The following are important points that should be observed when installing elbows on the fireplace:
1.  The support straps of all elbows not installed directly on top of the fireplace should be nailed securely to the 

surrounding structure.  This allows the support strap to carry the weight of the chimney above the elbow 

and prevents this weight from breaking the elbow or chimney sections apart.

2.  Elbows should not be used in any combination that inclines the chimney more than 30 degrees from 

vertical.

3.  The limitations on the quantity of elbows per chimney are as follows: If the total height of the fireplace and 

chimney is—12’ - 2” or more — two elbows may be used in the chimney.  21’ - 0” or more — four elbows 

may be used in the chimney.

4.  The inclined portions of chimneys that pass through living spaces likely to be used for storage should be 

enclosed to avoid contact with and possible damage to the chimney.  The minimum air space of two inches 

between the chimney and enclosing materials must be maintained.

5.  The length of the inclined portion of chimney between elbows must not exceed 6 feet when unsupported 

or 20 feet if the chimney is supported at six-foot intervals with support such as metal support straps.

6.  When enclosing the elbows and inclined portions of the chimney, enclosing materials must be installed 

vertically to maintain the required two-inch minimum air space clearance to the chimney at the extremities 

of the offset.  It is recommended that enclosing material not follow the inclined portions of the chimney.

o

FFset

 i

nstallation

 s

equence

1.  Determine the location and amount of offset required, then select the combinations of chimney sections 

and elbows required from the offset chart.  Refer to Page 19.

2.  Install the first LE30 elbow by placing the extended flue into the mating part of the fireplace or chimney 

section.  Push down until the outside or inlet air duct of the elbow overlaps and the snaps lock the elbow 

into the fireplace or chimney section.

3.  Nail the support straps to the framing member with a minimum of two 8-penny nails per strap.
4.  Install  the  sections  of  pipe  between  elbows  until  the  proper  number  of  chimney  sections  have  been 

installed.

5.  Install the second elbow to return the run of the chimney to vertical.
6.  Nail the support straps of the second elbow to a building frame member.
7.  Continue installing the vertical portion of the chimney.
NOTE:  If the inclined portion of the chimney passes through a floor or ceiling, an LF-FS-30 firestop spacer 

should be installed to provide the firestop and support required.  Be sure proper spacing in maintained between 

the chimney and combustibles.

F

iguRe

 20

FLUE PIPE

INLET AIR PIPE

30° ELBOW

ALL FOUR SUPPORT

STRAPS MUST BE NAILED

ON TO FRAMING MEMBER

AROUND THE ELBOW WITH 

A MINIMUM OF TWO (2)

8-PENNY NAILS PER STRAP

NOTE:

ALTHOUGH BOTH HALVES OF 

THE ELBOW SET MAY HAVE

TIE STRAPS, ONLY THE TOP

HALF MUST BE SECURED. THE

BOTTOM ELBOW HALF IS NOT

REQUIRED TO BE SECURED FOR

ADDED STABILIZATION OF PIPE  

Summary of Contents for Majestic SB5400SS

Page 1: ...SB5400SS Model Residential and Outdoor Fireplace Installation Operation and Maintenance Manual This fireplace is listed by OMNI Test Laboratories for use with L Series chimney system components...

Page 2: ...ver that failure to install operate and maintain this or any other factory built fireplace properly can result in a house fire or other occurrences that could cause deaths injuries and property damage...

Page 3: ...lly recommended for use in such areas Intended Product Usage The fireplace is designed to sit directly on a combustible floor The fireplace must be installed with clearances to combustible building ma...

Page 4: ...g down to close the damper When the fireplace is not in use the damper should be closed to prevent cold air form entering the chimney as well as preventing warm air in the room from escaping up the ch...

Page 5: ...SETS 15FT MIN HEIGHT 2 30 ELBOWS 21 FT MN HEIGHT 4 30 ELBOWS 86FT MAX HEIGHT CHIMNEY SUPPORT EVERY 25 FT FIRESTOP MODEL LF FS 2 REQUIRES 17x17 FRAMING 54 STORM COLLAR MODEL LC CHIMNEY CAP ROOF FLASHIN...

Page 6: ...LCF FLAT FLASHING SHOWN OR EQUIVALENT L48 CHIMNEY SECTION 1 REQUIRED 8 FT MIN CLEARANCE AIR SPACE 1 1 2 16 MIN 27 7 8 23 1 2 28 MIN SCREENED OPENING MIN MIN 76 1 2 APPLIES WHEN GLASS DOORS ARE INSTALL...

Page 7: ...1 8 L 3 6 39 5 16 76 11 16 L SERIES CHIMNEY SECTIONS 47 5 8 47 L48 35 5 8 35 17 5 8 17 11 5 8 11 L18 L36 L12 L18 L18 34 5 8 34 LINEAR GAIN L18 L36 52 LINEAR GAIN 52 5 8 L36 L36 70 5 8 70 LINEAR GAIN 1...

Page 8: ...of the fireplace required spacing to combustible walls and some suggested fireplace locations When selecting a location choose one that is away from frequently opened doors central heat outlets or re...

Page 9: ...material free space for the chimney to pass through If the chimney is to pass through living or storage spaces be sure there is adequate space to enclose the chimney to avoid personal contact with or...

Page 10: ...ACE FLUE OUTLET HEIGHT STORM COLLAR FLASHING 612 OR 1212 LC CHIMNEY CAP FIRESTOP SPACER LF FS 2 2 AIR SPACE CLEARANCE TO COMBUSTIBLES 17 SQUARE OPENING IN JOIST 17 SQUARE OPENING IN JOIST 612 OR 1212...

Page 11: ...essive strength to support the weight of the covering materials and persons standing on it and insulating qualities equal to or better than the 1 2 covering provided by the H2068 Figure 11 Figure 12 2...

Page 12: ...developing the hearth extension materials must be firmly fastened in place Wall ties should be screwed to the face of the fireplace and imbedded in the mortar joints of brick stone or other non combus...

Page 13: ...30 degree chimney incline through ceiling or floor 17 inch firestop spacer One required at each ceiling or floor level 6 12 12 12 pitch flashing for contemporary installation 0 6 12 pitch flashing for...

Page 14: ...grounding the fireplace and chimney Chimney Installation In order to assure safe and satisfactory performance of the fireplace it is very important to properly install the chimney This is an importan...

Page 15: ...ess down until the snap locks engage Continue the process adding the chimney sections on top of each other until the chimney is at least six inches above the roof opening on all sided As the chimney s...

Page 16: ...x 20 17 x 20 5 8 17 x 21 3 8 17 x 22 1 4 17 x 23 ROOF PITCH 0 12 1 12 2 12 3 12 4 12 5 12 6 12 7 12 8 12 9 12 10 12 11 12 12 12 INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTO...

Page 17: ...minimum air space clearance to the chimney at the extremities of the offset It is recommended that enclosing material not follow the inclined portions of the chimney Offset Installation Sequence 1 Det...

Page 18: ...ROOF AND INSTALL ROUND CHIMNEY CAP OR CHIMNEY HOUSING FIRESTOP SPACER DIAGONAL CHIMNEY ENCLOSURE RISE FIRESTOP SPACER 2 AIR SPACE CLEARANCE TO COMBUSTIBLES SUPPORT STRAPS DIAGONAL CHIMNEY ENCLOSURE O...

Page 19: ...ce and slide the flashing over the chimney Adjust the chimney to assure that the proper minimum clearances are maintained 5 Nail the flashing securely in place with eight nails 6 Seal the crack betwee...

Page 20: ...1 2 101 104 107 110 112 1 2 116 118 1 2 122 4 0 0 0 0 0 0 0 1 0 1 1 0 1 1 0 2 1 0 2 1 0 2 1 3 2 1 3 2 1 3 2 4 3 2 4 3 2 4 3 5 3 0 0 0 0 0 1 0 0 1 0 0 2 0 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2...

Page 21: ...s should be at least 24 inches apart to help prevent smoke from a fireplace in use from being drawn down the chimney of a fireplace that is not in use Additional spacing between caps or staggering the...

Page 22: ...RESTOP SPACER TO OUTSIDE WALL DUCT EXTENDED TO MISS JOIST SECOND FLOOR LONGER LENGTH OF THE TUBE TO OUTSIDE INSULATION RING INSERT SHORTEST SIDE OF THE TUBE THROUGH THE FIREPLACE OUTER WRAP TO PROPERL...

Page 23: ...an exterior location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet...

Page 24: ...yond the face of the wall to which the AK 4 inlet air vent will be attached The duct may be cut with a standard pocket knife use FP 4 U duct for maximum efficiency and safety Do not use a combustible...

Page 25: ...NSI IAS AGA Z21 11 2 unvented room heater is installed in this fireplace a H2853 CANOPY must also be installed Warning Do not operate an unvented gas log set in this fireplace with the chimney removed...

Page 26: ...ming and attaching the base to the supporting floor will further reduce the possibility of such a crack developing Wall ties should be fastened to the face of the fireplace with sheet metal screws and...

Page 27: ...BLE MANTEL USE ONLY NON COMBUSTIBLE MATERIALS BELOW TOP OF SPACERS COMBUSTIBLE FRAMING MEMBERS TO TOP OF SPACERS 12 MAX 18 MIN FROM FIREPLACE OPENING TO BOTTOM OF COMBUSTIBLE MANTEL MANUFACTURER RECOM...

Page 28: ...ore expensive but a little combined with other wood goes a long way Start your fire with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods will no...

Page 29: ...quipped with glass doors close them DO NOT LEAVE CHILDREN OR PHYSICALLY OR MENTALLY HANDICAPPED OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE You ll need a minimum of three logs preferably four to...

Page 30: ...on to determine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire The chimney cap can be removed for inspection maintenance and c...

Page 31: ...he installation of the fireplace 4 Do insulate the exterior walls surrounding the fireplace to prevent excessive heat loss from the fireplace 5 Do trim the face of the fireplace only with noncombustib...

Page 32: ...hing and between the flashing roof 14 Don t dry clothing or other articles near the fireplace 15 Don t store or place flammable liquids gases or pressurized containers near the fireplace 16 Don t negl...

Page 33: ...of parts needed Technical Service Department MHSC 149 Cleveland Drive Paris KY 40361 www mhsc com 10 9 8 7 6 5 4 3 2 1 SB5400SS PART NO 047647 050918 073104 067514 052874 053127 037391 067517 N A 070...

Page 34: ...e before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or around the fireplace Also under our five year coverage we do not pay the...

Page 35: ...33 53D9028 Attention Appliance Installer Please return these Operating and Installation Instructions to the Appliance for Consumer Use...

Page 36: ...34 53D9028 AUGUST 2008 53D9028 Rev 3 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: