background image

59

Majestic  •  PEARL36STIN, PEARL36PRIN Installation Manual  •  2478-980 Rev. C  •  3/17

C. Clean the Appliance

Clean/vacuum any sawdust that may have accumulated 
inside the 

fi

 rebox or underneath in the control cavity.

Once plumbing and wiring are complete on the 

fi

 replace, 

the lower access panel may be closed until the time that 
the splatter guard must be removed for 

fi

 ring the appliance.

To Close the Lower Access Panel:

Carefully disengage the tabs from the square holes and 
bend the access panel to its original position.  Bend the 
center bottom 

fl

 ap and insert it into the bottom of the ap-

pliance.

To Remove the Splatter Guard:

Carefully grab splatter guard on or near the vertical cen-
ter on the left and right sides.  Pull outward gently, but 

fi

 rmly, taking care not to tear or remove the inserted tabs.

Figure 11.10  Securing Tabs Inside Front of Splatter Guard

Figure 11.12  Splatter Guard with Lower Access Panel Closed

Figure 11.11  Splatter Guard with Lower Access Panel Open

Summary of Contents for PEARL36PRIN

Page 1: ...rtment Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in...

Page 2: ...t Information A Vent Termination Minimum Clearances 16 B Chimney Diagram 17 C Approved Pipe 18 D Use of Elbows 19 E Measuring Standards 20 F Vent Diagrams 20 5 Vent Clearances and Framing A Pipe Clear...

Page 3: ...properly installed ___________________________ Gas Section 9 Pg 51 52 Proper appliance for fuel type ___________________________ Was a conversion performed ___________________________ Leak check perfo...

Page 4: ...her flame proofed or not or plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local...

Page 5: ...d gas fu eled heating appliance or equipment The sign shall read in print size no less than one half 1 2 in in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or loca...

Page 6: ...raming square Voltmeter Electric drill and bits 1 4 in Plumb line Safety glasses Level Reciprocating saw Flat blade screwdriver Non corrosive leak check solution 1 2 3 4 in length 6 or 8 Self drilling...

Page 7: ...uld impair safe operation DO NOT install damaged in complete or substitute components Keep appliance dry Hearth Home Technologies disclaims any responsibility for and the warranty will be voided by th...

Page 8: ...ions and clearances refer to Section 5 Figure 3 1 Appliance Dimensions PEARL36STIN B C FRONT VIEW RIGHT VIEW ELECTRICAL ACCESS GAS LINE ACCESS LEFT VIEW A P J K L K D F G H M O i N E TOP VIEW Q Locati...

Page 9: ...05 M 9 1 2 241 N 38 965 O 34 5 8 880 P 24 610 Q 38 1 8 968 Location Inches Millimeters A 37 1 8 943 B 40 1 2 1029 C 24 1 2 622 D 33 1 2 851 E 1 25 F 2 1 8 54 G 4 1 8 105 H 4 1 4 108 Figure 3 2 Applian...

Page 10: ...3 3 Decorative Front Dimensions DBM36 and CRD36 Location DBM36 Inches Millimeters A 33 7 8 860 B 21 1 2 546 C 35 7 8 911 D 1 1 2 38 E 7 1 16 179 F 30 3 4 781 G 32 1 4 819 A B C D E F G Location CRD36...

Page 11: ...meters A 32 7 16 579 B 22 9 16 573 C 35 13 16 910 D 1 3 8 35 E 6 7 8 175 F 32 1 16 816 G 33 7 16 849 END PANEL FSPIER36EP Model PEARL36PRIN FSPIER36EP Location Inches Millimeters A 20 1 8 511 B 22 9 1...

Page 12: ...s Due to high temperatures the appliance should be lo cated out of traffic and away from furniture and draperies NOTICE Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY Ill...

Page 13: ...ull width and depth DO NOT install directly on carpeting vinyl tile or any combustible material other than wood WARNING Risk of Fire Maintain specified air space clearances to appliance and vent pipe...

Page 14: ...Rough Opening Depth Rough Opening Width Clearance to Ceiling Combustible Floor Combustible Flooring End of Appliance Sides of Appliance Rough Opening Width Rough Opening Width Inches 10 9 38 1 8 23 40...

Page 15: ...ssue the inside surfaces may be sheetrocked and taped or an equivalent method may be used to achieve maximum air tightness To further prevent drafts the wall shield and ceiling fire stops should be ca...

Page 16: ...CHARGE OPENING 4 4 Termination Location and Vent Information Fire Risk Maintain vent clearance to combustibles as specified DO NOT pack air space with insulation or other materials Failure to keep ins...

Page 17: ...ctrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x...

Page 18: ...2 A for vent component information and dimensions DO NOT mix pipe fittings or joining methods from differ ent manufacturers The pipe is tested to be run inside an enclosed wall There is no requirement...

Page 19: ...or DVP or SLP elbows Figure 4 4 DVP Pipe Effective Length Rise Run Inches Millimeters Inches Millimeters DVP4 4 102 2 3 4 70 DVP6 6 152 4 1 4 108 DVP12 12 305 8 1 2 216 DVP24 24 610 17 432 DVP36 36 91...

Page 20: ...el Horizontal termination cap should have a 1 4 inch downward slant to allow any moisture in cap to be released See Figure 4 8 F Vent Diagrams Top Vent Horizontal Termination Two 45 Elbows Installatio...

Page 21: ...x 2 ft SLP 305 mm Note The PEARL II series fireplaces can adapt to SLP series vent pipe if desired When venting off the top of the unit use a DVP 2SL adapter and a minimum 48 inch vertical section of...

Page 22: ...m 2 1 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 6 ft 1 8 m 3 ft 914 mm 9 ft 2 7 m 4 ft 1 2 m 12 ft 3 7 m 5 ft 1 5 m 15 ft 4 6 m 6 ft 1 8 m 18 ft 5 5 m V1 H1 50 ft 15 2 m Maximum H1 18 ft 5 5 m M...

Page 23: ...Maximum Elbow only 1 ft 305 mm 6 in 152 mm 1 ft 305 mm 6 in 152 mm 1 ft 305 mm 6 in 152 mm 3 ft 914 mm 6 in 152 mm 2 ft 610 mm 1 ft 305 mm 3 ft 914 mm 1 ft 305 mm 6 ft 1 8 m 1 ft 305 mm 6 ft 1 8 m 2...

Page 24: ...Not allowed 6 in 152 mm Not allowed 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 3 ft 914 mm 3 ft 914 mm 4 ft 1 2 m 4 ft 1 2 m 5 ft 1 5 m 5 ft 1 5 m 6 ft 1 8 m 6 ft 1 8 m V1 H1 H2 H3 50 ft 15 2 m...

Page 25: ...mm Top Vent Vertical Termination No Elbow NOTE If installing a vertical vent termination off the top of the appli ance the optional vertical termina tion baffle should be used V1 Figure 4 14 Exhaust r...

Page 26: ...e position to set the exhaust restrictor See Figure 4 17 1 2 3 4 5 SETTINGS 1 2 3 4 5 Vertical TOP VENT REAR VENT NG LP NG LP 10 ft 1 1 1 1 1 1 1 1 20 ft 2 2 2 2 2 2 2 2 30 ft 2 2 2 2 2 2 2 2 40 ft 3...

Page 27: ...tical Termination Figure 4 18 Two Elbows H1 V1 V2 V1 H1 Maximum V2 V1 V2 Minimum Elbow Only 2 1 2 ft 762 mm 2 ft 607 mm 6 ft 1 8 m 4 ft 1 2 m 12 ft 3 7 m 6 ft 1 8 m 18 ft 5 5 m V1 V2 H1 50 ft 15 2 m M...

Page 28: ...2 V1 V2 V1 H1 H2 V2 V1 V2 Minimum H1 H2 Maximum ELBOW ONLY 1 ft 305 mm 1 ft 305 mm 1 ft 305 mm 2 ft 610 mm 2 ft 610 mm 2 ft 610 mm 4 ft 1 2 m 4 ft 1 2 m 3 ft 914 mm 9 ft 2 7 m 9 ft 2 7 m 4 ft 1 2 m 12...

Page 29: ...L36PRIN Installation Manual 2478 980 Rev C 3 17 Rear Vent Horizontal Termination Figure 4 20 Figure 4 21 No Elbow One 45 Elbow H1 H1 16 in 406 mm Maximum DO NOT use a 45 elbow in corner installations...

Page 30: ...t 1 2 m 6 ft 1 8 m 3 ft 914 mm 3 ft 914 mm 7 ft 2 1 m 9 ft 2 7 m 3 ft 914 mm 4 ft 1 2 m 10 ft 3 m 12 ft 3 7 m 3 ft 914 mm 5 ft 1 5 m 12 ft 3 7 m 15 ft 4 6 m 3 ft 914 mm 6 ft 1 8 m 15 ft 4 6 m 18 ft 5...

Page 31: ...Y H1 H2 V1 V1 Minimum H1 Maximum 1 ft 305 mm 3 ft 914 mm 2 ft 610 mm 5 ft 1 5 m 3 ft 914 mm 7 ft 2 1 m 4 ft 1 2 m 8 ft 2 4 m 5 ft 1 5 m 8 ft 2 4 m V1 H1 40 ft 12 2 m Maximum V1 Minimum H1 H2 Maximum B...

Page 32: ...1 8 m No specific restrictions on this value EXCEPT V1 H1 H2 H3 cannot exceed 50 ft 15 2 m Maximum H1 H2 H3 6 ft 1 8 m Maximum H1 Maximum V1 Minimum H2 H1 H2 Maximum 1 ft 305 mm 1 ft 305 mm 1 ft 305...

Page 33: ...ttom sides Heat Shield Wall Shield Firestop Heat Shield WALL 3 in 76 mm top clearance 1 in 25 mm clearance around vertical sections Figure 5 2 Wall Penetration Shows center of vent framing hole for to...

Page 34: ...around the vent Insulation must be kept back from the pipe to prevent overheating Figure 5 3 Installing Ceiling Firestop Figure 5 4 Installing the Attic Shield INSTALL ATTIC INSULATION SHIELDS BEFORE...

Page 35: ...tion plug and the insulation basket Attach the first vent section it will snap into place Slide the vent gasket onto the vent section and then up against the ap pliance Secure the vent gasket to the a...

Page 36: ...ttached Figure 6 6 Cut the metal retaining band Figure 6 7 Remove the seal cap Figure 6 8 Discard the seal cap insulation plug and the insulation basket Figure 6 9 Attach the first vent section it wil...

Page 37: ...revent contact with Sagging or loose insulation Insulation backing or plastic Framing and other combustible materials Block openings into the chase to prevent entry of blown in insulation Make sure in...

Page 38: ...on The factory installed non combustible board spans the distance from the top of the fireplace to the framing header This board must be used See Figure 6 13 Figure 6 13 Non combustible Board NON COMB...

Page 39: ...ous exposure rating including the slip section that connects directly to the horizontal ter mination cap Apply a bead of silicone sealant 300 F minimum con tinuous exposure rating inside the female ou...

Page 40: ...s All outer pipe joints must be sealed with high temperature silicone 300 F minimum continuous exposure rating in cluding the slip section that connects directly to the hori zontal termination cap App...

Page 41: ...of silicone sealant 300 F minimum continuous exposure rating inside the female outer pipe joint prior to joining sections Only outer pipes are sealed sealing the inner flue is not required All unit co...

Page 42: ...7 E Disassemble Vent Sections Rotate either section see Figure 7 10 so the seams on both pipe sections are aligned as shown in Figure 7 11 Pull carefully to separate the pieces of pipe Figure 7 11 Ali...

Page 43: ...NG 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Figure 7 14 insert Bolt into Brackets Figure 7 14 insert Bolt into Brackets NOTICE Failure to properly caulk the ro...

Page 44: ...ap 1 1 2 in 38 mm mini mum There are two sections of the heat shield One section is factory attached to the wall shield firestop The other section is factory attached to the cap See Figure 7 16 If the...

Page 45: ...ion of a cap shield to prevent anything or anyone from touching the hot cap NOTICE For certain exposures which require superior resistance to wind driven rain penetration a flashing kit and HRC caps a...

Page 46: ...s or near sinks Low voltage and 110 120 VAC voltage cannot be shared within the same wall box 8 8 Electrical Information ROMEX CONNECTORS Figure 8 1 Junction Box Detail NOTICE DO NOT wire 110 120 VAC...

Page 47: ...g controls Wiring errors could cause improper and dangerous operation Verify proper operation after servicing WARNING Risk of Shock Replace damaged wire with type 105 C rated wire Wire must have high...

Page 48: ...ROUND TO FIREPLACE CHASSIS WHITE ORANGE INTERMITTENT PILOT IGNITER NG HOT NEUTRAL JUNCTION BOX I S IFT CONTROL MODULE 2326 130 VALVE NG 2166 302 BLK BLACK RED GREEN ORANGE BRN RED RED WHITE WIRE ASSEM...

Page 49: ...CHASSIS WHITE ORANGE INTERMITTENT PILOT IGNITOR HOT NEUTRAL JUNCTION BOX I S IFT CONTROL MODULE 2326 130 VALVE NG 2166 302 BLK GREEN ORANGE BRN 2478 012 WIRE HARNESS 2326 132 AC MODULE CABLE 2326 152...

Page 50: ...re 8 4 for location of the temperature sensor and fan control The power supply for the appliance must be brought into the junction box Install rheostat switch in location as seen in Figure 8 4 Connect...

Page 51: ...ping and handling WARNING Risk of Fire DO NOT change valve settings This valve has been preset at the factory WARNING Risk of Fire or Explosion High pressure will damage valve Low pressure could cause...

Page 52: ...evaluated for ideal shutter settings Shutter distances may vary due to vent run fuel quality and elevation E Air Shutter Setting Air shutter settings should be adjusted by a qualified service technic...

Page 53: ...minimum sealant Refer to Figure 10 1 WARNING Risk of Fire DO NOT apply combustible materials beyond the minimum clearances Comply with all minimum clearances to combustibles as specified in this manua...

Page 54: ...n inches TO CEILING 5 10 11 12 1 13 14 15 16 17 18 19 31 9 10 11 12 8 7 6 5 4 3 25 18 MAX MIN MEASUREMENT FROM FIREPLACE OPENING TO BOTTOM OF APPLIANCE 33 1 2 IN Figure 10 2 Minimum Vertical and Maxim...

Page 55: ...ombustible Mantel Leg or Wall Projections Acceptable on both sides of opening Figure 10 7 Non Combustible Mantel Leg Acceptable on both sides of opening TOP VIEW 3 1 4 in Min 1 2 in Min Unlimited FIRE...

Page 56: ...h 10 9 Inside Any 10 10 Stop finishing material flush with opening FINISHING MATERIAL 4 IN MAXIMUM THICKNESS DOOR FINISHING MATERIAL 4 IN MAXIMUM THICKNESS 1 in MAX FINISHING MATERIAL TOP EDGE DOOR FR...

Page 57: ...ce depending on the fireplace model Splatter guards must be removed before appliance is fired WARNING Risk of Fire Close the ball valve before in stalling the splatter guard to prevent accidental ligh...

Page 58: ...right sides of splatter guard using the scored line as the guide See Figure 11 4 Step 5 Fold bottom flap along score line as indicated in Figure 11 7 and tuck into valve access area of appliance Spla...

Page 59: ...ose the Lower Access Panel Carefully disengage the tabs from the square holes and bend the access panel to its original position Bend the center bottom flap and insert it into the bottom of the ap pli...

Page 60: ...may only be placed in areas as shown in Figure 11 13 Care should be taken not to cover the lighting trail of ports near pilot assembly as shown in Figure 11 13 When placing Glowing Embers onto the bu...

Page 61: ...gure 1 Some logs are similar to others in shape or size so it is imperative to correctly identify each log The unique features for each log are described below Figure 13 Figure 14 and Figure 15 show t...

Page 62: ...log so it touches the pilot shield as shown in Figure 4 Notice the locations of the flat spots for Log 3 and Log 6 Figure 4 Log 2 Installed View From Both Sides LOG PIN LOG PIN LOG PINS LOG PINS LOG...

Page 63: ...for accurate placement of the log as shown in Figure 6 Note that the burnt end of the log is positioned in the center of the appliance Notice the location of the flat spots for Log 5 and Log 9 LOG PIN...

Page 64: ...OT SIDE LOG TOUCHES LOG TOUCHES GRATE TINE GRATE TINE 7 7 FLAT SPOT FOR LOG 8 FLAT SPOT FOR LOG 8 FLAT SPOT FOR LOG 9 FLAT SPOT FOR LOG 9 Log 6 SRV2478 704 Place Log 6 on the flat spot of Log 2 Use th...

Page 65: ...ectly over burner ports Replace ember material annually Improperly placed embers interfere with proper burner operation Placing the Ember Material Ember material is shipped with this gas appliance To...

Page 66: ...EARL36STIN PEARL36PRIN Installation Manual 2478 980 Rev C 3 17 PILOT SIDE PILOT SIDE Figure 14 Log Set Installed Figure 15 Log Set Installed PILOT SIDE PILOT SIDE Figure 13 Log Set Installed PILOT SID...

Page 67: ...t to ensure it is undamaged and inspect the glass for cracks chips or scratches DO NOT strike slam or scratch glass DO NOT operate fireplace with glass removed cracked broken or scratched Replace as a...

Page 68: ...8 in 289 mm 1 1 4 in 32 mm 9 1 4 in 235 mm 13 1 4 in 337 mm 1 2 in TYP DVP90ST 90 Elbow 10 in 254 mm 10 in 254 mm 1 in 25 mm DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height...

Page 69: ...2 in 38 mm The heat shield is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall...

Page 70: ...RF12 Roof Flashing Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADDM Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP BEK2 DVP HPC Cap Bric...

Page 71: ...133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermination Cap Highwind 14 in 356 mm 12 in 305 mm 12 1 8 in 314 mm 7 1 8 in 181 mm 8 3 4 in 222 mm 1 5 8 in 41 mm 16 7 8 in 429 mm DVP HPC High Performance Ca...

Page 72: ...Rev C 3 17 A Vent Components Diagrams continued Figure 12 5 Vent Components 13 in 330 mm 15 in 381 mm 8 1 8 in 206 mm DVP HRC SS 10 7 8 in 276 mm 10 1 2 in 267 mm 3 87 Effective Length 5 3 4 to 8 3 8...

Page 73: ...connect to the appliance and are ordered separately from PVI SLP B Contact your dealer to order 16 IN 406 mm 15 IN 381 mm 16 11 16 IN 424 mm 9 3 16 IN 233 mm 4 1 2 IN 114 mm 16 11 16 IN 424 mm 13 5 8...

Page 74: ...203 mm 4 3 8 IN 112 mm 10 IN 254 mm 5 1 4 IN 135 mm 2 1 4 IN 57 mm 9 1 2 IN 241 mm 4 3 4 IN 121 mm 2 1 4 IN 57 mm 1 1 2 IN 38 mm 6 1 4 IN 159 mm Front View Top View Side View PVLP BEK Brick Kit PVLP S...

Page 75: ...t Length SLP PIPE SLP HVS Horizontal Pipe Support SLP FS Ceiling Firestop SLP WS Wall Shield Firestop DVP SLP24 Adapter 6 1 2 in 165 mm 25 3 16 in 640 mm 8 1 16 in 205 mm 10 7 8 in 276 mm 8 7 8 in 225...

Page 76: ...eld trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield Term Cap Minimum Effective Length Maximum Effective Length Trap1 3 1 8 in 4 3 4 in 79 mm 121mm Tr...

Page 77: ...ination Kit 14 in 356 mm 14 1 16 in 357 mm 7 1 2 in 192 mm 10 3 4 in 273 mm SLP CCS BK Cathedral Ceiling Support Box Black SLP DCF BK Ceiling Firestop Black SLK SNKD Snorkel Termination Cap SLP TVHW V...

Page 78: ...6STIN PEARL36PRIN Installation Manual 2478 980 Rev C 3 17 SLP HHW2 Horizontal High Wind Termination Cap 15 IN 381 mm 12 IN 305 mm 8 IN 203 mm Figure 12 11 SLP Series Vent Components A Vent Components...

Page 79: ...feature Keep remote controls out of reach of children See your dealer if you have questions Optional Fan Follow the instructions supplied with the fan kit to operate your fan See your dealer if you h...

Reviews: