Adjustments and Calibrations
Section 5
5-2
Thermometer Calibration
Occasionally, the rigors of shipping and installation
can shift the thermometer out of proper adjustment.
If the accuracy of the thermometer is in question,
place another thermometer inside the cabinet at
approximately mid-height and compare the readings.
If the thermometer requires adjustment, follow the
procedure below.
1.
Gently pry off the clear thermometer cover lens
with a small flat-bladed screwdriver.
2.
While carefully holding the dial indicator needle
with one hand, turn the slotted center pivot with a
flat-bladed screwdriver. Turn clockwise to
decrease the reading and counterclockwise to
increase the reading.
3.
Replace the clear thermometer cover lens by
pressing it into place around the perimeter.