INSTRUCTIONS FOR AUTO TEST
1. Install luminaire according to installation instruction sheet
2. Once the unit is powered up it will automatically initiate a self test and diagnostics as follows:
4. Manual Testing
3. Dual color indicator LED status Meanings
All test functions are factory preset and do not need field adjustment
• Every month: Performs a 3 minute duration test
• Every year: Performs a 1 Hour or 3 Hour duration test
•
One flash, 4 second pause
Battery not connected
••
Two flashes, 4 second pause
Battery short or low battery voltage
•••
Three flashes, 4 second pause
Charge board fault
••••
Four flashes, 4 second pause
Transformer fault
•••••
Five flashes, 4 second pause
LED lamp fault
NOTE:
After repairing a service fault, press and hold the test button for 2 seconds to reset the
flashing indicator light to green.
Press test button once
30 seconds duration test
Press test button twice (within 2 seconds)
3 minutes duration test
Press test button 3 times (within 2 seconds)
30 minutes duration test
Press test button 4 times (within 2 seconds)
3 hours duration test
120 mm
SPECIFICATION
Discharge
Duration
Input
Voltage
Power
consumption
Charge
Duration
Operation
Battery
Lumen
output
1 h
220-240V
Max 3.5W
24 h
Non-maintained
default
Ni-MH,
7.2V 800mA
235lm
Green
Solid on
Ready/Normal operation
Flashing
Testing
Red
Solid on
Requires service
OPERATION
Maintained
During maintained operation the lamp is on both during normal operation and if the AC supply fails.
Battery is charged automatically. Add the jumper cable to change from non-maintained operation to
maintained, you can also switch light on/of.
Non-Maintained default setting
During non-maintained operation, the lamp is only lit during AC failure