Smoke dampers are installed in duct served for smoke outlet. Damper closes the smoke duct.
Dampers are installed in the position "OPEN". Dampers blade automatically closes air duct using
an  actuating  mechanism  back  spring.  The  back  spring  of  the  actuating  mechanism  is  started
when the thermoelectrical starting mechanism BAT is activated, when a reset button on BAT is
pushed or when a power supply of the actuating mechanism is stopped.

Working conditions

Right damper function is secured under the following conditions:

 

  

a) Maximum air circulation speed: 12 m/s

 

  

Maximum pressure difference: 1200 Pa

 

  

b) Dampers  could  be  displaced  into  position  “CLOSED”  only  in  case  that  ventilator  is

  

  switched  off.  The  goal  is  the  securing  of  proper  closing  and  safe  function  of  Smoke

  

  Damper in case of Fire.

 

  

c) The  air  circulation  in  the  whole  damper  section  must  be  secured  as  steady  on  whole

  

  surface.

Damper characteristics

• Tested in accordance with EN 1366-2
• Classified acc. to EN 13501-3+A1 as 

E 30 ve, ho (i

o) S or E 90 (ho i

o) or E 60 (ho i

o) S or

E 90 (ve i

o) S

• Fire resistance ES 30 (ES 60, E 90)
• ES Certificate of conformity No. 1391-CPR-2016/0083
• Declaration of Performance No. PM/DM-S/01/20/1
• Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19b

 

Operation of the dampers does not depend on the direction of air circulation. The dampers can
 be located in an arbitrary position.

Dampers are suitable for systems without abrasive, chemical and adhesive particles.

 

Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.

 

Temperature in the place of installation is permitted to range from - 30°C to + 50°C.

Summary of Contents for DM-S

Page 1: ......

Page 2: ...dering delivery assembly and operation 1 Description 3 2 Design 4 3 Dimensions weights 4 4 Placement and Assembly 6 5 Statement of installations 7 6 Pressure loss and Noise data 15 7 Electrical Compon...

Page 3: ...securing of proper closing and safe function of Smoke Damper in case of Fire c The air circulation in the whole damper section must be secured as steady on whole surface Damper characteristics Tested...

Page 4: ...the breakdown position CLOSED The time of displacing the blade from the position OPEN to the position CLOSED takes maximum 16 s In case that the power supply is restored again the blade can be in any...

Page 5: ...BFN 45 5 55 5 4 9 0 0886 BFN 48 58 5 0 0 0918 BFN 70 80 5 5 0 1176 BFN 120 130 6 6 0 1863 BFN 185 195 14 0 0 2138 BF For round smoke damper the open damper blade overlaps the damper body from dimensi...

Page 6: ...ore dampers are supposed to be installed in one fire separating construction the distance between the adjacent dampers must be min 200 mm according to EN 1366 2 paragraph 13 5 The control mechanism ha...

Page 7: ...led by mineral stone wool min density 140 kg m or another approved fire insulation system Surface is covered by fire protection mastic Promastop P K or equal min thickness 1 mm ES 30 11 Damper install...

Page 8: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 9: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 10: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 11: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 12: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 13: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 14: ...ortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper instal...

Page 15: ...24 28 32 35 37 8 14 21 31 42 55 69 86 1 1 1 2 3 4 5 6 217 290 362 434 507 579 651 724 1357 1810 2262 2714 3167 3619 4072 4524 4 5 6 7 8 10 11 12 3 4 5 6 7 9 10 11 18 25 31 36 40 43 46 49 6 14 20 24 28...

Page 16: ...y voltage and safety extra low voltage not permitted at the both auxiliary switches Application examples for integration into monitoring and control systems or into bus networks can be found in the do...

Page 17: ...en transported and manipulated During transportation the damper blade must be in the CLOSED position Dampers are stored indoor in environment without any aggressive vapours gases or dust Indoor temper...

Page 18: ...ble to serve for their function for any cause it must be clearly marked The operator is obliged to ensure so that the damper is put into condition in which it is able to function and meanwhile he is o...

Page 19: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: