Majestic STR33 Homeowner'S Installation And Operating Manual Download Page 17

17

STR Series Woodburning Fireplaces

7412961

WARNING:  HEARTH EXTENSION MUST BE IN-
STALLED IN ACCORDANCE WITH FIGURES 24 AND 
25.

Alternate noncombustible materials may be used 
providing the (total) thermal resistance (Rt value) of the 
alternate material employed is greater than or equal to 
R = 1.09. Thermal resistance (R) or thermal conductivity 
(K), may be obtained from manufacturer of the material.  
Factors are related by the formula K = 1/R.
T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity
Noncombustible material with a lower R value may 
be used, provided thickness of material is sufficiently 
greater to maintain an equivalent (total) thermal resis-
tance (Rt).

Hearth Installation

A hearth extension is required to protect a combustible 
floor in front of the fireplace. Refer to Figure 24 for mini-
mum dimensions and mounting detail.

Note:  Hearth Extension must not cover the air inlet 
opening of a fireplace.

The hearth extension described in Figure 24 must be a 
durable noncombustible material with a minimum (total) 
Rt value of 1.09; refer to Figure 25 for examples. The 
overall height (above a combustible floor), depth and 
width must be as indicated, with the extension centered 
to the fireplace opening.
The top of the insulation material must be covered with 
a noncombustible decorative covering 

or

 a piece of 

.018” minimum sheet metal, to protect hearth extension 
material.  (Fig. 24)
Secure the hearth extension to the floor to prevent 
shifting, using trim molding or other similar means at 
three (3) outer edges. Seal crack between the fireplace 
hearth and hearth extension with a noncombustible 
material. (Figs. 24 and 26)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the 

fireplace

and hearth

extension with

noncombustible

material

Safety strips 

must overlap 

���

" minimum

May install 

noncombustible 

decorative 

covering

OR

 .018" min. 

sheet metal

Fireplace 

Hearth

Combustible 

Floor

Minimum 

Insulation 

Value "R"

4" MIN.

FP714

STR/CVR

6/4/98

Firebox

Opening

A -

 Min. clearance 

to combustible

perpendicular wall

B -

 Min. clearance 

to combustible

perpendicular wall when

using noncombustible wall shield*

Side

Wall

Side

Wall

F

**

C

**

E

E

D

4" BRICK

(Example material)

Combustible material permitted within shaded area.  

 * Noncombustible wall shield requires 1" MHSC 

    EH2416 insulation (minimum R Value = 1.09) between 

    decorative noncombustible rigid covering and combustible wall.  

    Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness 

    of noncombustible surround facing.

4"

Shaded area starts

1/2" away from

edge of unit

   

K

  STR33/36 

16" 

12" 

48°  41° 

18" 

14" 

8" 

16" 

48" 

24"   

   

(406 mm)  (305 mm) 

 

 

(457 mm)  (356 mm)  (203 mm)  (406 mm)  (1219 mm)  (610 mm)

  STR42 

20" 

12" 

42°  35° 

18" 

14' 

12" 

20" 

61

¹⁄₂

24"

   

(508 mm)  (305 mm) 

 

 

(457 mm)  (356 mm)  (305 mm)  (508 mm)  (1562 mm)  (610 mm)

FP714

Fig. 24

  Combustible side wall protection and hearth extension dimensions.

Summary of Contents for STR33

Page 1: ...Fireplace For Models STR33 STR36 STR42 For use in U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 7412961 12 08 Rev 19 Homeowner s Installation...

Page 2: ...mbination or assembly with a Majestic Fire places replace system notwithstanding any independent testing laboratory or other third party approval of such component parts or ac cessory Any such action...

Page 3: ...added note 9 21 99 Outside Air 14 12 C 12 G F B J 24 Total Unit Width Framing Width Will be 24 Minus 2 x Drywall Thickness 18 STR33 STR36 STR42 A 33 36 42 838mm 914mm 1067mm B 37 40 46 940mm 1016mm 1...

Page 4: ...STR36 29 17 737 mm 435 mm STR42 35 17 889 mm 435 mm FP1545 Fig 3a Hearth dimensions FP701a STR Parts ID Gas Line Access Outer Dome Outside Air Access Ledge Brackets Header Standoffs Flue Damper Contro...

Page 5: ...e and chase parts identi cation FP704 STR from FP528 7 28 98 Termination Cap Storm Collar Pan Flashing Draftstop Finish Wall Batt Insulation cut out around restop Firestop Ceiling Level Outer Dome Ref...

Page 6: ...imney exit STR Series Maximum 90 0 Minimum Without Elbows 15 6 With 2 Elbows 17 6 With 4 Elbows 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a structur...

Page 7: ...ey to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where it passes thr...

Page 8: ...HEN INSTALLING A FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL REQUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for vert...

Page 9: ...SK8 2 wall chimney systems STR Fireplaces use only model 11CF chimney system Straight Up Chimney Installation To locate the centerline of the ue put the replace in nal position and place a plumb bob f...

Page 10: ...ves restop spacer model num bers The inside dimension of the frame must be the same as the hole size selected from Figure 12 in order to provide the required air space 1 38 mm with SK8 2 51 mm with Mo...

Page 11: ...lace are noncombustible Eight 8 nailing anges are supplied with the replace found on the replace hearth To level the box and secure it rmly in place remove the nailing anges from the hearth and instal...

Page 12: ...space to chimney pipe for ceiling thickness up to 8 203 mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203mm adjustments must be made in framing to assure...

Page 13: ...ost portion of chimney sections and any adjacent combustible sur faces Fig 20 Combustible surfaces include burnable materials such as ceiling members joists ooring combustible insulation and roof stru...

Page 14: ...Firestop Spacers Finishing CAUTION All joints between the nished wall and the replace surround top sides must be sealed with non combustible material to prevent cold air leakage into the room Only no...

Page 15: ...2 12 305mm Min 12 305mm Max 6 159mm Min FP721 Fig 21 Fireplace surround ush with nished wall Mantel Clearance No Noncombustible Facing Material Finished Wall Standoff 2 x 4 Stud Noncombustible Mate ri...

Page 16: ...d for the SP40 Rt must 1 85 minimum Examples of wall shield insulation 1 Manville CERAFORM 126 K 27 1 2 inches thick 2 MHSC EH2416 K 458 1 inch thick required FP723 Fig 23 Minimum rebox dimensions fro...

Page 17: ...material Fig 24 Secure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth and hearth extension...

Page 18: ...required X of listed thickness K of listed material per inch material Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new required thickness Safety Strips Must be Over lapped 1 2 Min Minimu...

Page 19: ...OTE When installing an ANSI Z21 11 2 ventless ap pliance the nishing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rated le...

Page 20: ...embly two per replace 3049122 3030126 3032112 5 Screen Assembly four per replace 7554338 7554338 7554340 6 Screen Pulls four per replace 5584139 5584139 5584139 7a Firebrick Hearth 3100103 3102103 310...

Page 21: ...ssories for this appliance are available from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact MHSC 149 Cleveland Driv...

Page 22: ...a square cap Adaptor required Square Termination Top housing with simulated brick pattern T20B Red Tan or Black Proper adapter must be used Includes ashing Adapter Required adapters for T20B top hous...

Page 23: ...tact AIS SK SK8 with the chimney system FS2100 HT 11CF U S Chimney Components cont d Model Number Description Component Attic Insulation Shield Used to prevent insulation from coming in AIS SK SK8 con...

Page 24: ...ect safe operation We do not warrant this replace to be in compliance with your local building code Building codes vary greatly throughout the country and you should determine whether your local build...

Reviews: