Model HU-224/225

Technical Information

TI.224/225-08

HUMIDITY SENSOR

Page 2 of 4

TYPICAL APPLICATIONS (wiring diagrams)

HU-224/225 humidity transducers are 4–20 mA output units powered with a 12–40 VDC supply.

The following describes the proper wiring of these humidity transducers with mA output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller.
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in series with the [-] terminal.

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figures 1 & 2

 illustrate typical wiring diagrams for the HU-224/225, 4–20 mA, two-wire humidity transducers.

Figure 1 – 

Wiring for mA Output Humidity Transducers with External DC Power 

Supply.

Figure 2 – 

Wiring for mA Output Humidity Transducers where Controller or

Meter has Internal DC Power Supply.

If you are using grounded AC, the hot wire must be on the [+] terminal.  Also, if you are using a controller without built-in isolation, use an isolation transformer to 

supply the HU-224/225 transducer.

This product contains a half-wave rectifier power supply and must not be powered off transformers used to power other devices utilizing non-isolated full-wave

rectifier power supplies. 

When multiple HU-224/225 units are powered from the same transformer, damage will result unless all 24G power leads are connected to the same power lead on 

all devices.  It is mandatory that correct phasing be maintained when powering more than one device from a single transformer. 

RoHS

HU-224

Duct Mount

HU-225

Wall Mount

Wiring HU-224/225 Units with mA Output

mA Output

CAUTION!

S    Z

SPAN
ZERO

-   +

Z   S

+  -

SPAN
ZERO

Summary of Contents for HU-224

Page 1: ...ng diagram and in accordance with national and local electrical codes Use copper conductors only Caution Use electrostatic discharge precautions e g use of wrist straps during installation and wiring to prevent equipment damage Avoid locations where severe shock or vibration excessive moisture or corrosive fumes are present NEMA Type 4 housings are intended for outdoor use primarily to provide a d...

Page 2: ...Shield Ground Controller Meter Recorder mA Output Transducer Only Figures 1 2 illustrate typical wiring diagrams for the HU 224 225 4 20 mA two wire humidity transducers Figure 1 Wiring for mA Output Humidity Transducers with External DC Power Supply Figure 2 Wiring for mA Output Humidity Transducers where Controller or Meter has Internal DC Power Supply If you are using grounded AC the hot wire m...

Page 3: ...TIONS wiring diagrams Model HU 224 225 Technical Information TI 224 225 08 HUMIDITY SENSOR Page 3 of 4 HU 224 DUCT MOUNT 0 to 10 VDC default 0 to 5 VDC HU 225 WALL MOUNT 0 to 10 VDC default 0 to 5 VDC 1 2 O N 1 2 O N VDC Output Signal Common Supply Neutral Hot O Input Signal Common Shield Ground Controller Meter Recorder VDC Output Transducer Only 12 35 VAC Transformer Figures 3 4 illustrate typic...

Page 4: ...nsure humidity is stable and adjust zero trimmer Z Then select a controlled humidity environment between 70 75 RH Insure humidity is stable and then adjust span trimmer S All units are factory calibrated to meet or exceed published specifications If field adjustment is necessary follow the instructions below MAINTENANCE Regular maintenance of the total system is recommended to assure sustained opt...

Reviews: