background image

12

SR/SC Series "A" Woodburning Fireplace

7412948

Continue installing the pipe as required until pipe is 
installed up through the ceiling.  At this point, you must 
install a firestop spacer.

Installing the Firestop Spacer

 in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly 
and required for safety.
Nail the firestop spacer (at each corner) to the framing 
members of the ceiling hole. 

NOTE: 

 A firestop spacer 

is not required at the roof.
Hole sizes listed in Figure 13 for angled firestop spac-
ers provide minimum required air space to chimney 
pipe for ceiling thickness up to 8" (203 mm).  When 
combined thickness of ceiling material, ceiling joists and 
flooring material exceeds 8" (203 mm), adjustments 
must be made in framing to assure that minimum air 
spaces to chimney are maintained.

Proper Firestop Spacer Installation

Figure 18 shows different installation procedures for  
both an area that 

is

 an attic and  an area that 

is not

 an 

attic.
If the area above the ceiling

 is not 

an attic, position the 

firestop spacer with the flange on the ceiling side and 
the angled portion extending up into the hole.
If the area above the ceiling 

is

 an attic, position the 

firestop spacer with the flange on the top of the framed 
hole and the angled portion extending down into the 
hole.
Firestop spacers are not available for nor are they re-
quired on vertical walls.

DO NOT 

put any sealant around the area where the 

outer pipe slides through the firestop spacer.  If you seal 
this area,

 it may cause a fire hazard.

Canadian Requirements 

for Insulation Shield

In Canada, an attic insu-
lation shield is required 
to prevent attic insulation 
from contacting the chim-
ney section. 

NOTE:

 If the 

attic insulation shield is 
used, the firestop is not 
required in the attic instal-
lation. Framing dimen-
sions for the chimney 
hole should measure 
14

¹⁄₂

" x 14

¹⁄₂

" (368 x 368 

mm).  An attic shield 
MUST be installed on top 
of attic joists (above the 
floor level).  (Fig. 19) 

UP

FP558

BR

11/10/97

FP558

Fig. 16 

 Install pipe, listening for the snap-lock to fasten.

Pipe Section

Pipe 

Rim

Hem

Pipe 

Rim

Lance

FP270/271

CR Series

2/19/99   djt

Elbow Strap

Angled Strap

Fig. 17 

 Attach straps to a structural framing member.

FP270/271

Support Structure

Elbow Strap

(must be tight)

Ceiling Hole 

Framing

Angle Firestop

Chimney Support Strap

(must be tight)

Fig. 18 

 Installing firestop spacer.

FP593

FP593

SR/C

11/20/97

Attic Installation

Ceiling Installation

Nails (4)

Firestop 

Spacer

Joist

Joist

Firestop 

Spacer

Nails (4)

NOTE:

 If the attic insulation shield is used, the 

firestop is not required in the attic installation.

Summary of Contents for SR/SC Series "A" SC36A

Page 1: ...SC36A SR36A SC42A SR42A For use in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 948 SR cover 11 18 97 948 SC cover 11 18 97 7412948 7 08 Rev...

Page 2: ...anufactured or approved by MHSC in combination or assembly with a Majestic Fire places replace system notwithstanding any independent testing laboratory or other third party approval of such component...

Page 3: ...ss 8 Dia 203mm 3 4 8 7 6 m m FP590 Fig 2 SC36A Series speci cations and framing SC36A Series Woodburning Fireplace Circulating Model 36 914mm 14 372mm 15 391mm 11 279mm 40 1016mm 39 1006mm 3 76mm 5 8...

Page 4: ...8 Dia 203mm 3 6 9 1 4 m m FP592 Fig 4 SC42A Series speci cations and framing SC42A Series Woodburning Fireplace Circulating Model 42 1067mm 46 1168mm 39 1006mm 5 8 16mm 5 8 1 6 m m 1 2 13mm 1 2 22 57...

Page 5: ...Collar Pan Flashing Draftstop Batt Insulation cut out around estop Firestop Ceiling Level Nailing Flange Gas Line Access both sides Electrical Access Outside Air Cover Plate Metal Safety Strips 1 2 o...

Page 6: ...C42A Maximum 90 0 90 0 Minimum Without Elbows 12 6 12 6 With 2 Elbows 14 6 14 6 With 4 Elbows 21 0 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a struc...

Page 7: ...to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where it passes throu...

Page 8: ...FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL RE QUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for vertical chimney he...

Page 9: ...ri cal wire through listed cable clamp leaving approxi mately six 6 inches of wire exposed through the EB1 Secure listed cable clamp to the wire Attach white wire from power source to one 1 wire of re...

Page 10: ...gh a straight up chimney arrangement is to be used Mea sure your offset dimension from straight up chimney center point on ceiling Ceiling Chimney Hole Possible Obstructions The size of the hole in ce...

Page 11: ...on top of the replace Install the pipe as pictured in Figure 16 When you get a good lock you will hear the pipe clearly snap together Once sections are snap locked in place it is extremely dif cult t...

Page 12: ...cer with the ange on the top of the framed hole and the angled portion extending down into the hole Firestop spacers are not available for nor are they re quired on vertical walls DO NOT put any seala...

Page 13: ...tructions are horizontal dimen sions therefore the hole size must be marked on the roof accordingly Cover the opening of the installed chimney so debris cannot get into the system Cut and frame the ho...

Page 14: ...nd 12 305 mm from top of grille opening for circulating models Do not install a mantel face plate less than 6 159 mm from top of replace opening for radiant models and 6 159 mm from top of grille open...

Page 15: ...8mm 12 305mm Min 1 38mm 6 159mm Min 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Mantel Clearance Radiant Model No Noncombustible Facing Material Combustible Mantel and Trim Finished Wall Header Stand...

Page 16: ...al FIREPLACE HEARTH COMBUSTIBLE FLOOR MINIMUM INSULATION VALUE R 4 MIN FP594 SR SC 11 20 97 FIREBOX OPENING A Min clearance to combustible perpendicular wall B Min clearance to combustible perpendicul...

Page 17: ...al resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R value may be used provided thickness of material is suf ciently greater to maintain an equivalent to...

Page 18: ...ce the nishing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rated less than 100 000 BTU Hr Gas pipe installation is intend...

Page 19: ...er replace 20005487 20005631 5 Screen Pulls 5584139 5584139 6a Firebrick Hearth 20005621 20005421 6b Firebrick Rear 20005627 20005462 6c Firebrick Right Side 20005626 20005461 6d Firebrick Left Side 2...

Page 20: ...insurance Glass Door Standard Bi Fold door set Brushed Brass nish 36GDKBBSR SR SC36A 42GDKBBSR SR SC42A Black nish 36GDKBKSR SR SC36A 42GDKBKSR SR SC42A Polished Brass nish 36GDKDPSR SR SC36A 42GDKDPS...

Page 21: ...ate chimney through CT100 a chase top Appropriate adapter required Flashing not included Adapter Kit Unites Square Chase Termination with chimney CTSK pipe required Chase Top Housing Low pro le pyrami...

Page 22: ...ation Shield Used to prevent insulation from coming in AIS SK contact with the chimney system SK8 Chimney Sections Used to build chimney systems exposed above SK818CAN 1 Long roof SK84CAN 4 Long 45 Ch...

Page 23: ...re dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this replace to be in compliance with your local bui...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: