-14-
MAKELSAN UPS
INSTALLATION
4.2 Output
1. Please refer to output installation principle when installation.
2. Position and way of connection, refer to figure 15.
3. Output power cable is designed according to load current, do not use over-thin
cable. Please refer to Table 2
4. Avoid short-circuit and overload.
5. The comparison between output current rating and output cable size is listed in
Table 2.
Model
Max. input current
Input wire
Terminal specification
1KVA
6A
3.5mm
2
5.5
6
2KVA
10A
5.5mm
2
5.5
6
3KVA
14A
5.5mm
2
5.5
6
5KVA
17A
5.5mm
2
5.5
6
6.25KVA
22A
5.5mm
2
5.5
6
10KVA
29A
8.5mm
2
8.5
9
12.5KVA
36A
8.5mm
2
8.5
9
Table 2