16
NOTICE
•
The installer MUST test for proper connection and functionality of the operator and its accessories
before leaving the job site.
•
The installer should also perform a demonstration for the end-user.
8.1
Low Voltage (Controls) and High Voltage (Power) Connections
1. Route the power line wire from the
right of the control box, as shown in
Figure 18.
2. Route all low voltage control wires
from the left of the control box, as
shown in Figure 18. KEEP LOW
VOLTAGE WIRES SEPARATE FROM
LINE VOLTAGE WIRES.
3. USE COPPER CONDUCTORS ONLY.
8.2
Main Power Supply Connection
Single-Phase (115/230V)
Three-Phase (208/230-460-575V)
Correct motor rotation: Switch the BLUE and ORANGE
motor wires on the contactor.
Correct motor rotation: Switch ANY TWO incoming lines
(phase) on the power terminal block.
For technical support, please call
1-800-361-2260
for more information
Figure 18 - Low Voltage (Controls)
and High Voltage (Power)
Connections
Line 1
Line 2
Line 3
Ground Lug
P
o
w
er
T
er
m
in
al
B
lo
ck
NEUTRAL
LIVE
P
o
w
er
T
er
m
in
al
B
lo
ck
Power
Control
Ground Lug