Manson Engineering Industrial MP-3722 User Manual Download Page 6

3.4

     The Dip Switch , Set-Button and Reset button functions

The dip switch, set buttons and reset button are used for adjusting the PV Charge Controller
Settings (see Section 3.4.1 and 3.4.2)
( * Open the Side door, you can see the dip switch & set buttons.)

3.4.1  Adjust the PV Charge Controller Settings

    

Factory Preset

The following table shows the factory preset values of the PV Charge Controller :

Bulk Voltage.................................................. 14.3V
Float Voltage.................................................. 13.5V
Low Voltage Disconnect................................ 11.5V
Low Voltage Reconnect................................. 12.5V
Night Light Mode Option............................... Off (refer to Table 5  in Section 4.3.3)

Table 3 Preset values of the adjustable parameters

The preset Bulk and Float Setpoints are for typical Sealed Gel-type Lead Acid Battery only.
For typical wet-type Lead Acid Battery, set Bulk setpoint to 14.8V and Float setpoint to 13.5V.

Please refer to battery manufacturer’s specific recommended values.

How to adjust the Bulk, Float Charge Voltage, LVD, LVR and Night Light Mode

1. First take out all the connections to the PV controller except those to battery.
2. Push up the slide cover at the right side of the PV controller.
3. Push up all three DIP Switches to OFF position.
4. Disconnect the battery negative terminal at the controller.
5. Press and hold the Reset Button and reconnect the battery negative terminal again.
6. After 3 to 5 seconds release the Reset Button and note the LCD shows “Float V “
7. The controller is now in Set Mode , short presses of the Reset Button  show  as in following 

cyclic order with  preset values :

“FLOAT CH: , LVD , LVR , L OPTION:, Bulk CH , FLOAT CH 

8. Press the Set Button 1 and 2 to adjust the desired setting.
9. When the desired settings are done , double check all settings by pressing the Preset Button.
10. To store the new settings , push down the Dip Switch 2 to on position and take note of the 

LCD displays ”INITIALIZATION…. “until one complete cycle. 

Figure 5

P.5

Figure 4

Summary of Contents for MP-3722

Page 1: ...arge Controller Settings 4 3 4 2 Select the Auto Manual Equalization charging and Night Light Mode 6 4 PV Charge Control Mode 6 4 1 3 Stage Charge Control 6 4 2 Equalization Charging Mode Automatic or...

Page 2: ...use explosion Cover wrench handles with plastic tape or vinyl dip coating material Specifications Models MP 3722 Battery voltage 12V Maximum PV panel open circuit voltage 26V Continuous load charge cu...

Page 3: ...tage Disconnect and Low Voltage Reconnect Build In Microprocessor for PV charge control to maximize the charging efficiency Overcharge and Over discharge Protection Over Temperature Protection Short C...

Page 4: ...ler should be installed in a dry sheltered location away from sources of high temperature and moisture 3 2 LED Indicator Red Flashing Battery Voltage is lower than 12 6V Constant Red Battery Voltage h...

Page 5: ...the total Ampere Hour input to the system in current day L1D PV_AH Shows the total Ampere Hour input to the system a day before L2D PV_AH Shows the total Ampere Hour input to the system 2 days before...

Page 6: ...rer s specific recommended values How to adjust the Bulk Float Charge Voltage LVD LVR and Night Light Mode 1 First take out all the connections to the PV controller except those to battery 2 Push up t...

Page 7: ...ation Eq charging is only for wet type Lead Acid Battery When Auto Equalization Charging is set at ON mode Equalization charge will occur for 2 hours once every thirty days Use the dip switch to selec...

Page 8: ...age Setting for one full hour with various rapid On Off pulses PWM It then switches to Float Charge Mode c FLOAT CHARGE The controller will maintain the battery voltage at the float voltage setting by...

Page 9: ...ce and the controller will return to the charging mode before the Equalization charge 4 3 12V DC Load Terminal Control Mode The 12V DC load terminal is designed for low power DC load such as street li...

Page 10: ...in Z hours before sunrise Dusk to Dawn Load is turned on all night Measure Night Length The load timer options that turn the load on again before sunrise require that the PV charge controller to measu...

Page 11: ...rotection The operation temperature of the transistors of the PV Charge Controller is also continuously monitored If excessive temperature is detected the charge controller transistors will repeatedly...

Page 12: ...e battery status Red LED See Section 3 2 Pin 8 4 Shows the battery status Green LED See Section 3 2 Table 7 Pins configuration Note Pin 3 and 5 are not used in Remote signal Terminal Rev 2 0 05 2009 7...