1. Select and follow the appropriate wiring diagram. (Fig. 1 or 2)
2. Check all connections have been made correctly and ensure all terminal connections and cable clamps are 

securely fastened.

Fig.1   Continuous trickle (6 or 9L/s) with no remote boost facility or Continuous Boost (15 L/s) with no trickle  
facility.

Fig.2   Continuous trickle (6 or 9 L/s) with boost facility (15L/s) via remote switch. 

SL

N

L

SL

N

L

SWITCHED SPUR

FAN

MAINS

220-240VAC

Two Wire systems

Three Wire Systems

SL

N

L

N

~

L

SWITCHED SPUR

FAN

MAINS

220-240VAC

 

1. Loosen screw. 

 

2. Pull grille 

slightly away 

from bottom 

edge. 

 

3. Push grille upwards until 

clear from the fan chassis. 

C. SETUP
 WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE 
POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE

Accessing the wiring and control settings – (Fig. 3)

 

Trickle speed selection (6l/s or 9l/s) – Fig. 4
The fan can extract at 6l/s (22m

3

/h) or 9l/s (32m

3

/h) flow 

rate.
The fan will boost to 15l/s (54m

3

/h) when the LS 

connection is switched.  

• Factory set at 6l/s (22m

3

/h).  

• Remove jumper connector (JP1) if 9l/s (32m

3

/h)  

extract flow rate is required.

 

Fig 4

DIP SWITCH

Timer adjustment
T models
OR
Humidity adjustment
HT models

JP1

JP2