User manual

User manual

8. TROUBLESHOOTING PROCEDURE

If the Power supply does not deliver voltage :

•  Check mains presence on the mains terminal strip

•  Check the fuses

•  Check the voltage value on output terminals

•  The voltage on the battery cables must be identical to that of the load

•  Check that each 12 Vdc battery has a voltage greater than or equal to 11.5 Vdc

•  Repeat the measurement after having disconnected the load and the battery

•  Recheck the signalling of the indicator lights (see chapter 5)

•  If all the steps are validated, check the compatibility of your load

If the battery indicator light remains red :

•  Check if the battery voltage is between 12Vdc and 30Vdc

•  Check the battery voltage polarity

If the battery does not take over after a mains fault :

•  Check the voltage on the battery terminals

•  Check the battery fuse

•  Check the voltage on output terminals

If the indicator lights are not illuminated :

•  Check mains presence on the mains terminal strip

•  Check the battery connection

•  Check that the wire ribbon is properly connected

•  Check the voltage on output terminals

For additional technical assistance, contact Majorcom :

+ 33 (0) 5 61 31 86 87

Model

AES24V MS40

AES24V MS150

Dimensions (W x D x H)

483 x 395 x 89mm

Weight

3,1kg

5,4kg

9. TECHNICAL SPECIFICATIONS

Summary of Contents for AES24V MS40

Page 1: ...l a Fl a mb re 31300 To u l o u s e FR ANCE T l 33 0 5 61 31 86 87 Fax 33 0 5 61 31 87 73 co mmerc i a l ma j o rco m fr w w w majorcom fr User manual AES24V MS40 AES24V MS150 POWER SUPPLY UNITS USER...

Page 2: ...d EMC directives immunity and emission It is compliant with standards EN60950 1 2006 EN61000 6 1 2007 EN61000 6 2 2006 EN61000 6 3 2007 EN61000 6 4 2007 and EN 55022 class B 2007 It is also compliant...

Page 3: ...tage Default 1 2 3 Model AES24V MS40 AES24V MS150 Power voltage 195 264VAC 50 60Hz Primary Current 1A 195VAC 2A 195VAC Breaker Circuit D curve need to be provided Upstream Model AES24V MS40 AES24V MS1...

Page 4: ...e battery mesh every 4 hours The trigger threshold of the fault is 50 m 10 The trigger threshold of the fault is 13 m 10 Exceeding this threshold is signalled by a battery fault and means that the pow...

Page 5: ...User manual User manual 4 COMMISSIONING Connect the battery wires to the terminal strip but do not connect the battery terminals After the electrical connections are made mains loads and batteries 1...

Page 6: ...ry test is performed in the following manner every 30 seconds for the first 20 minutes after commissioning every 15 minutes after the first 20 minutes If a fault is detected the test is performed ever...

Page 7: ...ed clean and ensure that it is installed in a dry and ventilated location We shall in no case be liable for damages associated with improper use or incorrect maintenance of the equipment WARNING Repla...

Page 8: ...or equal to 11 5 Vdc Repeat the measurement after having disconnected the load and the battery Recheck the signalling of the indicator lights see chapter 5 If all the steps are validated check the co...

Page 9: ...a Fl a mb re 31300 To u l o u s e FR ANCE T l 33 0 5 61 31 86 87 Fax 33 0 5 61 31 87 73 co mmerc i a l ma j o rco m fr w w w majorcom fr AES24V MS40 AES24V MS150 POWER SUPPLY UNITS User manual MAJORC...

Reviews: