                              Universal Thermostat Kit 

Installation Instructions 

FOR USE WITH DISPENSERS ONLY 

THIS CONTROL KIT IS INTENDED TO REDUCE OVERFILL AND CONDENSATION ISSUES 

 

1.

 

Remove all ice from dispenser. 

2.

 

Disconnect all power to the ice machine and 
dispenser at the service disconnect or fuse/breaker 
panel. 

3.

 

Move the ice machine and dispenser away from 
the wall for easier access. 

4.

 

Remove all panels and control box cover.  

5.

 

If an ice machine is already installed on the 
dispenser, raise and support the right side of the 
ice machine. Install the mounting bracket on the 
right-hand side of the dispenser 6” from the right 
rear corner.  Compress the bracket to the thickness 
of the dispenser wall and tighten the two screws. 

6.

 

Route thermistor wire out back of  the  ice 
machine/dispenser (lower  the  ice machine,  if 
supported). Remove unused knockout on  the  ice 
machine back panel, install romex  connector and 
route wire into  the  ice machine compressor 
compartment. 

7.

 

Normally the controller can be mounted on the 
bulkhead flange. If not, a suitable area must be 
found for your model.  Use controller bracket to 
locate mounting holes on the flange of the 
bulkhead.  Drill two 9/32" diameter holes (used to 
mount the controller bracket -  see View A).  

Do 

not mount the controller, at this time.

 

8.

 

Route the four wires from the temperature control 
to the control box (insuring that the wires will not 
come in contact with any refrigeration tubing).

 

IMPORTANT: 
The thermostat must be wired to match the voltage 
of the ice machine.  The thermostat is pre-wired for 
115 volts.  Rewire thermostat, if your ice machine is 
240 volts. 

9.

 

The control box line voltage wiring offers two options: 

 

Connect thermostat L1 (brown) and L2 (blue) wires 
to contactor (incoming line voltage side) L1 and L2. 

OR 

 

Disconnect incoming power line wire nuts.  
Remove quick-connect fittings from brown and 
blue wires and strip 1/2”  of insulation from the 
wires.  Connect incoming power L1, ice machine 
L1,  and thermostat L1 (brown) wires together with 
wire nut.  Connect incoming power L2, ice machine 
L2,  and thermostat L2 (blue) wires together with 
wire nut. 

10.

 

Disconnect the red male/female connector bin switch 
wire and connect the red male wire from the controller 
to the red female bin switch wire. 

11.

 

Connect the white male bin switch wire to the white 
female wire of the controller. 

12.

 

Restore all power to the ice machine and the dispenser 
at the service-disconnect or fuse/breaker panel. 

13.

 

The factory setting on the thermostat will be correct for 
most applications.  Adjust only when necessary. 

14.

 

With two screws, secure the controller bracket 
assembly to the flange of the bulkhead. 

15.

 

Reinstall the control box cover and all panels. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

View A

 

Position the controller in a suitable 
location.  It can be installed here on most 
ice machines.  Use bracket to locate 
mounting holes - drill two 9/32" holes 
through bulkhead flange to secure 
controller 

Route sensor wire between 
dispenser and ice machine 

Install romex connector in a vacant 
knockout and route sensor wire into 
compressor compartment 

Summary of Contents for K00364

Page 1: ...lock move the jumper from one pin to two pins P4 Jumper The P4 jumper labeled Jump 1 is used to set the control for heating or cooling mode Jump 2 is used to establish set point at either cut in or cut out Cubers Flake Nugget Chiplet Setting Control Set point Value To view and adjust set point follow these steps A Press MENU until the display flashes SP B Press MENU again to display the existing s...

Page 2: ...2110 South 26th Street P O Box 1720 Manitowoc WI 54221 1720 USA 8016563 Telephone 920 682 0161 Fax Sales 920 683 7589 Service Parts 920 683 7585 Other 920 683 7879 Sheet 1 of 4 Web Site www manitowocice com Rev 03 14 06 ...

Page 3: ...edures 1 Check for proper voltage to the control A Remove the cover by loosening the four cover screws B Use an AC voltmeter to check the voltage between the common and 120V or 240V terminals C The voltage must be between 102 and 132 volts for 120V applications 177 and 264 volts for 208 230V applications D If the voltage reading is not within the required range check the power source and input pow...

Page 4: ...8016563 Sheet 2 of 4 Rev 03 14 06 ...

Page 5: ...tubing IMPORTANT The thermostat must be wired to match the voltage of the ice machine The thermostat is pre wired for 115 volts Rewire thermostat if your ice machine is 240 volts 9 The control box line voltage wiring offers two options Connect thermostat L1 brown and L2 blue wires to contactor incoming line voltage side L1 and L2 OR Disconnect incoming power line wire nuts Remove quick connect fit...

Page 6: ...8016563 Sheet 3 of 4 Rev 03 14 06 ...

Page 7: ...Delay ASD 1 Temperature Offset OFS 0 Sensor Failure Operation SF 1 Cube 0 Flake Nugget Chiplet Keypad Locked Out Jumper Position Red Lead Sensor Probe Black Lead Sensor Probe Brown Lead Power Blue Lead Power Red 22AWG Lead Bin Switch or Toggle Switch White 22AWG Lead Bin Switch or Toggle Switch Route Sensor Wiring Here ...

Page 8: ...8016563 Sheet 4 of 4 Rev 03 14 06 ...

Reviews: