Majestic STR33 Homeowner'S Installation And Operating Manual Download Page 7

7

STR Series Woodburning Fireplaces

7412961

Planning Information

Preplanning an installation is very important to ensure 
safety and to save time and money. An installer must 
predetermine where a fireplace will be set and how the 
chimney system will be run.

NOTE:

 STR33/36 models use MHSC SK8 (2-wall) 

chimney systems. STR42 Fireplace uses only model 
11CF chimney system.

Mounting the Fireplace

A fireplace may only be mounted on the following sur-
faces:
1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed beneath 

each of the four (4) corners of the fireplace.

The fireplace 

must

 be spaced 1/2" (13 mm) from a 

combustible back wall and 1/2" (13 mm) from a com-
bustible side wall or support. (Page 14, Fig. 20)

Planning the Chimney Run

Determine how the chimney will be run, length of run 
and chimney components required to complete the 
job. (Fig. 6)  

Never

 install a chimney below minimum 

heights.

The Ten Foot Rule

Major U.S. building codes specify a minimum chimney 
height above the roof top. The “Ten Foot Rule” is a fire 
safety rule and not a draft rule.  To ensure proper draft, 
it is recommended that you always meet or exceed the 
“Ten Foot Rule,” especially when installing a termination 
on a high pitch roof.  (Fig. 7)
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the 

peak of the roof is 10' (3m) or less, the top of the 
chimney must be at least 2' (610mm) above the peak 
of the roof, but never less than 3' (914mm) in height 
above the highest point where it passes through the 
roof.

2. If a horizontal distance from the chimney to the peak 

of the roof is more than 10' (3m), a chimney height 
reference point is established on the surface of the 
roof a distance of 10' (3m) from the chimney in a 
horizontal plane.  The top of the chimney must be 
at least 2' (610mm) above the reference point, but 
never less than 3' (914mm) in height above the high-
est point where it passes through the roof.

In planning a chimney system, it is important to know:
1.  The height of a chimney is measured from the 

hearth to the exit point on the termination.

2.  A chimney cannot be offset more than 30° from a 

vertical plane.

3.  A chimney may run straight up or it may be neces-

sary to offset it to avoid obstructions.

4.  The maximum length of an angled run (total chimney 

system) is 20' (6m).  

5.  No more than 2 offsets (4 total 30˚ elbows in U.S./or 

2 total 45° elbows in Canada) per fireplace may be 
used.

6.  A guy wire stabilizer is required for chimneys extend-

ing more than 6' (1.8m) above a roof line.

Fig. 6

  Installed lengths of chimney sections.

FP705

L1

L1

LT

MODEL SK &

MODEL 11 CF

2 WALL CHIMNEY

TOTAL

LENGTH 

(LT)

INSTALLED

LENGTH 

(L1)

SK81 / 11CF1

SK818 / 11CF18

SK83 / 11CF3

SK84 / 11CF4

�����

"

�����

"

�����

"

�����

"

�����

"

�����

"

�����

"

�����

"

FP705

STR/CVR-CHIM SECT. INSTALLED LENGTH

5/28/98

AC246

Fig. 7

  Ten Foot Rule illustration.

2' Min.

2' Min.

3'

Min.

0 To 10'

3'

Min.

0 To 10'

AC246

4/1/96

Reference

Point

Summary of Contents for STR33

Page 1: ...Fireplace For Models STR33 STR36 STR42 For use in U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 7412961 12 08 Rev 19 Homeowner s Installation...

Page 2: ...mbination or assembly with a Majestic Fire places replace system notwithstanding any independent testing laboratory or other third party approval of such component parts or ac cessory Any such action...

Page 3: ...added note 9 21 99 Outside Air 14 12 C 12 G F B J 24 Total Unit Width Framing Width Will be 24 Minus 2 x Drywall Thickness 18 STR33 STR36 STR42 A 33 36 42 838mm 914mm 1067mm B 37 40 46 940mm 1016mm 1...

Page 4: ...STR36 29 17 737 mm 435 mm STR42 35 17 889 mm 435 mm FP1545 Fig 3a Hearth dimensions FP701a STR Parts ID Gas Line Access Outer Dome Outside Air Access Ledge Brackets Header Standoffs Flue Damper Contro...

Page 5: ...e and chase parts identi cation FP704 STR from FP528 7 28 98 Termination Cap Storm Collar Pan Flashing Draftstop Finish Wall Batt Insulation cut out around restop Firestop Ceiling Level Outer Dome Ref...

Page 6: ...imney exit STR Series Maximum 90 0 Minimum Without Elbows 15 6 With 2 Elbows 17 6 With 4 Elbows 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a structur...

Page 7: ...ey to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where it passes thr...

Page 8: ...HEN INSTALLING A FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL REQUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for vert...

Page 9: ...SK8 2 wall chimney systems STR Fireplaces use only model 11CF chimney system Straight Up Chimney Installation To locate the centerline of the ue put the replace in nal position and place a plumb bob f...

Page 10: ...ves restop spacer model num bers The inside dimension of the frame must be the same as the hole size selected from Figure 12 in order to provide the required air space 1 38 mm with SK8 2 51 mm with Mo...

Page 11: ...lace are noncombustible Eight 8 nailing anges are supplied with the replace found on the replace hearth To level the box and secure it rmly in place remove the nailing anges from the hearth and instal...

Page 12: ...space to chimney pipe for ceiling thickness up to 8 203 mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203mm adjustments must be made in framing to assure...

Page 13: ...ost portion of chimney sections and any adjacent combustible sur faces Fig 20 Combustible surfaces include burnable materials such as ceiling members joists ooring combustible insulation and roof stru...

Page 14: ...Firestop Spacers Finishing CAUTION All joints between the nished wall and the replace surround top sides must be sealed with non combustible material to prevent cold air leakage into the room Only no...

Page 15: ...2 12 305mm Min 12 305mm Max 6 159mm Min FP721 Fig 21 Fireplace surround ush with nished wall Mantel Clearance No Noncombustible Facing Material Finished Wall Standoff 2 x 4 Stud Noncombustible Mate ri...

Page 16: ...d for the SP40 Rt must 1 85 minimum Examples of wall shield insulation 1 Manville CERAFORM 126 K 27 1 2 inches thick 2 MHSC EH2416 K 458 1 inch thick required FP723 Fig 23 Minimum rebox dimensions fro...

Page 17: ...material Fig 24 Secure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth and hearth extension...

Page 18: ...required X of listed thickness K of listed material per inch material Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new required thickness Safety Strips Must be Over lapped 1 2 Min Minimu...

Page 19: ...OTE When installing an ANSI Z21 11 2 ventless ap pliance the nishing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rated le...

Page 20: ...embly two per replace 3049122 3030126 3032112 5 Screen Assembly four per replace 7554338 7554338 7554340 6 Screen Pulls four per replace 5584139 5584139 5584139 7a Firebrick Hearth 3100103 3102103 310...

Page 21: ...ssories for this appliance are available from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact MHSC 149 Cleveland Driv...

Page 22: ...a square cap Adaptor required Square Termination Top housing with simulated brick pattern T20B Red Tan or Black Proper adapter must be used Includes ashing Adapter Required adapters for T20B top hous...

Page 23: ...tact AIS SK SK8 with the chimney system FS2100 HT 11CF U S Chimney Components cont d Model Number Description Component Attic Insulation Shield Used to prevent insulation from coming in AIS SK SK8 con...

Page 24: ...ect safe operation We do not warrant this replace to be in compliance with your local building code Building codes vary greatly throughout the country and you should determine whether your local build...

Reviews: