Page 15
Version 2023-03-07
Fire damper - FDMQ 120
TPM 162/22
■
Design with the communication and supply device BKN
230-24MP and actuator BF 24TL-TN-ST for connection to
MP-Bus.
■
BKN 230-24MP supplies to the intelligent actuators of fire
dampers BF 24TL-TN-ST decentrally needed power supply.
■
In this way can be realize long MP-Bus communications
(up to 800 m).
■
Up to 8 Bus nodes can be parallel connected and
controlled by Master device (DDC with interface).
■
Device can be equipped with an external smoke detector.
Design .62
Communication and supply device BKN 230-24MP
Nominal voltage
AC 230 V 50/60Hz
Power consumption
8 W (including actuator)
Dimensioning
10 VA (including actuator)
Protection Class
II
Degree of protection
IP 40
Ambient temperature
Non-operating temperature
-30°C … +50°C
-40°C … +80°C
Connection - net
- motor (BF ...-Top)
- net MP
- actuating mechanism (variable)
- Top-Line PC-Tool (via ZIP-RS232)
cable 1 m with EURO plug
4-pole connector
screw terminals 2-pole
screw terminals 2-pole
3-pole connector
Communication and supply device BKN 230-24MP
PC Tool
1
7
Ya
24V
GND
MP
1)
2)
24V
AC230 V
GND
MP
net MP-Bus
additional external conntact,
e.g. fire smoke detector