background image

21

Majestic Royalton Series • BE36/42 • 4044-197 Installation Manual • Rev J •  09/18

Installation of a ceiling firestop is required:

•  Refer to Figures 5.5, 5.6, 5.7.

• 

 If the attic shield is pre-rolled continue.  If it is a flat part, 

try and roll it up to aid in wrapping it around the chimney.

• 

Pre-bend all the tabs in at the top to 45°.

•  Wrap the shield (around the chimney if already installed) 

until you have an overlap and the three holes on each 

side match up (large holes on top). 

•  Insert three screws into the matching holes to form a 

tube starting at the bottom.

•  Bend the tabs on the bottom of the tube inward to 90° to 

maintain chimney air space.

•  Rest the insulation shield on the ceiling firestop below.

• 

Tape off any opening around the bottom.

If you wish to make a custom shield or barrier, follow 

these guidelines:

•  Metal is preferred, although any material stiff enough to 

hold back the insulation can be used.

 WARNING! 

Risk of Fire! 

Use of cardboard or other 

materials that can deflect under humidity or other envi

-

ronmental conditions is not recommended.

•  The  shield  or  barrier  must  be  tall  enough  to  extend 

above the insulation and prevent blown-in insulation from 

spilling into the cavity.

•  Maintain specified air spaces around chimney.

•  Check instructions and local codes for further details.

Insert three 

screws

Pre-bend the tabs to 
rest against pipe to 
prevent insulation 
from falling in.

(5)Tabs bent 

in 90° 

Figure 5.5  Prepare Attic Insulation Shield

F.  Install Attic Insulation Shield

WARNING! Risk of Fire! 

You MUST install an attic insu-

lation shield when there is any possibility of insulation or 

other combustible material coming into contact with the 

chimney. 
• 

DO NOT

 pack insulation between the chimney and the 

attic insulation shield. 

•  Failure to keep insulation and other materials away from 

chimney pipe could cause fire.

• 

DO NOT

 offset chimney inside insulation shield.

•  Combustible material may come into contact with the attic 

insulation shield as long as the required clearances are 

maintained to the chimney pipe.

  Double-check the Chimney Assembly

Continue assembling the chimney sections up through 

the  ceiling  firestops  as  needed.  While  doing  so,  be 

aware  of  the  height  and  unsupported  chimney  length 

limitations given under Section 5.
Check each section by pulling up slightly from the top 

to ensure proper engagement before installing the suc

-

ceeding sections. If they have been connected correct

-

ly, they will not disengage when tested.

Figure 5.6  Install Attic Insulation Shield (firestop above ceiling)

5 Tabs bent

in 90°

Tabs bent in to 

rest against pipe

Attic Insulation Shield

Ceiling Firestop

10-1/2 in.

(267 mm)

14-1/2 in. (368 mm)

diameter

Insulation

Insulation

Pipe

Pipe

2 in. (51 mm)

air space

Seal with tape

5 Tabs bent

in 90°

Tabs bent in to 

rest against pipe

Attic Insulation Shield

Ceiling Firestop

10-1/2 in.

(267 mm)

14-1/2 in. (368 mm)

diameter

Insulation

Insulation

Pipe

Pipe

2 in. (51 mm)

air space

Seal with tape

Figure 5.7  Install Attic Insulation Shield (firestop below ceiling)

Summary of Contents for Royalton BE36

Page 1: ...d other flammable materials away INSTALLER Leave this manual with party responsible for use and operation OWNER Retain this manual for future reference BE36 BE42 NOTICE DO NOT discard this manual DO N...

Page 2: ...e 11 D Frame the Fireplace 12 E Secure and Level the Fireplace 12 F Protective Metal Hearth Strips 13 G Outside Air Kit optional 14 4 Chimney and Termination Requirements A Chimney Requirements 15 B O...

Page 3: ...oud is installed properly per instructions Fi i hi S ti 7 P 27 Dealer Distributor Phone Serial Roof flashing installed Termination installed Hearth Home Technologies recommends the following Comments...

Page 4: ...e following materials Wood Compressed paper Plant fibers Plastic Plywood OSB Sheet rock drywall Any material that can ignite and burn flame proofed or not plastered or un plastered 1 Product Specific...

Page 5: ...ion cap Chimney penetrates roof preferably without affecting roof rafters Offset Return with hanger straps Framing headed off in ceiling joists Enclosed space above and around fireplace Mantel and sur...

Page 6: ...Clearances Section 3 NOTICE A minimum 1 2 in air clearance at the back and sides of the fireplace assembly must be main tained Chimney sections at any level require a 2 in minimum air space clearance...

Page 7: ...ighest point of the roof Wind loading possible Multi level Roofs Windward Leeward Recommended Location Above peak Recommended Insulated exterior chase in cooler climates Recommended Location Above pea...

Page 8: ...Keep fire place dry Remove fireplace and components from packaging and inspect for damage Vent system components and doors are shipped in separate packages Report to your dealer any parts damaged in s...

Page 9: ...in 359 mm 18 3 4 in 476 mm 21 in 533 mm 7 1 2 in 191 mm 9 1 4 in 235 mm 7 1 2 in 191 mm Gas Knockout Outside Air 9 1 4 in 235 mm Gas Knockout 7 1 2 in 191 mm 39 1 2 in 1003 mm C D B 21 3 8 in 543 mm...

Page 10: ...als Minimum Clearances to Combustibles WITHIN ENCLOSURE AREA Fireplace to backwall 1 2 in 13 mm Fireplace to sidewall 1 2 in 13 mm Top standoffs to header 0 in 0 mm Door opening to sidewall 12 in 305...

Page 11: ...gure 3 3 Chase Assembly 1 2 3 1 Fireplace and chimney enclosed in an exterior chase 2 Chimney offset through exterior wall and enclosed in chase 3 Chase constructed on roof Note In cooler climates all...

Page 12: ...sed insulation Secure insulation and vapor barriers Provide minimum air space clearances at the sides and back of the fireplace assembly E Secure and Level the Fireplace This fireplace may be placed o...

Page 13: ...under front edge of fireplace Overlap strips in the middle of fireplace opening by 1 in 25 mm minimum Metal strips must extend beyond the front and sides of the fireplace opening by at least 2 in 51 m...

Page 14: ...inlet hood and the house with silicone to prevent air infiltration CAUTION Risk of Cuts Abrasions Wear protective gloves and safety glasses during installation Sheet metal edges are sharp CAUTION Risk...

Page 15: ...from the fireplace or at any chimney joint A Chimney Requirements Vertical distances are measured from the base of the fireplace as shown in Figure 4 1 4 Chimney and Termination Requirements Table 4...

Page 16: ...offset return You determine from the table that you need 34 1 8 in 867 mm Dimension B between the offset and return The chimney component that best fits your application is one SL324 15 degree 30 deg...

Page 17: ...See illustration above B Gas Termination Cap A Perpendicular Wall If using decorative cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decor...

Page 18: ...vertical Lock chimney sections together firmly to resist movement Ceiling firestops are required where chimney passes through ceiling or floor Support straps for offsets not shown must be secured to...

Page 19: ...turns to chimney sections Insert the screws provided through the predrilled holes Do NOT penetrate inner flue Secure chimney returns with hanger straps provided fasten to studs or joists Vertical stra...

Page 20: ...ming Note Use same dimensional lumber for framing ceiling firestop and joists 2 in 51mm clearance 2 in 51mm clearance WARNING Risk of Fire DO NOT seal area between firestop opening and chimney pipe ex...

Page 21: ...n 90 Figure 5 5 Prepare Attic Insulation Shield F Install Attic Insulation Shield WARNING Risk of Fire You MUST install an attic insu lation shield when there is any possibility of insulation or other...

Page 22: ...m Turn down Drip Edge Chase 2 in 51 mm Collar on Chase Top 018 26 ga min Galvanized Chase Top Figure 5 9 Chase Top Construction H Install Chase Chase Top You MUST use a chase top in a chase installati...

Page 23: ...o NOT block air holes Caulk gaps between storm collar pipe and storm collar chase top Termination cap pipe and chimney section must be snapped together to maintain an overlap of 1 1 2 in 38 mm Slip st...

Page 24: ...Collar 2 in 51 mm Minimum Height Remove 2 screws from front back to lift the top off Place waterproof sealer under each flange of the termination cap and on top of each screw to help prevent leaks Th...

Page 25: ...stems and termination caps 3 in 76 mm minimum Min Base Dim Min Base Dim Min Top Dim Min Top Dim Min Opening Width Min Opening Width Radiation Shield 14 1 2 in 368 mm maximum height TS345 TR344 TR342B...

Page 26: ...se Top Radiation Shield 3 in 76 mm Radiation Shield Height Termination Cap Figure 65 Roofed Style Shroud Dimensions 3 Roofed Style Shroud Radiation shield required 2 Mailbox Style Shroud Radiation shi...

Page 27: ...al 300 silicone sealant around edge of fireplace and drywall Figure 7 1 Non combustible Facing A Finishing Material Refer to Sections 1 B and Sections 1 C for combustible non combustible materials Ref...

Page 28: ...t a k value to an R value Refer to Table 7 2 for hearth extension insulation alternatives WARNING Risk of Fire Hearth extensions are to be installed only as illustrated to prevent high temperatures fr...

Page 29: ...e Metal Hearth Strip is required under the front of the fireplace Tile stone or other non combustible material Floor constructed of wood or other combustible material Fireplace Opening 4 in 102 mm min...

Page 30: ...e hearth framing must be constructed of non combustible materials such as metal framing or equivalent material and placed on HX3 s HX4 s or equivalent material When creating the platform allow for the...

Page 31: ...andoffs Measured from top of fireplace opening 12 in 305 mm 1 1 2 in 38 mm maximum 12 in 305 mm minimum 6 in 152 mm minimum Combustible Decorative Facing Seal joint with non combustible sealant Non co...

Page 32: ...n 305 mm 11 1 4 in 286 mm FLUSH FRONT 4 in 102 mm BRICK FRONT 5 0 a n g l e 39 angle Grid represents 1 scale Figure 7 11 Mantel Leg Surround or Wall Projection acceptable on both sides of opening E Si...

Page 33: ...as Log Lighter Provision WARNING Fire and or Asphyxiation Risk Use with solid wood fuel or decorative gas appliance only Gas fire generates fumes DO NOT install unvented gas logs Damper must be locked...

Page 34: ...ney Offset Return 30 deg FS338 Ceiling Firestop Straight FS339 Ceiling Firestop 15 deg FS340 Ceiling Firestop 30 deg AS8 SL300 Straight Attic Insulation Shield 24 in 610 mm JB877 Chimney Joint Band CB...

Page 35: ...F370 Roof Flashing JB877 Chimney Joint Band 2 in 51 mm 10 1 2 in 267 mm 24 5 8 in 625 mm 27 3 8 in 695 mm 12 in 305 mm 31 in 787 mm 24 5 8 in 625 mm 12 in 305 mm TR TVK Top Vent Kit Catalog A B FS338...

Page 36: ...nstallation Manual Rev J 09 18 TR344 Round Termination Cap 15 3 4 in 400 mm TR342 Round Telescoping Termination Cap TR342 B Round Telescoping Termination Cap ST375 Square Termination Cap TS345 TS345P...

Page 37: ...Installation Manual Rev J 09 18 B A C B C A DTS134 DTS146 DTO134 DTO146 Decorative Caps DTO134 A B C in 34 20 24 mm 864 508 610 DTO146 in 46 22 7 26 mm 1168 576 660 DTS134 A B C in 34 21 18 24 mm 864...

Page 38: ...n 13 mm HX3 Hearth Extension B Optional Components LDSCP M Corner Post Kit for custom size Bifold Glass Doors DM1036 DM1042 2 Wire Ties Fastener Pack Outside Air Hood Outside Air Plate Assembly AK24 O...

Page 39: ...39 Majestic Royalton Series BE36 42 4044 197 Installation Manual Rev J 09 18 Majestic a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www majesticproducts com...

Reviews: