background image

Summary of Contents for DM-S

Page 1: ......

Page 2: ...dering delivery assembly and operation 1 Description 3 2 Design 4 3 Dimensions weights 4 4 Placement and Assembly 6 5 Statement of installations 7 6 Pressure loss and Noise data 15 7 Electrical Compon...

Page 3: ...securing of proper closing and safe function of Smoke Damper in case of Fire c The air circulation in the whole damper section must be secured as steady on whole surface Damper characteristics Tested...

Page 4: ...the breakdown position CLOSED The time of displacing the blade from the position OPEN to the position CLOSED takes maximum 16 s In case that the power supply is restored again the blade can be in any...

Page 5: ...BFN 45 5 55 5 4 9 0 0886 BFN 48 58 5 0 0 0918 BFN 70 80 5 5 0 1176 BFN 120 130 6 6 0 1863 BFN 185 195 14 0 0 2138 BF For round smoke damper the open damper blade overlaps the damper body from dimensi...

Page 6: ...ore dampers are supposed to be installed in one fire separating construction the distance between the adjacent dampers must be min 200 mm according to EN 1366 2 paragraph 13 5 The control mechanism ha...

Page 7: ...led by mineral stone wool min density 140 kg m or another approved fire insulation system Surface is covered by fire protection mastic Promastop P K or equal min thickness 1 mm ES 30 11 Damper install...

Page 8: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 9: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 10: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 11: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 12: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 13: ...Mortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper inst...

Page 14: ...ortar or gypsum 1 Smoke damper DM S 3 Fire protection mastic Promastop P K or equal min 2 Stuffing box mineral stone wool min density 140 kg m or another approved fire sealing system for damper instal...

Page 15: ...24 28 32 35 37 8 14 21 31 42 55 69 86 1 1 1 2 3 4 5 6 217 290 362 434 507 579 651 724 1357 1810 2262 2714 3167 3619 4072 4524 4 5 6 7 8 10 11 12 3 4 5 6 7 9 10 11 18 25 31 36 40 43 46 49 6 14 20 24 28...

Page 16: ...y voltage and safety extra low voltage not permitted at the both auxiliary switches Application examples for integration into monitoring and control systems or into bus networks can be found in the do...

Page 17: ...en transported and manipulated During transportation the damper blade must be in the CLOSED position Dampers are stored indoor in environment without any aggressive vapours gases or dust Indoor temper...

Page 18: ...ble to serve for their function for any cause it must be clearly marked The operator is obliged to ensure so that the damper is put into condition in which it is able to function and meanwhile he is o...

Page 19: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: