background image

13

SR/SC Series "A" Woodburning Fireplace

7412948

NOTE:

 In the U.S., it is a good idea, although not al-

ways required, to install an attic insulation shield where 
blown-in insulation is planned to be used in the attic.
Install the attic insulation shield with the flanges on its 
base extending down into the framing hole. Nail each 
corner of attic insulation shield to the framing members 
of the ceiling hole using 8d nails.  Attic shields are not 
required at the roof.

Penetrating the Roof

Run pipe to roofline. Since the chimney system must be 
vented to the out-of-doors, you 

must 

use an approved 

termination.
If a chase is used, refer to the installation manual pro-
vided with the termination cap.

Locate Chimney Centerpoint On Roof

Use same procedure detailed in locating centerpoint of 
the flue system.
Drive a nail up through roof at the center point.  This will 
determine center point on outside of the roof.

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney ter-
mination installed.  Refer to installation instructions 
provided with the chimney termination to find correct 
size of roof hole.
There must be a 1

¹⁄₂

 (38 mm) air space between out-

ermost portion of chimney sections and any adjacent 
combustible surfaces. (Combustible surfaces include 
burnable materials such as:  ceiling members, joists, 
flooring, combustible insulation and roof structures.)

WARNING:  DO NOT PACK REQUIRED AIR SPACES 
WITH INSULATION OR OTHER MATERIALS.

Mark an outline of the roof hole around the center of the 
point nail.  

NOTE:

 Hole dimensions given in the chim-

ney top installation instructions are 

horizontal 

dimen-

sions; therefore, the hole size must be marked on the 
roof accordingly.
Cover the opening of the installed chimney so debris 
cannot get into the system.
Cut and frame the hole.  It is good practice to use fram-
ing lumber that is the same size as the rafters.  Install 
the frame securely because the chimney top and flash-
ing anchored to the frame must be able to withstand 
heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your 
termination according to the 

Ten Foot Rule

, continue to 

install pipe to the predetermined height.
Check the chimney top installation instructions for 
details on how high above the roof top the chimney sec-
tions (all pipes) should extend.

FP263

Fig. 19 

 Attic shield installlation (Canadian requirement).

FP263

MBUF

5/9/96

Attic 

Insulation 

Shield

Nails

(4 required)

Attic Joist

Ceiling

Base 

Flanges

Continue Installing Pipe to Complete Run

Continue attaching pipe sections to complete system 
to next level always being careful that the pipe is firmly 
snapped locked in place before proceeding to next pipe 
section.

Chimney Supports

If chimney supports are required, they are installed 
the same as elbows.  Nail chimney support straps to 
adjacent structural framing, as shown on, Page 8, Fig. 
9. Bend straps as necessary and make sure they are 
secure so they will support the weight of the chimney. A 
chimney support is 2

¹⁄₂

" (64 mm)  long when installed. 

Consider this dimension when determining how many 
straight chimney sections are needed.

NOTE:

  Chimney supports are generally used in long 

runs in a chase installation.

Additional Ceilings

If you encounter additional ceilings, repeat same steps 
required for first ceiling installation.  Refer to firestop 
illustration on Page 12, Figure 18. 

Summary of Contents for SR/SC Series "A" SC36A

Page 1: ...SC36A SR36A SC42A SR42A For use in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 948 SR cover 11 18 97 948 SC cover 11 18 97 7412948 7 08 Rev...

Page 2: ...anufactured or approved by MHSC in combination or assembly with a Majestic Fire places replace system notwithstanding any independent testing laboratory or other third party approval of such component...

Page 3: ...ss 8 Dia 203mm 3 4 8 7 6 m m FP590 Fig 2 SC36A Series speci cations and framing SC36A Series Woodburning Fireplace Circulating Model 36 914mm 14 372mm 15 391mm 11 279mm 40 1016mm 39 1006mm 3 76mm 5 8...

Page 4: ...8 Dia 203mm 3 6 9 1 4 m m FP592 Fig 4 SC42A Series speci cations and framing SC42A Series Woodburning Fireplace Circulating Model 42 1067mm 46 1168mm 39 1006mm 5 8 16mm 5 8 1 6 m m 1 2 13mm 1 2 22 57...

Page 5: ...Collar Pan Flashing Draftstop Batt Insulation cut out around estop Firestop Ceiling Level Nailing Flange Gas Line Access both sides Electrical Access Outside Air Cover Plate Metal Safety Strips 1 2 o...

Page 6: ...C42A Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a struc...

Page 7: ...to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where it passes throu...

Page 8: ...FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL RE QUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for vertical chimney he...

Page 9: ...ri cal wire through listed cable clamp leaving approxi mately six 6 inches of wire exposed through the EB1 Secure listed cable clamp to the wire Attach white wire from power source to one 1 wire of re...

Page 10: ...gh a straight up chimney arrangement is to be used Mea sure your offset dimension from straight up chimney center point on ceiling Ceiling Chimney Hole Possible Obstructions The size of the hole in ce...

Page 11: ...on top of the replace Install the pipe as pictured in Figure 16 When you get a good lock you will hear the pipe clearly snap together Once sections are snap locked in place it is extremely dif cult t...

Page 12: ...cer with the ange on the top of the framed hole and the angled portion extending down into the hole Firestop spacers are not available for nor are they re quired on vertical walls DO NOT put any seala...

Page 13: ...tructions are horizontal dimen sions therefore the hole size must be marked on the roof accordingly Cover the opening of the installed chimney so debris cannot get into the system Cut and frame the ho...

Page 14: ...nd 12 305 mm from top of grille opening for circulating models Do not install a mantel face plate less than 6 159 mm from top of replace opening for radiant models and 6 159 mm from top of grille open...

Page 15: ...8mm 12 305mm Min 1 38mm 6 159mm Min 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Mantel Clearance Radiant Model No Noncombustible Facing Material Combustible Mantel and Trim Finished Wall Header Stand...

Page 16: ...al FIREPLACE HEARTH COMBUSTIBLE FLOOR MINIMUM INSULATION VALUE R 4 MIN FP594 SR SC 11 20 97 FIREBOX OPENING A Min clearance to combustible perpendicular wall B Min clearance to combustible perpendicul...

Page 17: ...al resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is suf ciently greater to maintain an equivalent to...

Page 18: ...ce the nishing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rated less than 100 000 BTU Hr Gas pipe installation is intend...

Page 19: ...er replace 20005487 20005631 5 Screen Pulls 5584139 5584139 6a Firebrick Hearth 20005621 20005421 6b Firebrick Rear 20005627 20005462 6c Firebrick Right Side 20005626 20005461 6d Firebrick Left Side 2...

Page 20: ...insurance Glass Door Standard Bi Fold door set Brushed Brass nish 36GDKBBSR SR SC36A 42GDKBBSR SR SC42A Black nish 36GDKBKSR SR SC36A 42GDKBKSR SR SC42A Polished Brass nish 36GDKDPSR SR SC36A 42GDKDPS...

Page 21: ...ate chimney through CT100 a chase top Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required Chase Top Housing Low pro le pyrami...

Page 22: ...ation Shield Used to prevent insulation from coming in AIS SK contact with the chimney system SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN 1 Long roof SK84CAN 4 Long 45 Ch...

Page 23: ...re dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this replace to be in compliance with your local bui...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: