background image

MAJORSINE Inverter Manual / M101.4 

 

 

Page 37

 

MAJORSINE1000i-48-2U 

 

DC Input 

 

Voltage 

40-60 VDC 

Rated Current 

25 Amps 

Protection 

Fuse and DC Breaker 

Efficiency 

>85% (full linear load), 
48 VDC I/P, 230 VAC O/P 

AC Output  

 

Capacity 

1KVA / 800W 

Voltage 

208, 220, 230, 240 VAC 

Voltage Regulation 

±2% 

Frequency 

50/60Hz ± 0.2Hz 

Wave Form 

Pure Sine Wave 

THD (linear load) 

3% 120 V/100% 

THD (SPS load) 

5% 120 V/100% 

Crest Factor 

3:1 

Receptacles 

(4) IEC 320 outlets – C13 

Utility Power (Bypass) 

 

Voltage 

Nominal 230 VAC 

Frequency 

50/60± 5 Hz 

Protection 

AC Circuit Breaker 

Protection 

 

Short 

For 1 second; Switch to 

 

Bypass, then shutdown 

Overload 

105-125% for 3 minutes 

 

126-150% for 3 seconds; 

 

>150% for 1 second; 

 

Switch to bypass 

Temperature 

55±5º(Inside the case) 

Safety 

 

Safety 

CE Approved 

EMI / RFI 

FCC Class A 

Mechanical 

 

Dimensions 

17.32”W x 11.81”D x 3.46”H 

 

(440x300x88mm) 

 

2U Rackmount 

Weight 

7kg / 15.4 lbs 

Summary of Contents for Majorsine

Page 1: ...Majorsine Power Inverter INSTALLATION OPERATION MANUAL...

Page 2: ...2004 Issue 1 M101 2 January 2006 Issue 2 M101 3 August 2006 Issue 3 M101 4 March 2008 Issue 4 Copyright Notice 2008 Majorpower Corporation All rights reserved This document may not be copied in whole...

Page 3: ...Date This user s manual contains important technical instructions to be followed by qualified personnel responsible for the installation start up and maintenance of this unit It is recommended that th...

Page 4: ...of equipment to the service center The repaired or replacement unit will returned to the user freight prepaid limited to North America locations by the service center if the repair is covered under w...

Page 5: ...4 INSTALLATION 15 4 1 DELIVERY 15 4 2 INSTALLATION PROCEDURES 15 4 3 INSTALLATION TOOL KIT 16 4 4 LOCKING HARDWIRE ADAPTER 16 5 OPERATION 17 5 1 CONNECTING THE INPUT POWER 17 5 2 CONNECTING THE LOADS...

Page 6: ...RS 232 COMMUNICATION PORT GUI 31 8 TECHNICAL SPECIFICATIONS 32 MAJORSINE1000 24 2U 32 MAJORSINE1000 48 2U 33 MAJORSINE2000 48 2U 34 MAJORSINE1000 125 2U 35 MAJORSINE2000 125 2U 36 MAJORSINE1000I 48 2...

Page 7: ...l details for all models in the MAJORSINE Power Inverter family The general operation procedures are common however in some instances all or part of the information will not apply to the specific mode...

Page 8: ...s or other metal objects Use tools with insulated handles Wear rubber gloves and boots 2 2 Additional Safety Notes Upon receipt examine the shipment box for damage Notify the carrier immediately befor...

Page 9: ...g Adequate input power must be supplied to the inverter for proper use correct wiring sizes must be respected Grounding Reliable grounding of rack mounted equipment should be maintained Inverter DC po...

Page 10: ...ign the MAJORSINE series inverter features high efficiency light weight and compact design Modular Design MAJORSINE inverters use a modular design structure resulting in easy maintenance and high MTBF...

Page 11: ...put power will be diverted through the DC to AC inverter mode Once AC mains are restored the unit will revert from inverter mode to bypass mode In the second option On Line mode AC output power will b...

Page 12: ...LOAD Means that the inverter is in overload condition or that there is an output short circuit DC ABNORMAL Means that the input DC voltage is abnormal and requires verification FAULT Indicates that th...

Page 13: ...input and overload protection are integrated within the internal circuitry and neither of these faults should trip the DC breaker 3 4 Rear Panel Communication Interface MAJORSINE Inverter provides tw...

Page 14: ...s for FAULT When input DC voltage or fault occurs the internal contact relay will open close The terminal can support 5A 250VAC 3 5 Bypass Switching and Grounding SDVV 19 19 1 3 3 1 1 1 2 3 QYHUWHU 5H...

Page 15: ...nd verify the correct DC polarity connections have been made to the inverter Turn off the DC breaker before connecting the DC voltage to the input terminal The DC terminal strip will accommodate ring...

Page 16: ...2 KVA 12 AWG 12 AWG NEMA 5 20R 4 3 Installation Tool Kit Contents of the tool kit include x Poly zip bag containing twelve M4 screws and two 6 32 screws x Two large mounting brackets 23 or 24 rack mou...

Page 17: ...power consumption VA of the load being attached to the output Make sure that the total power consumption does not exceed the rated load of the inverter The load consumption can be monitored on the fr...

Page 18: ...verter will display either following message 2 Press the ON button for a minimum of one full second and Release within 10 seconds to start the system power if you press the ON key less than 1 second t...

Page 19: ...F 60 V 118 Chang Setting Yes ON No OFF O P FREQ 60HZ SEL D Sure ON O P VOL 120V SEL D Sure ON Press the ON key for entry into programming pages 10SEC Time Out Start Up Sequence INVERTER On Press the O...

Page 20: ...creen A Output voltage Shows present output voltage OUTPUT VOLT V B Inverter voltage Shows present inverter voltage INVERTER VOLT V C Output frequency Shows present output frequency OUTPUT FREQ Hz D B...

Page 21: ...ut current Shows present output current OUTPUT CURRENT A H Output VA Shows present output Volt Amp OUTPUT VA VA I Output power Shows present output power Watt OUTPUT POWER W J Temperature Shows the te...

Page 22: ...is normal and INVERTER output voltage is from DC to AC inverter LCD shows INVERTER ON BYPASS STD BY b When the output is from input bypass AC LCD shows INVERTER STD BY BYPASS ON c When the INVERTER is...

Page 23: ...temperature inside the INVERTER is too high LCD shows AMBIENT OVER TEMPERATURE d When the INVERTER output is in short circuit detection mode LCD shows INVERTER SHORT CIRCUIT e When the INVERTER output...

Page 24: ...age is normal LCD shows BYPASS AC NORMAL b When the input bypass voltage is normal and INVERTER output is in bypass mode LCD shows INVERTER STD BY BYPASS ON c When the input bypass voltage is too low...

Page 25: ...D Input DC status a When the input DC voltage is normal INPUT DC NORMAL b When the input DC voltage is under threshold the LCD shows INPUT DC LOW VOLTAGE c When the input DC voltage is over threshold...

Page 26: ...T AVAILABLE EEPROM checksum error 6 MAINTENANCE AND TROUBLESHOOTING 6 1 Maintenance Make sure that the inverter vents are not blocked Use a vacuum cleaner to clear any dust from the fan area When clea...

Page 27: ...voltage Bypass AC fail AC voltage or frequency may be out of range Inverter failure Call for service FAULT LED lights up Output was short Load may be abnormal OVERLOAD LED is ON The power drawn from...

Page 28: ...t Load Sensing short condition High Temperature Overload Indicator includes The AC power drawn from the inverter exceeded the load rating of the inverter See Section 8 TECHNICAL SPECIFICATIONS DC Abno...

Page 29: ...64 5Hz AC Bypass Recovery From Over Voltage 115Vac 125Vac 130Vac 135Vac AC Bypass Recovery From Under Voltage 85Vac 95Vac 100Vac 105Vac For 200VAC system O P 208Vac O P 220Vac O P 230Vac O P 240Vac AC...

Page 30: ...rmally Open 7 2 SNMP Expansion Card Slot WEB Remote monitoring is a prime consideration and requirement to manage multiple network elements from a central location SNMP remote access as easy as instal...

Page 31: ...output load input dc voltage and temperature 3 Coupled with PC software application port provides scheduled on off function for inverter Inverter monitoring data will be transmitted by local RS 232 c...

Page 32: ...m Pure Sine Wave THD linear load 3 120 V 100 THD SPS load 5 120 V 100 Crest Factor 3 1 Receptacles 4 NEMA 5 20 R outlets Utility Power Bypass Voltage Nominal 120 VAC Frequency 50 60 5 Hz Protection AC...

Page 33: ...ve THD linear load 3 120 V 100 THD SPS load 5 120 V 100 Crest Factor 3 1 Receptacles 4 NEMA 5 15 R outlets Utility Power Bypass Voltage Nominal 120 VAC Frequency 50 60 5 Hz Protection AC Circuit Break...

Page 34: ...ve THD linear load 3 120 V 100 THD SPS load 5 120 V 100 Crest Factor 3 1 Receptacles 4 NEMA 5 20 R outlets Utility Power Bypass Voltage Nominal 120 VAC Frequency 50 60 5 Hz Protection AC Circuit Break...

Page 35: ...Wave THD linear load 5 120 V 100 THD SPS load 3 120 V 100 Crest Factor 3 1 Receptacles 4 NEMA 5 15 R outlets Utility Power Bypass Voltage Nominal 120 VAC Frequency 50 60 5 Hz Protection AC Circuit Bre...

Page 36: ...Wave THD linear load 5 120 V 100 THD SPS load 3 120 V 100 Crest Factor 3 1 Receptacles 4 NEMA 5 20 R outlets Utility Power Bypass Voltage Nominal 120 VAC Frequency 50 60 5 Hz Protection AC Circuit Bre...

Page 37: ...THD linear load 3 120 V 100 THD SPS load 5 120 V 100 Crest Factor 3 1 Receptacles 4 IEC 320 outlets C13 Utility Power Bypass Voltage Nominal 230 VAC Frequency 50 60 5 Hz Protection AC Circuit Breaker...

Page 38: ...THD linear load 3 120 V 100 THD SPS load 5 120 V 100 Crest Factor 3 1 Receptacles 4 IEC 320 outlets C13 Utility Power Bypass Voltage Nominal 230 VAC Frequency 50 60 5 Hz Protection AC Circuit Breaker...

Page 39: ...MAJORSINE Inverter Manual M101 4 Page 39 Drawing No MPXXXNX02ABX...

Page 40: ...n play card configuring your network IP address and attaching the network interface cable Locking Hardwire Adapter Reliable locking NEMA 5 15 plug to secure load circuits to the output sockets of the...