Statement  of installations

 

Examples of smoke damper installing

 

The  smoke  damper  can  be  installed  into  a  solid  wall  construction  made  e.g.  of  normal
concrete/masonry,  porous  concrete  with  minimum  thickness  100  mm  or  into  solid  ceiling
construction made e.g.  of  normal  concrete/porous  concrete  with  minimum  thickness 150  mm.
Recommended installation openings are specified in Fig. 5.

 

The  smoke  damper  can  be  installed  into  a  gypsum  wall  construction  with  minimum  thickness
100 mm

 

The smoke damper can also be installed outside of wall (ceiling) construction.

Damper installed in a solid wall construction. Space between damper and wall is filled
by mortar, gypsum or another approved fire sealing system for damper installation.

ES 30

6

Damper  installed  in  a  solid  wall  construction.  Space  between  damper  and  wall    is
filled  by  mineral  stone  wool  (min.  density  140  kg/m

³

)  or  another  approved  fire

insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness  1 mm.

ES 30

7

Damper installed in a gypsum wall construction. Space between damper and wall is
filled  by  mortar,  gypsum  or  another  approved  fire  sealing  system  for  damper
installation.

ES 30

8

Damper installed in a gypsum wall construction. Space between damper and wall  is
filled  by  mineral  stone  wool  (min.  density  140  kg/m

³

)  or  another  approved  fire

insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness  1 mm.

ES 30

9

Damper installed in a solid ceiling construction. Space between damper and ceiling
is  filled  by  mortar,  gypsum  or  another  approved  fire  sealing  system  for  damper
installation.

ES 30

10

Damper installed in a solid ceiling construction. Space between damper and wall  is
filled  by  mineral  stone  wool  (min.  density  140  kg/m

³

)  or  another  approved  fire

insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness  1 mm.

ES 30

11

Damper  installed  outside  of  a  solid  wall  construction.  Space  between  damper  and
wall  is filled by mortar, gypsum or another approved fire sealing system for damper
installation.

ES 30

12

Damper  installed  outside  of  a  solid  wall  construction.  Space  between  damper  and
wall  is filled by mineral stone wool (min. density 140 kg/m

³

) or another approved fire

insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness  1 mm.

ES 30

13

Damper installed outside of a gypsum wall construction. Space between damper and
wall  is filled by mortar, gypsum or another approved fire sealing system for damper
installation.

ES 30

14

Damper installed outside of a gypsum wall construction. Space between damper and
wall  is filled by mineral stone wool (min. density 140 kg/m

³

) or another approved fire

insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness  1 mm.

ES 30

15

Damper installed outside of a solid ceiling construction. Space between damper and
wall  is filled by mortar, gypsum or another approved fire sealing system for damper
installation.

ES 30

16

Damper installed outside of a solid ceiling construction. Space between damper and
wall  is filled by mortar, gypsum or another approved fire sealing system for damper
installation.

ES 30

17

Damper installed outside of a solid ceiling construction. Space between damper and
wall  is filled by mortar, gypsum or another approved fire sealing system for damper
installation. BEWARE OF FIRE SIDE!

E 90, ES 60

18

Damper installed outside of a gypsum wall construction. Space between damper and
wall    is  filled  by  mortar  and  gypsum  or  another  approved  fire  sealing  system  for
damper installation. BEWARE OF FIRE SIDE!

ES 90

19

Summary of Contents for DM-S

Page 1: ......

Page 2: ...dering delivery assembly and operation 1 Description 3 2 Design 4 3 Dimensions weights 4 4 Placement and Assembly 6 5 Statement of installations 7 6 Pressure loss and Noise data 15 7 Electrical Compon...

Page 3: ...securing of proper closing and safe function of Smoke Damper in case of Fire c The air circulation in the whole damper section must be secured as steady on whole surface Damper characteristics Tested...

Page 4: ...the breakdown position CLOSED The time of displacing the blade from the position OPEN to the position CLOSED takes maximum 16 s In case that the power supply is restored again the blade can be in any...

Page 5: ...BFN 45 5 55 5 4 9 0 0886 BFN 48 58 5 0 0 0918 BFN 70 80 5 5 0 1176 BFN 120 130 6 6 0 1863 BFN 185 195 14 0 0 2138 BF For round smoke damper the open damper blade overlaps the damper body from dimensi...

Page 6: ...ore dampers are supposed to be installed in one fire separating construction the distance between the adjacent dampers must be min 200 mm according to EN 1366 2 paragraph 13 5 The control mechanism ha...

Page 7: ...led by mineral stone wool min density 140 kg m or another approved fire insulation system Surface is covered by fire protection mastic Promastop P K or equal min thickness 1 mm ES 30 11 Damper install...

Page 8: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 9: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 10: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 11: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 12: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 13: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 14: ...ortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper instal...

Page 15: ...24 28 32 35 37 8 14 21 31 42 55 69 86 1 1 1 2 3 4 5 6 217 290 362 434 507 579 651 724 1357 1810 2262 2714 3167 3619 4072 4524 4 5 6 7 8 10 11 12 3 4 5 6 7 9 10 11 18 25 31 36 40 43 46 49 6 14 20 24 28...

Page 16: ...y voltage and safety extra low voltage not permitted at the both auxiliary switches Application examples for integration into monitoring and control systems or into bus networks can be found in the do...

Page 17: ...en transported and manipulated During transportation the damper blade must be in the CLOSED position Dampers are stored indoor in environment without any aggressive vapours gases or dust Indoor temper...

Page 18: ...ble to serve for their function for any cause it must be clearly marked The operator is obliged to ensure so that the damper is put into condition in which it is able to function and meanwhile he is o...

Page 19: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: