B. WIRING. 

  WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE 

POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE.

•  The cross - sectional area of supply cord used should be ranged from 1 - 1.5mm2.
•  Cable entry can only be made from the rear of the fan. 
•  The extraction fan is suitable for connection to 220-240V 50Hz supply. 
•  The fan is a class II double insulated product and MUST NOT be earthed.

1. Select and follow the appropriate wiring diagram. (Fig. 1, 2 & 3)
2. Check all connections have been made correctly and ensure all terminal connections and cable clamps are 

securely fastened.

Fig.1   Continuous trickle (8 L/s) with no remote boost facility.  Link Switched Live terminal to Neutral terminals. 

SL

N

L

N

~

L

SWITCHED

SPUR

FAN

MAINS

220-240VAC

LINK

Fig.2   Continuous Boost (15 L/s) with no trickle  facility. Note:- Link must be fitted between Live & Switched Live 
terminals.

SL

N

L

N

~

L

SWITCHED

SPUR

FAN

MAINS

220-240VAC

LINK

Fig.3   Continuous trickle (8 L/s) with boost facility (15L/s) via remote switch. 

SL

N

L

SL

N

L

SWITCHED

SPUR

FAN

MAINS

220-240VAC

 

Two Wire systems

Three Wire Systems