• When multiple transducers are powered from the same transformer, damage 

will result unless all 24-gage power leads are connected to the same power 
lead on all transducers. Maintain the correct phasing when powering more than 
one transducer from a single transformer.

Wiring the Wall Mount Humidity Transducer for VDC Output

Figures 6 and 7 illustrate proper VDC output wiring for the wall mount humidity 
transducer.

Figure 6. 

Wall Mount Wiring for 0 - 5 VDC Output

Figure 7.

 Wall Mount Wiring for 0 - 10 VDC Output

Wiring the Duct Mount Humidity Transducer for VDC Output

Figures 8 and 9 illustrate proper VDC output wiring for the duct mount humidity 
transducer.

Figure 8. 

Duct Mount Wiring for 0 - 5 VDC Output

Figure 9. 

Duct Mount Wiring for 0 - 10 VDC Output

Typical Applications (wiring diagrams)

Figures 10 and 11 illustrate typical wiring diagrams for the mA output humidity 
transducers.

Figure 10. 

Wiring mA Output Transducers With an External DC

Power Supply

Figure 11.

 Wiring mA Output Transducers Where the Controller 

or Meter Has an Internal DC Power Supply

Figures 12 and 13 illustrate typical wiring diagrams for the VDC output humidity 
transducers.

Figure 12. 

Wiring VDC Output Transducers With an

External AC Power Supply

Figure 13. 

Wiring VDC Output Transducers With an

External DC Power Supply

Checkout

1.

Verify that the transducer is mounted in the correct position.

2.

Verify the appropriate input signal and supply voltage.

3.

Verify the appropriate configuration range.

Caution!

• Do not connect 120 VAC to the humidity transducers. AC voltage should never 

be supplied to a transducer intended for DC power.

Transducer Operation

This humidity transducer is a highly accurate device. For applications requiring a 
high degree of accuracy, use laboratory quality meters and gages.

Calibration

All transducers are factory calibrated to meet or exceed published specifications. 
If field adjustment is necessary, follow these instructions:

1.

Do not verify comparative RH with a sling psychrometer. Doing so can 

introduce errors into the calibration process. New humidity transducers are 
already calibrated.

2.

Recalibrate the humidity in a controlled environment only. Relative humidity 

must be held stable while making any adjustment.

3.

Verify the output from the transducer directly with calibrated instrumentation. 

Verify the RH with calibrated instrumentation, not a controller output. With the 
correct power applied and only a meter connected to the output of the 
transducer, ensure that the output is proportional to the true RH.

4b.

Single-point Calibration 

Select either option 1 or option 2:
Option 1: Select a controlled humidity environment between 10 to 40% RH. 
Ensure humidity is stable and adjust the zero trimmer [Z].
Option 2: Select a controlled humidity environment between 40 to 70% RH. 
Ensure humidity is stable and adjust the span trimmer [S].

4b.

Two-point Calibration

Select a controlled humidity environment between 10 and 40% RH. Ensure 
humidity is stable and adjust the zero trimmer [Z]. Then select a controlled 
humidity environment between 70 and 75% RH. Ensure humidity is stable 
and adjust the span trimmer [S].

Maintenance

Perform regular maintenance on the total system to ensure the sustained 
optimum performance of the humidity transducer.

Field Repair

Do not attempt to repair the humidity transducer. Replace the malfunctioning 
transducer with a functional transducer if necessary.

Warranty

See the accompanying data sheet for additional information. For technical / 
application assistance, call your nearest office.

Copyright 

©

 Mamac Systems 2003. All rights reserved.

EUROPE

AUSTRALIA

Baird House, Units 6 & 7

Dudley Innovation Centre

Pensnett Estate • Kingswinford

West Midlands • DY6 8XZ

United Kingdom

01384-271113 • Fax 01384-271114

4 Armiger Court, Unit 2
Holden Hill • S.A. 5088

Australia

08-8359-4333 • Fax 08-8395-4433

ASIA

CANADA

No. 22 Lorong 21A Geylang

#11-02 Chin Hin Hang Building

Singapore • 388431

65-6392-7273 • Fax 65-6392-7276

155 Mcintosh Drive, Unit 5

Markham • Ontario • L3R 0N6

Canada

905-474-9215 • Fax 905-474-0876

Reviews: