main function Models FW562 A B C and FW562C A B C Duct Smoke Detectors utilize photoelectric smoke detectors for the detection of smoke When sufficient smoke is sensed an alarm signal is initiated Test function Alarm simulation Pressing the TEST SW can simulate an alarm condition Cover tightness monitor When the JUMPER switch is on the NORMAL s...