Working conditions

Dampers  are  designed  for  smoke  exhaust  piping  systems  with  underpressure  max.  1500  Pa  or
overpressure max. 500 Pa.
Dampers are designed for maximum air velocity 12 m/s.
Dampers are installed with the horizontal or vertical axis of the blades.

 

Dampers are intended for installation on air ducts and in/onto the walls where in the case of wall installation,

this wall with damper does not have fire resistance and therefore does not separate two fire compartments.

 

Dampers are suitable for systems without abrasive, chemical and adhesive particles.

 

Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.
Temperature in the place of installation is permitted to range from -20°C to +50°C.

 

Design with actuating mechanism

 

Belimo actuators are used for dampers, series BEN, BEE, BE for 230V AC resp. 24 V AC/DC.
After connection to the power supply voltage, the actuator moves the damper blade to the "OPEN" position
or  "CLOSED"  (according  to  the  corresponding  connection,  see  wiring  diagram).  If  the  power  supply  is
interrupted, the actuator stops at the current position. The signalling of the "OPEN" and "CLOSED" damper
blade positions is ensured by two built-in fixed “potential-free” end- limit switches.
The  actuator  for  operating  the  damper  blade  is  mounted  in  an  insulated  cover/box.  It  is  accessible  after
removing the cover lid. The electrical connection of the actuator is made with a non-flammable cable (or a
cable located in the adjoining cable duct), which passes through an opening made in the wall of the insulated
cover/box when installing the damper or when connecting the actuator power cable. The cable entry must
meet a minimum fire resistance of 30 minutes.

 

Belimo modulating actuators, BEN (BEE)-SR series for 24V AC/DC are specially designed for remote control
of fire dampers. The position of the damper blade is adjustable by means of control voltage 0 (2)...10V DC.

 

The  signalling  of  the  "OPEN"  and  "CLOSED"  damper  blade  positions  is  ensured  by  two  built-in  fixed
“potential-free” limit switches.

 

The  actuator  for  operating  the  damper  blade  is  mounted  in  an  insulated  cover/box.  It  is  accessible  after
removing  the  cover  lid.  The  electrical  connection  of  the  actuator  is  made  with  non-flammable  cables  (or
cables located in the adjoining cable duct), which pass through an opening made in the wall of the insulated
cover when installing the damper or when connecting the power cables of the actuator. The cable entry must
meet a minimum fire resistance of 30 minutes.

Summary of Contents for SEDS-L

Page 1: ......

Page 2: ...on designing ordering delivery maintenance and operation 1 Description 3 2 Design 4 3 Dimensions weights 11 4 Placement and Assembly 13 5 Suspension systems 15 6 Pressure drops 16 7 Noise data 16 8 Ma...

Page 3: ...applications according with EN 1366 9 The field of direct applications based on tests results is acceptable according to EN 1363 1 part A 1 and A 2 EN 1366 2 part 13 and EN 1366 10 part 9 Smoke extra...

Page 4: ...r blade positions is ensured by two built in fixed potential free end limit switches The actuator for operating the damper blade is mounted in an insulated cover box It is accessible after removing th...

Page 5: ...I III II Degree of protection IP 54 Adjustment time for 95 30 s Ambient temperature Storage temperature 30 C 55 C 40 C 80 C Connection drive auxiliary switch Cable 1 m 3 x 0 75 mm2 Cable 1 m 6 x 0 75...

Page 6: ...1 W 3 W 0 3 W 3 5 W 0 4 W Dimensioning 5 VA Imax 8 2 A 5 ms 5 5 VA Imax 8 2 A 5 ms 6 VA Imax 4 A 5 ms Protection class III III II Degree of protection IP 54 Adjustment time for 95 60 s Ambient temper...

Page 7: ...in the end position 12 W 0 5 W 8 W 0 5 W Dimensioning 18 VA Imax 8 2 A 5 ms 15 VA Imax 7 9 A 5 ms Protection class III II Degree of protection IP 54 Adjustment time for 95 60 s Ambient temperature Sto...

Page 8: ...30 24 controls the switching position of the actuator its adjustment time and the data exchange with the BKSE 24 6 In addition it controls the actuator current actuator connection and the power supply...

Page 9: ...work drive terminal blocks cable 1 m without plug 6 pin plug 3 pin plug screw terminals for 2x1 5 mm2 conductor yellow flashing damper rotates to the open position yellow lit up damper is open green f...

Page 10: ...valuated separately All BKNE 230 24 are controlled simultaneously A maximum of 6 BKNE 230 24 can be connected to the BKSE 24 6 Damper control is ensured with a simple 2 wire line The damper s correct...

Page 11: ...11 1 Damper body 2 Damper blade 3 Actuating mechanism cover Dimensions mm mm BEN BEE 176 5 315 BE 186 5 380 BEN BEE BKNE 236 5 315 BE BKNE 251 5 380 standard height of the flange...

Page 12: ...44 5 0 3075 BEE 5 38 5 0 1785 BEE 5 47 0 0 3485 BEE 6 41 6 0 1947 BEE 6 50 9 0 3801 BEE 6 43 6 0 2157 BEE 6 53 4 0 4211 BEE 1 15 9 0 0369 BEN 1 19 2 0 0653 BEN 2 18 3 0 0439 BEN 2 22 2 0 0777 BEN 2 19...

Page 13: ...53 1 0 4928 BEE 4 63 2 0 6647 BE 4 56 7 0 5788 BE 4 67 4 0 7807 BE 5 62 5 0 6450 BE 5 74 5 0 8700 BE 5 66 0 0 7310 BE 5 78 7 0 9860 BE 6 71 8 0 7972 BE 6 85 8 1 0753 BE 6 75 4 0 8832 BE 6 90 0 1 1913...

Page 14: ...1 Damper hinge 2 Nut 3 Washer 4 Profile C 5 Washer C 6 Wall construction without fire resistance 7 Atypical protection box with access to actuator from side not as standard from the top Installation...

Page 15: ...234 M20 245 150 300 Position 1 Threaded rod M8 M20 2 Nut 3 Washer 4 Coupling Nut 5 Anchor 6 Hinge plate min thickness 10 mm 7 Concrete screw tested for fire resistance R30 R90 max Tension up to 0 75...

Page 16: ...63 68 68 67 65 62 48 57 65 70 70 69 67 64 50 w air velocity in the free cross section AxB i e before blades f frequency of octave band Sound power level corrected with filter A ps static pressure drop...

Page 17: ...67 65 62 48 w air velocity in the free cross section AxB i e before blades f frequency of octave band 13 21 26 26 25 23 20 6 21 29 34 34 33 31 28 14 28 36 41 41 40 38 35 21 34 42 47 47 46 44 41 27 38...

Page 18: ...re must be in the range from 5 C to 40 C and maximum relative humidity 80 Dampers must be protected against mechanic damages when transported and manipulated All effective safety standards and directi...

Page 19: ...ith cables from actuator acc to above mentioned electrical diagram Seal up the space around cable with fire resistant mastic HILTI CFS S ACR PROMASTOP or equivalent Let the mastic harden Drill two hol...

Page 20: ...o ensure that the damper is put into condition in which it is ready for function and meanwhile he is obliged to provide the fire protection by another appropriate way Results of regular checks imperfe...

Page 21: ...tuating mechanism BEN BEE BE for 230V 44 with actuating mechanism BEN BEE BE for 24V 54 with actuating mechanism BEN BEE SR for 24V 65 with the communication and supply device BKNE 230 24 and actuatin...

Page 22: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: