![Mandik FDMB Technical Documentation Manual Download Page 34](http://html2.mh-extra.com/html/mandik/fdmb/fdmb_technical-documentation-manual_4025453034.webp)
FDMB - Fire damper
Page 34
Version 2022-12-20
TPM 164/22
C
1
FDMB
2
Ablative Coated Batt (e.g. Firestop Board HILTI CFS-CT B 1S 140/50 - min. density
140 kg/m
3
+ Firestop acrylic sealant HILTI CFS-S ACR or equivalent)
3
Gyproc FireLine
4
Gyproc CoreBoard
5
Gypframe 'I' Stud
6
Gypframe Retaining Channel
7
Gypframe Deep Flange Floor & Ceiling Channels
8
Duct
9
Protective cladding boards - (not part of the damper) but must be used as part of
the penetration filling. It can be ordered from MANDÍK as an accessory (e.g.
PROMATECT-MST - min. density 750 kg/m
3
for AxB ≤ 500x400, th. 10 mm, for AxB
> 500x400, th. 15 mm or equivalent)
10 Fire resistant mastic - fill the gap on both sides of the fire separation construction
and around the perimeter of penetration and damper body. (e.g. HILTI CFS-S ACR)
11 Fixing profile with threaded rod
Shaft wall British gypsum - Ablative Coated Batt
■
For connection following duct
■
Follow the instructions of the shaft wall producer.
■
All technical specifications and conditions can be found at
■
Damper can be installed on either side of the wall.
B-B
40...130
C
B
m
in
.
B
+
8
0
m
a
x
.
B
+
2
6
0
A
min. A+80
max. A+260
A
A
B
B
A-A
4
0
..
.1
3
0
B
B
EIS 90 with fire resistance wall EI 90
EIS 60 with fire resistance wall EI 60