HU-224/225 humidity transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these humidity transducers with VDC output:

Wiring HU-224/225 Units with VDC Output

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [O] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the negative output terminal.
4.  Connect the [O] terminal, which is the positive VDC output terminal, to the controller’s input terminal.
5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [O] and [-] terminals.

TYPICAL APPLICATIONS (wiring diagrams)

Model HU-224/225

Technical Information

TI.224/225-08

HUMIDITY SENSOR

Page 3 of 4

HU-224

DUCT MOUNT

0 to 10 VDC (default)

0 to 5 VDC

HU-225

WALL MOUNT

0 to 10 VDC (default)

0 to 5 VDC

1

2

O N

1

2

O N

VDC Output

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Figures 3 & 4

 illustrate typical wiring diagrams for the HU-224/225, 0–5/0–10 VDC output humidity transducers.

Figure 3 – 

Wiring for VDC Output when applied with External AC Supply.

Figure 4 – 

Wiring for VDC Output when applied with External DC Power Supply.

Signal

+

Common

Supply

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–40 VDC Power Supply

RoHS

0 to 10 VDC 

(

Factory Default

)

1

2

O N

1

2

O N

HU-224 (Duct Mount)

Board Layout

HU-225 (Wall Mount)

Board Layout

0 to 10 VDC 

(

Factory Default

)

Figure 5 – 

Dip Switch Settings for HU-224/225 VDC Output

S   Z

ON

1

2

SPAN
ZERO

0

   -

    

+

ZERO
SPAN

Z    S

+

   

-

 

    

0

ON

1

2

Summary of Contents for HU-224

Page 1: ...ng diagram and in accordance with national and local electrical codes Use copper conductors only Caution Use electrostatic discharge precautions e g use of wrist straps during installation and wiring to prevent equipment damage Avoid locations where severe shock or vibration excessive moisture or corrosive fumes are present NEMA Type 4 housings are intended for outdoor use primarily to provide a d...

Page 2: ...Shield Ground Controller Meter Recorder mA Output Transducer Only Figures 1 2 illustrate typical wiring diagrams for the HU 224 225 4 20 mA two wire humidity transducers Figure 1 Wiring for mA Output Humidity Transducers with External DC Power Supply Figure 2 Wiring for mA Output Humidity Transducers where Controller or Meter has Internal DC Power Supply If you are using grounded AC the hot wire m...

Page 3: ...TIONS wiring diagrams Model HU 224 225 Technical Information TI 224 225 08 HUMIDITY SENSOR Page 3 of 4 HU 224 DUCT MOUNT 0 to 10 VDC default 0 to 5 VDC HU 225 WALL MOUNT 0 to 10 VDC default 0 to 5 VDC 1 2 O N 1 2 O N VDC Output Signal Common Supply Neutral Hot O Input Signal Common Shield Ground Controller Meter Recorder VDC Output Transducer Only 12 35 VAC Transformer Figures 3 4 illustrate typic...

Page 4: ...nsure humidity is stable and adjust zero trimmer Z Then select a controlled humidity environment between 70 75 RH Insure humidity is stable and then adjust span trimmer S All units are factory calibrated to meet or exceed published specifications If field adjustment is necessary follow the instructions below MAINTENANCE Regular maintenance of the total system is recommended to assure sustained opt...

Reviews: