background image

 7 

MAMM-WSHP-IOM-1KA (September 2011) 

1.  If the K-Vintage units are equipped with optional 

water shutoff valves, either electric or pressure op-
erated, the supply and return run-outs must be con-
nected at each heat pump location. This will pre-
vent the introduction of dirt into the heat pump. 

2.  Fill the system at the city water makeup connection 

with all air vents open. After filling, close all air 
vents. 

3.  The contractor should start the main circulator with 

the pressure reducing valve open. Check vents in 
sequence to bleed off any trapped air, providing 
circulation through all components of the system. 

4.  While circulating water, the contractor should check 

and repair any leaks in the piping. Drains at the 
lowest point(s) in the system should be opened for 
the initial flush and blow down, making sure city 
water fill valves are set to make up water at the 
same rate. Check the pressure gauge at the pump 
suction and manually adjust the makeup to hold the 
same positive steady pressure both before and 
after opening the drain valves. Flush should con-
tinue for at least two hours, or longer if required, 
until the drain water is clear and clean. 

Cleaning and Flushing 

5.  Shut off the circulator pump and open all drains 

and vents to completely drain down the system. 
Short circuited supply and return runouts should 
now be connected to the heat pump supply and 
return connections. Do not use sealers at the 
swivel flare connections of the hoses. 

6.  Refill the system with clean water. Test the water 

using litmus paper for acidity and treat as required 
to leave the water slightly alkaline (pH 7.5 to 8.5). 
The specified percentage of antifreeze may also be 
added at this time. Use commercial grade anti-
freeze designed for HVAC systems only. Do not 
use automotive grade antifreeze. 

7.  Once the system has been filled with clean water 

and antifreeze (if used), precaution should be taken 
to protect the system from dirty water conditions. 
Dirty water will result in system wide performance 
degradation and solids may clog valves, strainers, 
flow regulators, etc. Additionally, the heat exchang-
ers may become clogged which reduces compres-
sor service life or causes premature failure. 

8.  Set the loop water controller heat add setpoint to 

70°F and the heat rejection setpoint to 85°F. Sup-
ply power to all motors and start the circulation 
pumps. After full flow has been established through 
all components including the heat rejecter 
(regardless of season) and air has been vented 
and loop temperatures have been stabilized, each 
of the heat pumps will be ready for check, test and 
start-up, and water balancing. 

 

IMPORTANT:  

Prior to first operation of K-Vintage units, the water 
circulation system must be cleaned and flushed of all 
construction dirt and debris.  After the cleaning 
and flushing has taken place, the initial connection 
should have all valves wide open in preparation for 
the water system flushing.

 

 

Summary of Contents for K Vintage

Page 1: ...MAMM WSHP IOM 1KA September 2011 Vertical Water to Water Heat Pumps With R 410A Installation Operation and Maintenance Manual Sizes 064 to 480 Model K Vintage P N 71144912 ...

Page 2: ...n 4 Unit Location 5 Piping 6 Cleaning and Flushing 7 Start up 8 Operating Limits 9 Controls 10 Inputs Outputs 13 General Maintenance 14 Parts and Service Support 14 Troubleshooting 15 Performance Troubleshooting 16 Unit check out sheet 17 Table of Contents K Vintage Water to Water Sizes 064 to 480 ...

Page 3: ...tation on the shipper s delivery ticket before signing If there is any evidence of rough han dling immediately check for concealed damage If any damage is found notify the carrier within 48 hours to establish your claim and request their inspection and a report Then contact the Mammoth Service department at 952 358 6618 or info mammoth inc com for a warranty claim number Do not stand or transport ...

Page 4: ...he location and routing of water piping and electrical wiring The locations of these items are clearly marked on the submittal drawings 7 Mammoth recommends the unit be covered during construction to protect components from dust and other harmful materials This is critical while spray ing fireproofing material on bar joists sandblasting spray painting and plastering NOTE Check the unit name plate ...

Page 5: ... be beneficial but not always necessary The requirements on any specific unit may increase or be reduced depending on several factors such as maintenance requirements and mechanical or electrical installation codes The electrical connections are accessible from the front The compressor can be accessed from either side There are no air filter ductwork or ventilation air requirements for K Vintage w...

Page 6: ...f the water connection on the unit One end of the hose should have a swivel fitting to facilitate removal for service Hard piping can also be brought directly to the heat pump This option is not recommended since no vibration or noise attenuation can be accomplished The hard piping must have a union to facilitate heat pump removal 4 The supply and the discharge pipes should be insulated to prevent...

Page 7: ...pump supply and return connections Do not use sealers at the swivel flare connections of the hoses 6 Refill the system with clean water Test the water using litmus paper for acidity and treat as required to leave the water slightly alkaline pH 7 5 to 8 5 The specified percentage of antifreeze may also be added at this time Use commercial grade anti freeze designed for HVAC systems only Do not use ...

Page 8: ...ure controller to the off position The unit will stop running and the reversing valve should de energize 6 Leave unit off for approximately five minutes to allow pressure to equalize 7 Adjust temperature controller to lowest setting 8 Set temperature controller to heat 9 Slowly adjust temperature controller to higher temperature until the compressor energizes 10 Check the heating high and low refr...

Page 9: ...nst ex tremes in temperature and or humidity and equipment performance reliability and service life may be ad versely affected Note Voltages listed are to show voltage range However units operating with over or under voltage conditions for extended periods of time will experience premature component failure Three phase system imbalance should not exceed 2 APPLICATION LIMITS Standard range Low Temp...

Page 10: ...diagnostic Random start time delay from 5 to 35 seconds Compressor anti short cycle protection for 300 seconds 5 minutes Compressor and reversing valve control Compressor lockout with selectable intelligent manual reset LED status on the board Lockout alarm signal to the temperature controller in the event of a safety circuit fault Operable on 50 and 60 cycle power Emergency shutdown from a field ...

Page 11: ...nication to the Mammoth line of intelligent space sensors and keypad display units Key Features and Benefits I O point count 5 digital outputs relayed and 6 universal imputs Built in protocol support BACnet ARCNET and MS TP Modbus RTU and N2 Optional plug in communica tions boards LonTalk On board battery backed real time clock is standard thus enabling full stand alone scheduling capabilities as ...

Page 12: ... s line of intelligent space sensors and keypad display units Key Features and Benefits I O point count 5 digital outputs relayed 8 inputs and 3 analog outputs Built in protocol support BACnet ARCNET and MS TP Modbus RTU and N2 Optional plug in communica tions boards LonTalk On board battery backed real time clock is standard thus enabling full stand alone scheduling capabilities as well as histor...

Page 13: ...mpressor Call 1 Thermistor Dry Contact Load Supply Water Temperature Outlet Load Return Water Temperature Inlet Thermistor Dry Contact Source Leaving Water Temperature Outlet Source Entering Water Temperature Inlet Description Notes 1 Multiplexed inputs 5 6 use 10K 4 99K 2 49K resistors for contact inputs 1 24K resistor not used Could do more stages if cooling call and pump started externally A mi...

Page 14: ...ution flow rate should be at least 1 5 times the normal flow rate preferably in backflush mode Before restarting flush the unit with plenty of fresh water to purge any remaining acid Clean at regular intervals Improper Unit Functioning If unit is not performing properly several readings of temperature pressure and electrical characteristics need to be taken The normal required troubleshooting info...

Page 15: ...ve should be in stalled in the charging line to flash the liquid to vapor while charging All Mammoth K Vintage units are designed for commercial use Units are designed for the cooling mode of operation and fail safe to heating Troubleshooting Refrigeration Circuit Symptom Head Pressure Suction Pressure Compressor Amp Draw Super Heat Subcooling Water Loops Temp Differential Safety Lock Out Charge U...

Page 16: ...cold Check load loop sizing loop backfill ground moisture High head pressure X Reduced or no water flow in cooling Check pump operation or valve operation setting Check water flow adjust to proper flow rate X Inlet water to hot Check load loop sizing loop backfill ground moisture X Scaling in waterside heat exchanger Perform scaling check and clean if necessary X X Unit overcharged Check superheat...

Page 17: ...s __________________ Operating Conditions Unit Conditions Cooling Mode Heating Mode Entering Fluid Temperature _____________ _____________ Leaving Fluid Temperature _____________ _____________ Fluid Flow gpm _____________ _____________ Fluid Side Pressure Drop _____________ _____________ Compressor 1 2 Mode Cooling Heating Cooling Heating Suction Pressure psig _______ _______ _______ _______ Disch...

Page 18: ...18 MAMM WSHP IOM 1KA September 2011 Notes ...

Page 19: ...19 MAMM WSHP IOM 1KA September 2011 Notes ...

Page 20: ... has a policy of continuous product improvement and reserves the right to change design and specifications without notice 2011 Mammoth Inc MAMM WSHP IOM 1KA September 2011 info mammoth inc com www mammoth inc com ...

Reviews: